FIRECLASS Fire detection system
Install the PNI800 - Network Interface Card
Installation Guide
Doc. version 2.0
33
Item
Function
J1
See Table
SW1
SW2
See Table
SW3
See Table
SW4
See Table 30. DIP switch
(Internal N-BUS address)
SW5
Reset button
XT1
FCNET connector
XP1
Slot backplane (Internal
N-BUS) connector
XP2
Auxiliary Zonal LED panel
connector (e.g. for
PNI800 in box)
XP3
Debug Port (RS232) con-
nector
XP4
Auxiliary power supply
connector (e.g. for
PNI800 in box)
XP5
Left fibre optic module
XP6
Right fibre optic module
XP7
Auxiliary JTAG port for
CPU
XP8
Auxiliary JTAG port for
CPLD
Table 18: PNI800 - Jumper, switch and terminal functions
Jumper
1-2
2-3
J1Bypass
Normal Mode* Node Bypassed
[2]
Table 19: PNI800 - J1 jumper setting
* Default.
[2] The MX-Network left and right channels are hardware-con-
nected. Set this only if the PNI800 slot card is non-opera-
tional (due to a fault or not being powered up for example).
SW1 Position
Application
1
2
OFF OFF
Gateway
ON
OFF
Bridge
ON
ON
Hub
OFF
ON
Reserved
Table 20: PNI800 - Application setting
SW1 Position
Network Baud Rate
3
4
5
ON
ON
ON
9600
OFF
ON
ON
19200
ON
OFF
ON
38400
OFF
OFF
ON
57600
ON
ON
OFF
76800
OFF
ON
OFF
115200*
ON
OFF
OFF
Reserved
OFF OFF
OFF
Reserved
Table 21: PNI800 - Network baud-rate setting
* Default.
SW1
Network Topology
Position 6
ON BUS
OFF RING*
Table 22: PNI800 - Network topology setting
* Default.
SW1
MAIN MCU FW
upgrade mode
Position 8
ON
Enabled. Mode is
activated after RESET
OFF
Disabled*
Table 23: PNI800- Main MCU FW upgrade mode enable
* Default.
SW2
Host Interface
Position 1
ON RS232
OFF
NBUS*
Table 24: PNI800 - Host Interface setting
* Default.
SW2
Emergency Display
Position 2
ON Enabled
OFF Disabled*
Table 25: PNI800 - Emergency display setting
* Default.