FAN PERFORMANCE
DSV060B
DSV096B
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1600
408 0.13 555 0.29 652 0.38 739 0.45 819 0.54 893 0.63 963 0.71 1029 0.81
1800
459 0.20 600 0.39 689 0.48 770 0.58 846 0.66 917 0.76 984 0.86 1047 0.96
2000
510 0.25 647 0.51 729 0.61 806 0.71 877 0.81 944 0.92 1008 1.00 1069 1.14
2200
561 0.35 695 0.65 772 0.76 843 0.88 911 0.99 975 1.10 1036 1.23 1094 1.34
2400
612 0.45 745 0.83 816 0.95 883 1.07 947 1.19 1008 1.31 1066 1.44
~
~
1. Blower perf ormance includes evaporat or coil and 2" f ilt ers
2. At higher evaporat or airf lows and wet bulb condit ions, condensat e carry-over may occur. Decrease airf low downward as necessary.
CONDENSER FAN PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3100
513 0.50
615 0.65
706 0.80
790 0.98
867 1.15
938 1.33 1006 1.50
Hi-Static Drive
Standard Factory Drive 1.5 HP
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.0
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive +1.5 HP
OUTDOOR
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Standard Factory Drive + 1 HP
Field Supplied Lo w Static
Drive
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2600
496 0.28
605 0.40
701 0.50
788 0.62
868 0.74
947 0.89 1016 1.04 1045 1.19 1075 1.35 1105 1.50
2900
514 0.36
618 0.48
710 0.60
794 0.72
872 0.86
944 0.98 1017 1.12 1075 1.28 1128 1.42
~
~
3200
538 0.44
636 0.58
725 0.70
806 0.84
881 0.98
952 1.12 1018 1.26 1081 1.42
~
~
~
~
3500
571 0.56
664 0.70
748 0.84
826 0.98
898 1.14
967 1.28 1031 1.44
~
~
~
~
~
~
3800
613 0.70
700 0.86
779 1.00
853 1.16
923 1.32
989 1.48
~
~
~
~
~
~
~
~
1. Blower perf ormance includes evaporat or coil and 2" f ilt ers
2. At higher evaporat or airf lows and wet bulb condit ions, condensat e carry-over may occur. Decrease airf low downward as necessary.
CONDENSER FAN PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4400
478 0.60
560 0.78
634 0.96
702 1.14
765 1.34
824 1.54
880 1.74
Standard Factory Drive + 2 HP
Optional Hi-Static Drive + 2 HP
OUTDOOR
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Optional Hi-Static Drive + 1.5 HP
Standard Factory Drive + 1 HP
Lo w Static
Drive
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Summary of Contents for DSV60B-300B
Page 5: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 5 DSV TYPICAL INSTALLATION DIAGRAM ...
Page 37: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 37 APPENDIX C TYPICAL UNIT WIRING SCHEMATICS ...
Page 38: ...FORM 145 29 IOM2 814 38 JOHNSON CONTROLS ...
Page 39: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 39 ...
Page 40: ...FORM 145 29 IOM2 814 40 JOHNSON CONTROLS ...
Page 41: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 41 ...
Page 42: ...FORM 145 29 IOM2 814 42 JOHNSON CONTROLS ...
Page 43: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 43 TYPICAL VFD UNIT WIRING SCHEMATIC ...
Page 45: ...FORM 145 29 IOM2 814 JOHNSON CONTROLS 45 NOTES ...