background image

Note: 

 The SNC is shipped with the EOL switch in the

initial factory position, 

ON

 (up) position as shown in

Figure 9. If the SNC is not a terminated device on the

FC Bus, reposition the EOL switch to the Off (down)

position.

Set the EOL switches appropriately for the FC Bus.
For the RS-485 connection, set the EOL termination to

ON

 (or install an EOL terminator) for the two devices

located at either end of each bus segment on an RS-485

Bus. Set the EOL switches to off (or do not install an EOL

terminator) for all other devices on the bus segment on

an RS-485 Bus.

Powering on the SNC

Apply power to the SNC. The device requires

approximately three minutes to start up and become

operational. See 

LED test sequence at startup

.

Startup is complete and the SNC is operational after the

HEARTBEAT LED flashes blue/purple at 1 Hz and the red

FAULT LED is off.

Disconnecting power from the SNC

Disconnect power from the SNC by removing the gray 2-

pin terminal block from the 24 V~ power terminal port on

the SNC.
When you disconnect or lose supply power from the

SNC, the SNC becomes non-operational when the power

management settings expire. The blue HEARTBEAT

LEDremains on, and the super capacitor continues to

power the SNC for approximately 30 seconds so that

volatile data can be backed up in nonvolatile memory.

The HEARTBEAT LED goes off when the data backup

completes.

Important: 

The behavior of the super capacitor

is different from backup batteries that network

engines have used in the past. For example, the

capacitor requires time to recharge after each power

cycle. The unit is not designed for frequent power

cycles over a short period of time, such as three or

four power cycles in one hour. In this scenario, the

capacitor can deplete enough so that it no longer

functions. A fully depleted capacitor can take up to

90 minutes to recharge after the SNC is plugged into

its power source.

Rotary switch dials

The SNC has 3 rotary switch dials labeled Controller

Number for setting the controller number which can be

numbered from 000 to 999. The switches are shipped

from the factory set to 000. You can use them to set a

decimal number from 000 to 999 as a unique identifier for

each SNC.

Setting the controller number

About this task:

The controller number is set using three rotary switches

and may be numbered from 000 to 999. The numbers are

ordered from left to right, most significant bit (MSB) to

least significant bit (LSB) when the controller is oriented

as shown in . In Figure 10 the switches are set to 1 2 3.

If you change the controller number, refresh the SMP

Hardware

 tab to see the change.

Figure 10: Rotary switch controller number

Troubleshooting

LED status indicators

LEDs on the front panel of the SNC indicate its functional

state. For a comprehensive list of LED functional

information, see Table 10.

LED test sequence at startup

During startup, the SNC automatically initiates a self-test

to verify correct operation of the unit. When you connect

supply power, the following LED lighting sequence occurs:
• The 

HEARTBEAT

 LED flashes blue/purple when the SNC

starts.

• The 

FAULT

 LED is solid red for approximately 30

seconds, then turns off.

• The 

USB-1|2

 LED flashes green when a supported

device is connected to either of the USB ports. The

LED turns solid red when an unsupported device is

connected. The LED is off if no device is connected.

SNC LED indication table

Table 10 describes each LED on the device. The normal states are in bold. A flicker has a fast blink rate faster than one

second and a flash has a much slower blink rate of one second.

F4-SNC Installation Guide

17

Summary of Contents for F4-SNC

Page 1: ...an navigate the display using the direction arrows back OK and menu buttons The F4 SNC25151 0x x models have a total of 40 I O points with 25 inputs and 15 outputs The F4 SNC16121 0x models have a total of 28 I O points with 16 inputs and 12 outputs The first two numbers of the product code number represent the number of inputs SNC25151 0x x and the next two numbers represent the number of outputs...

Page 2: ...e There is one micro USB port that is reserved for future use 7 Sensor Actuator SA Bus port RJ12 6 Pin Modular Jack Table 1 Physical features of the SNC25151 0x and SNC16121 0x Callout Physical features 8 Field Controller FC Bus port RJ12 6 pin Modular Jack 9 Field Controller FC Bus removable terminal block blue terminal See FC Bus terminal block for more information 10 End of Line EOL switch 11 S...

