Table 4: FX-PCG2511 and FX-PCG26 terminal blocks, functions, ratings, requirements, and
cables
Terminal block
label
Terminal
label
Function, ratings,
requirements
Determine wire size and
maximum cable length
Analog Output - Voltage
Mode (0–10 VDC)
10 VDC maximum output
voltage
10 mA maximum output
current
Required an external load of
1,000 ohms or more.
See Guideline
A
in Table 5.
OUT
n
Binary Output - 24 VAC Triac
(External Power Source only)
Connects OUT
n
to OCOM
n
when activated.
External Power Source
Requirements:
30 VAC maximum output
voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
See Guideline
C
in Table 5.
Analog Output Signal
Common
All Configurable
Outputs (COs) defined as
Analog Outputs (AOs) are
isolated from all other
commons except the Binary
Input common.
CONFIGURABLE
(Outputs)
OCOM
n
Binary Output Signal
Common
All Configurable
Outputs (COs) defined as
Binary Outputs are isolated
from all other commons,
including other CO commons.
Same as (Configurable)
OUT
n
.
FX-PCG26 General Purpose Programmable Controller Installation Instructions
22