FMS-2000C
LIT-12013504
32
Specifying the minimum temperature input
To specify the minimum temperature input for third-party pressure sensors, complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog input you want to adjust, swipe left.
4. On the
ANALOG
screen, tap the
Minimum Temperature Input
arrow.
5.
Enter the minimum temperature input specific to the sensor you are using.
6.
To confirm the new settings, tap the
Checkmark
icon.
Specifying the K-Factor for precision temperature
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3. Swipe left once to get to the
ANALOG 2
screen.
4. To specify the K-Factor, tap
K-Factor
.
5. Enter the
K-Factor
that the manufacturer provided with the sensor.
6.
To confirm the settings, tap the
Checkmark
icon.
Setting the analog output signal range for precision temperature
If you select the 0-5V, 0-10V, 0-20mA range, the analog output swings from zero to the maximum specified by the hardware DIP switch
selection. If you select the 1-5V, 2-10V, 4-20mA range, it includes an offset from zero.
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3. Swipe left once to get to the
ANALOG 2
screen.
4. On the
ANALOG 2
screen, expand
Range
and choose from the following:
•
0-5V, 0-10V, 0-20mA
•
1-5V, 2-10V, 4-20mA
5. To save the new settings, collapse
Range
.
Adjusting the setpoint for precision temperature
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3. Swipe left twice to get to the
ANALOG 2
screen.
4. On the
ANALOG 2
screen, tap the
Setpoint
arrow and enter a setpoint value.
5.
To confirm the new settings, tap the
Checkmark
icon.
Adjusting the alarm settings for precision temperature
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3. Swipe left once to get to the
ANALOG 2
screen.
4. To adjust the alarm for precision temperature, tap the
Alarm Setup
arrow.
5. On the
Alarm Setup
screen, switch
Alarm Enabled
on.
6. Tap the
High Alarm Setpoint
arrow.
7. Enter the
High Alarm Setpoint
and tap the
Checkmark
to confirm your settings.
8. Tap the
High Warning Setpoint
arrow.
9. Enter the
High Warning Setpoint
and tap the
Checkmark
to confirm your settings.
10. Tap the
Low Warning Setpoint
arrow.
11. Enter the
Low Warning Setpoint
and tap the
Checkmark
to confirm your settings.
12.
To confirm your
Alarm Setup
settings, tap the
Checkmark
icon.
Naming precision temperature for the analog input
Set up a name for the analog input configured for precision temperature you want to appear on the home screen. If your FMS-2000C
controller is in portrait mode, you can have up to 16 characters. If your FMS-2000C controller is in landscape mode, you can have 12
characters.
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3. Swipe left once to get to the
ANALOG 2
screen.
4. To set up a new name for the external thermostat, scroll down and tap the
Name
arrow.
5. On the
Name
screen enter a new name.
6.
To confirm the new name, tap the
Checkmark
icon.