Page 3: ...rth America M4 screws Europe DIN rail option 20 3 cm 8 in DIN rail for DIN rail mount applications only Mounting Location considerations Follow these guidelines when you mount an SNC Ensure that the mounting surface can support the SNC and any user supplied enclosure Mount the SNC in the proper orientation horizontal preferred vertical acceptable Mount the SNC on an even surface in wall mount appl...

Page 4: ...appropriate rating The minimum input voltage for the SNC to operate properly is 20 VAC Use a dedicated power supply to the SNC only Do not connect any other loads to the power supply Additional loads may cause noise interference Outputs should be powered from a separate source when not using internal power Ethernet port The Ethernet port is an 8 pin RJ45 network port used to connect the SNC to Eth...

Page 5: ...quipement la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon permanente d autres dispositifs tels que des systèmes de supervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du SNC Important Do not ap...

Page 6: ... RJ12 6 position modular jack that provides a connection for the MAP or other SA Bus devices with RJ12 plugs The Sensor port is connected internally to the SA Bus terminal block See Communications Bus and supply terminal blocks functions ratings requirements and cables for more information The SA Bus port pin assignment is shown in Figure 4 and Table 2 Connecting to the SA Bus terminal 1 Connect t...

Page 7: ...onnection Label numbers 20 and 26 is the same as the 24V HOT connection Label number 02 and the COM connections Label numbers 19 and 25 are the same as the 24VAC COM connection Label number 01 These extra power connections can be used to jumper power for switched high externally sourced or switched low externally sourced Triac loads Table 5 Input and output terminals Type of Point Options Universa...

Page 8: ...delines Table 6 Terminal wiring Terminal block label Terminal labels Function ratings and requirements Determine wire size and maximum cable length 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal UI terminals Provides 100 mA total current Same as Universal inputs UI Note Use a 3 wire cable for devices that source power from the 15 V terminal Analog Input Voltage...

Page 9: ...res an external load of 1 000 Ohms or more Note The AO operates in Voltage Mode when connected to devices with impedances greater than 1 000 Ohms Devices that drop below 1 000 Ohms may not operate as intended for Voltage Mode applications See Guideline C in Table 7 AO Analog Output Current Mode 4 20 mA Requires an external load between 0 300 Ohms Note The AO operates in Current Mode when connected...

Page 10: ...ires an external load of 1000 Ohms or more See Guideline A in Table 7 CO Binary Output 24 VAC Triac External Power Source only Connects CO to CO C when activated External Power Source 30 VAC maximum voltage to load 0 5 A maximum output current 1 3 A at 25 duty cycle Maximum 6 cycles hour with M9220 BGx 3 40 mA minimum load current See Guideline C in Table 7 CONFIGURABLE Outputs CO C Analog Output ...

Page 11: ...ed wire cable N A Maximum cable length versus load current In most cases inputs outputs with cables less than 30 m 100 ft do not require an offset in the software setup Cable runs over 30 m 100 ft may require an offset in the input output software setup Use Figure 8 to estimate the maximum cable length relative to the wire size and the load current in mA when wiring inputs and outputs Figure 8 Max...

Page 12: ...mon Isolated from all other Common terminals on controller 0 8 mm to 1 5 mm 20 to 16 AWG 2 wire Note See Table 7 to determine wire size and cable lengths for cables other than the recommended cables FC Bus and SA Bus and supply power wiring guidelines Table 8 provides information about the functions ratings and requirements for the SNC communication bus and supply power terminals and guidelines fo...

Page 13: ...nput output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input self powered UI Current Input External Source isolated UI Current Input Internal Source 2 wire UI F4 SNC Installation Guide 13 ...

Page 14: ...Current Input Internal Source 3 wire UI Current Input External Source in loop UI Feedback from EPP 1000 UI Dry Contact binary input UI or BI 0 10 VDC Output to Actuator external source CO or AO 0 10 VDC Output to Actuator internal source CO or AO Current Output AO F4 SNC Installation Guide 14 ...

