18
P5417055
● Motion Sensor Setting
The operation mode for activations of functions 1 and 2 can be selected as follows:
* “ALL MODES” : Functions 1 and 2 are available when the operation mode is “COOL”, “DRY”,
“HEAT”, or “FAN”.
* “COOL + DRY” : Functions 1 and 2 are available when the operation mode is “COOL”, “DRY”,
or “FAN”.
* “HEAT”
: Functions 1 and 2 are available when the operation mode is “HEAT”.
* “OFF”
: Functions 1 and 2 are not available.
(The default setting is “ALL MODES”.)
● If absent
The operation mode for activations during the automatic capacity save operation for Function 1 can
be selected from “Running”, “Stand-by”, or “Stop” on the wired controller. It is set for the indoor unit
operation after the motion sensor detects as an absence for the set time in “Check Interval”.
* Running:
The operation continues with saving the capacity after being detected as an absence.
If human activity is detected over a period of time, normal operation is performed again.
* Stand-by:
The operation mode is the fan operating at “Slow” speed. If human activity is detected for a period of
time, normal operation is performed again.
* Stop:
The operation is stopped by the wired controller when all the indoor units with motion sensor detect an
absence that is connected with the same wired controller. If human activity is detected for a period of
time by the stoppage, normal operation is performed again.
● Check Interval
When the motion sensor detects an absence at a selected check time interval, the function “If absent”
(Function 1) is executed. The interval can be selected from choices ranging from: 30, 60, 90, 120, or
180 minutes.
(The default setting is 30 minutes.)
(1) In instances where people are gathered within or are beyond the range of the motion sensor.
The air conditioning capacity is adjusted by the automatic setting temperature correction depending on
human activity and movements of a heat source in the detecting area of the motion sensor .
● If human activity and movements of a heat source are small, the motion sensor cannnot detect them.
● If room temperature is high and there is little difference between the radiation temperature of walls, floor
space, and humans, the motion sensor may not detect increase or decrease in the number of humans.
(For example: The cooling operation is performed with a setting at 86°F (30°C) in the summer season.)
● During the “Capacity Save” and “If absent” phase of operation of Function 1, the Function 2 is unavailable.
(2) The adjusted setting temperature will return to normal setting temperature after 10 to 30 minutes,
depending on the conditions.
Function 2 Adjusting Capacity by Increase or Decrease in the Number of People
NOTICE
Cooling or Dry
Operation
Increase in the
number of people
The setting temperature is adjusted
from -2
o
F to -3
o
F (-1
o
C to -2
o
C).
Decrease in the
number of people
The setting temperature is adjusted
from +2
o
F to +3
o
F (+1
o
C to +2
o
C).
Heating
Operation
Increase in the
number of people
The setting temperature is adjusted
from -2
o
F to -3
o
F (-1
o
C to -2
o
C).
Decrease in the
number of people
The function is invalided.
5.8.2 Descriptions for Setting Items