Table 10: Menu navigation
Menu
Submenu
Parameters displayed
Conditions for parameter
displayed units and range
Modulating Compressor output
% (0-100)
Modulating Condenser Fan 1 Command
% (0-100)
Modulating Condenser Fan 2 Command
% (0-100)
Cooling mode enabled for operation
No, yes
Number of cooling stages installed
Occupied cooling setpoint
°F / 45–98
Unoccupied cooling setpoint
°F / 46–99
Discharge air temp setpoint configuration
Fixed, OAT reset, supply fan reset, zone temp
reset, external
Cooling discharge air temp upper setpoint
°F / 40–79
Cooling discharge air temp lower setpoint
°F / 41–80
Outside air temperature reset setpoint upper
°F / 51–111
Outside air temperature reset setpoint lower
°F / 50–99
Zone temperature reset setpoint upper
°F / 51–81
Zone temperature reset setpoint lower
°F / 50–80
Supply fan DAT setpoint high threshold
% / 0–100
Supply fan DAT setpoint low threshold
% / 0–100
Compressor 1A enabled
Yes, no
Compressor 1B enabled
Yes, no
Compressor 1C enabled
Yes, no
Compressor 2A enabled
Yes, no
Compressor 2B enabled
Yes, no
Compressor 2C enabled
Yes, no
Modulating compressor enable
Disable / enable
Circuit 1 outside air temperature cooling cutout
°F / …75
Cool
Click on
cooling setup 1
Circuit 2 outside air temperature cooling cutout
°F / …75
Morning cooldown enabled
No, yes
Morning cooldown/return air temp setpoint
°F / 50–85
Morning cooldown discharge air temp setpoint
°F / 40–69
Circuit 1 number of condenser fans
1–3
Circuit 2 number of condenser fans
1–3
Circuit 1 modulating condenser fan installed
True, false
Cool
Click on
cooling setup 2
Circuit 2 modulating condenser fan installed
True, false
Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units
33