Table 15: Display specifications and technical data
Specification
Technical data
Battery
Rechargeable lithium battery, not user-replaceable
Mounting
Direct wall mount and control panel mounting kits
(See Table 14)
Display housing (protection
class)
IP66 (front), IP20 (rear)
Display dimensions (H x W x D) 7.80 in. x 11.10 in. x 2.53 in. (197 mm x 282 mm x 64 mm)
Display enclosure box 710-01
dimensions (H x W x D)
7.44 in. x 10.79 in. x 3.00 in. (189.2 mm x 274.2 mm x 76 mm)
Communication cable length
RS-485 limit of 5,000 feet (FC bus) / 1,000 feet (SA bus) for controller to SERIAL port on the display. For
FC bus applications that go further than 1,000 feet, refer to Table
. FC Bus Wire Gauge and FC Bus Baud
Rate
from the
MS/TP Communications Bus Technical Bulletin
(Table 13) for cable recommendations and
baud rate.
RJ-12 (Telephone) limit of 100 ft from MAP to controller
RJ-45 (Ethernet) limit of 328 ft from MAP to display (can be extended using Ethernet switch; refer to
Communication cable
specifications
SA Bus - RS-485 connector (field installed), 22 AWG stranded, 5-wire, two twisted pair shielded cable
FC Bus - RS-485 connector (field installed), 22 AWG stranded, 5-wire, two twisted pair shielded cable
RJ-12 (telephone style jack - 6-pin port - 24 AWG/6-wire (3 pair) solid, non-shielded Category 3 (Cat3)
for controller to MAP
RJ-45 (Ethernet style jack) - 8-pin port - Category 5 (Cat5 or Cat5e or Cat6) for MAP connection to
display
Weight
5.51 lb (2.5 kg)
Agency listing
CE - Emission EN 61000-6-4, Immunity EN 61000-6-2 for installation in industrial environments
UL - cULus: UL61010-1 / UL61010-2-201
UL - cULus: Class 1 Div 2
Table 16: MAP gateway specifications and technical data
Specification
Technical data
MAP version
MAP 5.0 and above
Ambient operating conditions
32.0–122.0°F (0.0–50.0°C)
Ambient storage conditions
-40.0 to 158.0°F (-40.0 to 70.0°C), 5–95% relative humidity 86.0°F (30.0°C) maximum dew
point conditions\
Network and serial interfaces
1 SA/FC port (6-pin port; connects with RJ-12 field bus cable on the controller)
1 Ethernet port (8-pin port; connects with RJ-45 display port)
Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units
47