Configuring analog inputs to measure humidity
You can configure humidity on AI-2, AI-3 and AI-4. To configure the corresponding analog output, see
Configuring the analog output for
. If you only want to monitor humidity, leave the setpoint at 0% RH and do not configure an analog output.
Configuring the analog input type for humidity
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog input you want to adjust, swipe left.
4.
To configure the analog input type for humidity, tap the
Type
arrow.
5. On the
Type
screen, scroll to
Humidity
.
6.
To confirm the settings, tap the
Checkmark
icon.
Specifying the K-Factor for humidity
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog input you want to adjust, swipe left.
4. On the
ANALOG
screen, tap
K-Factor
.
5. Enter the
K-Factor
that the manufacturer provided with the sensor.
6.
To confirm the settings, tap the
Checkmark
icon.
Setting the setpoint to zero for humidity
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog input you want to adjust, swipe left.
4. On the
ANALOG
screen, tap
Setpoint
.
5. Enter zero and tap the
Checkmark
icon to confirm the settings.
Enabling the alarm and changing the alarm limits for humidity
1. On the home screen, tap the
Settings
icon.
2. On the
SETTINGS
screen, tap
Analog I/O
.
3.
To find the analog input you want to set up the alarm for, swipe left.
4. Scroll down and tap the
Alarm Setup
arrow.
5. Switch
Alarm Enabled
on.
6. Tap the
High Alarm Setpoint
arrow.
7. Enter the
High Alarm Setpoint
and tap the
Checkmark
to confirm your settings.
8. Tap the
High Warning Limit
arrow.
9. Enter the
High Warning Limit
and tap the
Checkmark
to confirm your settings.
10. Tap the
Low Warning Limit
arrow.
11. Enter the
Low Warning Limit
and tap the
Checkmark
to confirm your settings.
Naming the humidity input
Set up a name for the analog input you want to appear on the home screen. If your FMS-2000C controller is in portrait mode, you can
have up to 16 characters. If your FMS-2000C controller is in landscape mode, you can have 12 characters.
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog input you want to set up a new name for, swipe left.
4. On the
ANALOG
screen, scroll down and tap the
Name
arrow.
5. On the
Name
screen, enter a new name.
6.
To confirm the new name, tap the
Checkmark
icon.