Page 15: ...utput switch high internally sourced Triac BO or CO 24 VAC Triac output switch low external source BO or CO Incremental control to actuator switch high internally sourced Triac BO Incremental control to actuator switch low internally sourced Triac BO Network Stat with Phone Jack Fixed Address 199 SA Bus F4 SNC Installation Guide 15 ...

Page 16: ...he Site Configuration Tool SCT as needed The default state creates I O points for all connections on the input and output terminals It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs with an initial value of 0 The default state also takes input from a Network Sensor at address 199 If there is no connected Network Sensor...

Page 17: ...In this scenario the capacitor can deplete enough so that it no longer functions A fully depleted capacitor can take up to 90 minutes to recharge after the SNC is plugged into its power source Rotary switch dials The SNC has 3 rotary switch dials labeled Controller Number for setting the controller number which can be numbered from 000 to 999 The switches are shipped from the factory set to 000 Yo...

Page 18: ...mitting only Flashing 1 blink per second 1 Hz indicates communication activity Off No devices are communicating or no controllers have been configured to work with this bus FC BUS Green On Controllers have been defined but none are communicating network engine transmitting only Flickering Data is transferring on the Ethernet connection ETH 1 and ETH 2 Green Off No communications Flashing Flash gre...

Page 19: ...the button The actions taken are as follows First press odd numbered The SNC resets and restores the factory default settings on the active partition Second press even numbered The SNC resets and makes the opposite partition the currently active partition with the factory default settings Any staged configuration files are lost If the SNC has never been imaged with a release other than the shipped...

Page 20: ... B has Rel 11 0 0 7212 Press button 7th time Active Inactive Partition A has Rel 11 0 0 7212 Partition B has Rel 11 0 0 7212 Wiring considerations and guidelines Table 12 Ethernet network rules Category Allowed maximums and rules General Star topology with network switches 2 000 m 6 600 ft for plastic or glass fiber optic with external adapter Line length and type 1000 BaseT 100 m 330 ft CAT5E cab...

Page 21: ...365 m 1 198 ft maximum bus length 152 m 500 ft maximum between an NS network sensor and the bus supervisor SNC supplying power to the sensor using bus cable connected to the SA Bus screw terminal blocks 30 m 98 ft maximum length for network sensors using bus cables connected to the 6 pin modular jack 6 Pin SA Bus port Cable length for SA Bus 366 m 1 198 ft maximum Bus Length Recommended bus cable ...

Page 22: ...ggable terminal blocks Site Management Portal SMP UI Wind River Linux Operating System Three mounting clips for direct screw mounting or for DIN Rail mounting Table 17 SNC model features F4 SNC25151 0x x F4 SNC25151 0 F4 SNC16121 0 F4 SNC16121 04 Integral Equipment Controller 40 Integral I O points 25 inputs 15 outputs 14 UI 11 BI 4 AO 7 BO 4 CO 40 Integral I O points 25 inputs 15 outputs 14 UI 11...

Page 23: ...air information If the SNC fails to operate within its specifications replace it The SNC is not a serviceable product however it does support software updates to enable feature enhancements For a replacement unit software updates or accessories contact your local Johnson Controls representative Do not open the SNC housing The SNC has no user serviceable parts inside and does not require periodic f...

Page 24: ...re conditions Operating 0 C to 50 C 32 F to 122 F Non operating 40 C to 70 C 40 F to 158 F Ambient humidity conditions Storage 5 to 95 RH 30 C 86 F maximum dew point conditions Operating 0 to 90 RH 30 C 86 F maximum dew point conditions Housing Black Polycarbonate and Acrylonitrile butadiene styrene ABS blend Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail D...

Page 25: ... 10 Mbps 8 pin RJ45 connector One FC port RJ12 6 pin port connects with 1 5 m 4 9 ft RJ12 field bus cable One SA port RJ12 6 pin port connects with 1 5 m 4 9 ft RJ12 field bus cable One optically isolated RS 485 port with a removable 4 pin terminal block One magnetically isolated FC Bus port with a removable 4 pin terminal block One SA Bus port with a removable 4 pin terminal block Two USB A ports...

Page 26: ...ordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil n...

Reviews: