Terminal wiring guidelines, functions, ratings, and
requirements
Input and Output wiring guidelines
The next sections provide information and guidelines about the functions, ratings, and
requirements for the controller input and output terminals; it also references guidelines for
determining proper wire sizes and cable lengths.
In addition to the wiring guidelines, observe these guidelines when wiring controller inputs and
outputs:
• Run all low-voltage wiring and cables separate from high-voltage wiring.
• All input and output cables, regardless of wire size or number of wires, should consist of
stranded, insulated, and twisted copper wires.
• Shielded cable is not required for input or output cables.
• Shielded cable is recommended for input and output cables that are exposed to high
electromagnetic or radio frequency noise.
• Inputs/outputs with cables less than 30 m (100 ft) typically do not require an offset in the
software setup. Cable runs over 30 m (100 ft) may require an offset in the input/output software
setup.