SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4800
529 0.84
601 1.02
667 1.22
729 1.42
786 1.64
841 1.84
893 2.06
942 2.28
987 2.54 1037 2.78
5400
580 1.14
646 1.36
707 1.58
764 1.80
819 2.02
870 2.26
920 2.50
967 2.74 1012 2.98 1056 3.24
6000
610 1.42
671 1.66
729 1.90
783 2.14
835 2.40
885 2.64
933 2.90
979 3.16 1023 3.44 1066 3.70
6600
702 2.04
757 2.30
809 2.56
858 2.84
906 3.10
952 3.38
996 3.66 1039 3.96 1080 4.24 1121 4.54
7200
760 2.62
810 2.90
858 3.18
905 3.48
950 3.78
993 4.08 1035 4.38 1076 4.68 1116 5.00
~
~
1. Blower perf ormance includes evaporat or coil and 2" f ilt ers
2. At higher evaporat or airf lows and wet bulb condit ions, condensat e carry-over may occur. Decrease airf low downward as necessary.
CONDENSER FAN PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7200
642 1.78
706 2.08
766 2.40
823 2.74
877 3.08
929 3.42
979 3.78
Standard Factory Drive + 5 HP
Optional Hi-Static Drive + 5 HP
Standard Factory Drive + 3 HP
Optional Hi-Static Drive + 5 HP
Field Supplied Low St at ic Drive
OUTDOOR
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6400
592 1.38
659 1.63
721 1.96
779 2.26
835 2.58
888 2.88
942 3.02 1001 3.38 1058 3.76 1101 4.18
7200
645 1.88
706 2.18
770 2.50
818 2.84
870 3.18
920 3.52
965 3.88 1014 4.24 1065 4.61 1113 4.98
8000
698 2.46
769 2.80
808 3.14
858 3.50
907 3.88
954 4.26 1000 4.64 1044 5.02 1087 5.42 1128 5.82
8800
756 3.20
808 3.56
858 3.96
905 4.34
951 4.72
995 5.14 1038 5.54 1080 5.96 1121 6.38 1160 6.82
9600
811 4.04
859 4.44
905 4.84
950 5.26
993 5.68 1035 6.12 1076 6.56 1116 7.00 1154 7.45
~
~
1. Blower perf ormance includes evaporat or coil and 2" f ilt ers
2. At higher evaporat or airf lows and wet bulb condit ions, condensat e carry-over may occur. Decrease airf low downward as necessary.
CONDENSER FAN PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
10800
775 3.87
827 4.29
877 4.71
925 5.16
971 5.61 1016 6.06 1052 7.00
Field Supplied Lo w Static Drive
Standard Factory Drive + 5 HP
Optional Hi-Static Drive + 7.5 HP
Standard Factory Drive + 7.5 HP
OUTDOOR
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Summary of Contents for DSV60B-300B
Page 5: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 5 DSV TYPICAL INSTALLATION DIAGRAM ...
Page 37: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 37 APPENDIX C TYPICAL UNIT WIRING SCHEMATICS ...
Page 38: ...FORM 145 29 IOM2 814 38 JOHNSON CONTROLS ...
Page 39: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 39 ...
Page 40: ...FORM 145 29 IOM2 814 40 JOHNSON CONTROLS ...
Page 41: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 41 ...
Page 42: ...FORM 145 29 IOM2 814 42 JOHNSON CONTROLS ...
Page 43: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 43 TYPICAL VFD UNIT WIRING SCHEMATIC ...
Page 45: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 45 NOTES ...