Sensor replacement and reuse scenarios table
Table 3: Sensor replacement and reuse scenarios
Sensor used with PCV1410,
PCV1415, PCV1420, PCV1440
Controller
Sensor replacement and
reuse scenarios
Instructions
Replace a sensor with an NS
Series Sensor
Note:
Replacing a
TE-6xxx Series Sensor
is recommended over
reusing the sensor
because it provides
a usable port at the
sensor location for
commissioning.
series sensor connected to FX-
Reuse a sensor, installing an
adapter at an FX-PCV controller
location
Reusing a TE-6xxx series sensor
AP-TMZ1600-0 (see
)
Replace a sensor with an NS
Series Sensor
TE-7710-0 Series Wireless
Transmitter and TE-7720-0
Wireless Receiver (see
)
Replace with an FX-WRZ Series
Wireless Sensor and an FX-
WRZ7860 Series One-to-One
Receiver
Replace a sensor with a TE-730
Series Sensor
)
Reuse a sensor
Reusing a TE-700 Series sensor
Sensor replacement scenario descriptions
TE-6xxx series sensor connected to FX-PCV Controller
To replace a TE-6xxx Series Sensor with a functionally equivalent NS Series Network Sensor, follow
Replacing a TE-6xxx series sensor
To reuse a TE-6xxx Series Sensor connected to an FX-PCV controller, follow the instructions in the
Reusing a TE-6xxx series sensor
section.
Replacing the sensor with an NS Series Network Sensor is preferred to reusing the TE-6xxx Series
Sensor because the NS sensor allows for easier controller commissioning. Be sure to use an
NS sensor with similar dimensions as the existing sensor in order to match the original sensor