TC-19001

 

2-3

SYSTEM SPECIFICATION

  Combination Use with Other Controllers

 Applicable 

Controllers

 Mini Central Controller: CCM01

 Large Central Controller: CCL01

NOTES:
1.  To connect RC-less indoor units to the system where 2 or more controllers are connected, 

the indoor units need to support dual setpoint.

2.  Up to 8 central controllers, including VRF Central Touchscreen Controller can be connected to 1 

H-LINK.

3.  If central controller that doesn’t support dual setpoint coexists on the same network, dual setpoint 

and setback function are unavailable on entire system.

RC Group- Registered on CCXL01 as a collection of indoor units (up to 16) connected via RC 

control line

Group- Registered on CCXL01 as a collection of multiple RC groups altogether. 
Block - Registered on CCXL01 as a collection of multiple Groups altogether. 
Area – Registered on CCXL01 as a collection of multiple Blocks altogether. 

Area

Block

Group

RC Group

ALL

H-LINK Wiring

H-LINK Wiring

Indoor

Unit

Indoor

Unit

RC

Indoor

Unit

Indoor

Unit

RC

Indoor

Unit

RC

Indoor

Unit

RC

Indoor

Unit

 Managing Range

VRF Central Touchscreen Controller, with 15 VRF Central Touchscreen Controller Adapter, can control 
up to 2,048 groups (VRF Central Touchscreen Controller Adapter (15 H-LINK) x 128 groups).  
No restriction on H-LINK to arrange Blocks and Areas.

Summary of Contents for CCXL01

Page 1: ...001 ENGINEERING MANUAL VRF Central Touchscreen Controller Engineering Manual VRF Central Touchscreen Controller CCXL01 VRF Central Touchscreen Controller Adapter CCXLA01 Energy Calculation Software CC...

Page 2: ......

Page 3: ...rovides common descriptions basic and advanced information to maintain and service this central controller which you operate as well for other models This manual should be considered as a permanent pa...

Page 4: ...or adjust any safety devices inside the indoor or outdoor units All safety features disengagement and interlocks must be in place and functioning correctly before the equipment is put into operation...

Page 5: ...and maintenance of the unit to the customer according to the information in all manuals that accompanied the system All manuals and warranty information must be given to the user Electrical Precautio...

Page 6: ...cables Secure the suspended cables at regular intervals but not too tightly Make sure that the terminals do not come into contact with the surface of the electrical box If the terminals are too close...

Page 7: ...NTS 1 System Summary 1 1 2 System Specification 2 1 2 1 Features 2 1 2 2 Example for System Configuration 2 4 2 3 Standard Specification 2 5 2 4 Appearance 2 6 IMPORTANT NOTICE AND SAFETY SUMMARY i 1...

Page 8: ...vi TC 19001...

Page 9: ...on day 1 5 summer winter regular 8 Displayed Item for Usage History Each of the following data of up to 2 years can be shown Accumulated operation time Accumulated thermo ON time Ave air intake temp A...

Page 10: ...ntral Controller Large Central Controller VRF Central Touchscreen Controller Outdoor Units Indoor Units Individual Remote Controllers Wired Controller Simplified Wired Controller IR Receiver Wireless...

Page 11: ...oller CIS01 Wireless Controller CIR01 IR Infrared Receiver Kit for 4 Way Cassette C4IRK01 IR Infrared Receiver Kit for 1 Way Cassette C1IRK01 IR Infrared Receiver Kit for Wall Mounted and Ducted CWDIR...

Page 12: ...system Central Controllers Mini Central Controller VRF Central Touchscreen Controller Large Central Controller Item H LINK II Max Number of Refrigerant Groups System 64 Address Setting Range of Indoor...

Page 13: ...2 Central Controller Configuration Example OK Menu Back Help ECO On Off A C MODE SPEED TEMP COOL LOUV Adj Meeting Room LOUV FLTR Motion Sensor ON Avoid OK Menu Back Help ECO On Off A C MODE SPEED TEMP...

Page 14: ......

Page 15: ...as an optional feature 5 Various information display styles Choose from panel layout list display depending on the number of controlled points and items to be monitored Panel Displays items that are f...

Page 16: ...Pump H Y VAHP_B21S Top Flow 208 230V Heat Pump Low Ambient Type H Y VAHP_B31CW Top Flow 460V Heat Pump Low Ambient Type H Y VAHP_B41CW Indoor Unit Ducted High Static H Y IDH_B21S H Y IDH_B22S Ducted...

Page 17: ...ntire system RC Group Registered on CCXL01 as a collection of indoor units up to 16 connected via RC control line Group Registered on CCXL01 as a collection of multiple RC groups altogether Block Regi...

Page 18: ...be available Controlling and monitoring on the system are all based on the clock on VRF Central Touchscreen Controller Correct operation may not be expected due to unnecessary clock setting change on...

Page 19: ...ication Specification Item Specification Communication Peer Indoor units Outdoor units 1 Communication Line Nonpolar Two Wires Communication Method Half Duplex Communication Synchronous Method Asynchr...

Page 20: ...YSTEM SPECIFICATION 2 6 TC 19001 2 4 Appearance Unit inch mm 14 5 8 372 1 1 4 32 5 H LINK External in output Wiring Port Power Input LAN Port SD Card Slot USB flash drive slot 1 1 8 27 8 8 15 16 227 2...

Page 21: ...via H LINK SW2 LCD power Switch RS 485 communication Yellow Currently not in use SW1 Power switch for embedded adapter POWER Green Lights while power is provided to VRF Central Touchscreen Controller...

Page 22: ...6 5 8 167 9 Screw Hole for Wall Mount H LINK External input output Wiring Port Power Input LAN Port 8 15 16 227 2 Rear View Screw Hole for Wall Mount 5 1 2 140 1 9 16 39 5 0 11 16 17 6 1 7 16 36 3 1 8...

Page 23: ...6 110 6 1 8 155 2 13 16 72 10 1 16 255 6 4 0 1 4 6 9 1 4 235 6 Status Indicator Power Button Power Line Port H LINK External in output and LAN Wiring Port Screw Hole for Wall Mount Remove rubber cover...

Page 24: ...2019 Johnson Controls Inc TC 19001 Code No LIT 12013165 Issued Feb 2019...

Reviews: