FORM 145.29-IOM2 (814)
18
JOHNSON CONTROLS
DSV300B
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8200
581 1.80
647 2.16
707 2.49
765 2.85
819 3.24
870 3.60
920 3.99
967 4.38 1012 4.80 1056 5.19
8800
639 2.31
699 2.70
755 3.06
809 3.45
860 3.84
910 4.26
957 4.65 1002 5.07 1045 5.49 1087 5.94
9200
676 2.70
733 3.09
787 3.48
839 3.87
888 4.29
935 4.71
981 5.13 1025 5.58 1068 6.00 1109 6.45
9600
716 3.15
771 3.54
822 3.96
872 4.38
920 4.80
965 5.25 1010 5.70 1052 6.15 1093 6.60 1113 7.05
10000
755 3.63
807 4.05
856 4.47
904 4.92
950 5.37
994 5.82 1037 6.27 1079 6.75 1119 7.20
~
~
1. Blower perf ormance includes evaporat or coil and 2" f ilt ers
2. At higher evaporat or airf lows and wet bulb condit ions, condensat e carry-over may occur. Decrease airf low downward as necessary.
CONDENSER FAN PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
12800
735 4.41
790 4.98
843 5.55
894 6.15
944 6.78
992 7.41 1031 8.01
SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Optio nal Hi-Static Drive + 10HP
Field Supplied Lo w Static Drive
OUTDOOR
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Standard Facto ry Drive + 7.5HP
Optio nal Hi-Static Drive +7.5HP
Standard Facto ry Drive + 10HP
Summary of Contents for DSV60B-300B
Page 5: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 5 DSV TYPICAL INSTALLATION DIAGRAM ...
Page 37: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 37 APPENDIX C TYPICAL UNIT WIRING SCHEMATICS ...
Page 38: ...FORM 145 29 IOM2 814 38 JOHNSON CONTROLS ...
Page 39: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 39 ...
Page 40: ...FORM 145 29 IOM2 814 40 JOHNSON CONTROLS ...
Page 41: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 41 ...
Page 42: ...FORM 145 29 IOM2 814 42 JOHNSON CONTROLS ...
Page 43: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 43 TYPICAL VFD UNIT WIRING SCHEMATIC ...
Page 45: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 45 NOTES ...