TC-19001
1-1
SYSTEM SUMMARY
1.1 Function
Speci
fi
cation
Item
Description
(1) Model
VRF Central Touchscreen Controller: CCLX01
VRF Central Touchscreen Controller Adapter: CCXLA01 *1
Energy Calculation Software: CCSE01 *2
(2) Product Code
VRF Central Touchscreen Controller: 60292274
VRF Central Touchscreen Controller Adapter: 60292275
Energy Calculation Software: 60292276
(3) Management Range
H-LINK: 16
Groups: 2,048
Blocks: 512 *3
Areas: 512 *3
(Up to 128 Groups can be registered on 1 H-LINK)
(4) Control Function
On/Off
Mode
Set temperature
(including dual setpoint for Auto mode)
Fan speed
Louver
Remote Controller (RC) prohibition
Filter sign reset
Function selection for indoor units *4
Function selection for outdoor units *5
Capacity control for outdoor units *5
Lower noise control for outdoor units *5
(5) Monitor
On/Off
Mode
Set temperature
(including dual setpoint for Auto mode)
Air intake temperature
RC sensor temperature
Outdoor temperature *6
Fan Speed
Louver
RC prohibition
Thermo-ON information
Filter sign/Auto cleaning fault
Alarm status/Alarm codes
Setback information
(6) Display Format
Panel (7 sizes provided)
Layout
List
(7) Schedule
Weekly schedule (16 items/day)
Annual schedule (Exception day 1-5, summer/winter/regular)
(8) Displayed Item for
Usage History
Each of the following data of up to 2 years’ can be shown:
• Accumulated operation time
• Accumulated thermo-ON time
• Ave. air intake temp.
• Ave. outdoor temp.
• Ave. temp. (including dual setpoint for Auto mode)
• Ave. RC sensor temp.
(9) External In/Output
Management Point
[VRF Central Touchscreen Controller/VRF Central Touchscreen Controller Adapter]
External input: 4 (Level or pulse)
External output: 2 (Set voltage contact/ No-voltage contact on DSW)
Features
[Energy saving]
• Run/Stop
• RC prohibition
• Temperature shift
(For Cool/Dry mode: +1°F ~ +18°F (+1°C ~ +9°C))
(For Heat mode: -1°F ~ -18°F (-1°C ~ -9°C))
• Mode shift
(Mode shifted to Fan when in Cool/Dry mode,
and shifted to Stop in Heat mode)
• Capacity control on outdoor units
• Lower noise control for outdoor units
[Control/Monitor]
Controlled items:
• Run/Stop
• Mode (Cool/Heat)
Monitored items:
• Run/Stop
• Mode (Cool/Heat)
• Alarm state
[Others]
• Power consumption signal input
• Emergency stop
(10) History
• Alarm history: 10,000 records
• External In/Output history: 1,000 records
• Pulse input history: 6 months
*1. Required only when the system consists of multiple H-LINKs
*2. Required only for calculating electricity
*3. No restriction on the number of H-LINK
*4. Some indoor units may not fully support all functions.
*5. Available for applicable indoor units only
*6. This is the air intake temperature on representative outdoor unit.
Summary of Contents for CCXL01
Page 2: ......
Page 8: ...vi TC 19001...
Page 14: ......
Page 24: ...2019 Johnson Controls Inc TC 19001 Code No LIT 12013165 Issued Feb 2019...