Codes
Description
Option 1 – Touchscreen display field install
option on a unit with factory installed MAP (part
number – 2TS0401)
•
Option should be selected when the unit has a factory installed MAP.
•
BACnet MS/TP can be selected for a single touchscreen to a single RTU, or a
single touchscreen to multiple RTU.
•
BACnet IP can be selected for a single touchscreen to a single RTU only.
•
Requires field wiring and installation for the touchscreen display.
•
The touchscreen display requires a separate 115 V field supplied power source.
•
Includes the following for the touchscreen display: a wall box (for indoor
installation), 24 VDC power supply, 3-prong power cord, and the touchscreen
display.
•
Does not include communication wiring as required between the MAP,
touchscreen display, and the controller.
Option 2 – Touchscreen display field install
option on a unit without factory installed MAP
(part number – 2TS0402)
•
Option should be selected when the unit does not have a factory installed MAP.
•
BACnet MS/TP can be selected for a single touchscreen to a single RTU, or a
single touchscreen to multiple RTU.
•
BACnet IP can be selected for a single touchscreen to a single RTU only.
•
Requires field wiring and installation for the touchscreen display.
•
Provides a MAP, which must be field installed.
•
The touchscreen display requires a separate 115 V field supplied power source.
•
Includes the following for the touchscreen display: a wall box (for indoor
installation), 24 VDC power supply, 3-prong power cord, and a touchscreen
display.
•
Includes the following for the MAP installation: a MAP device.
•
Does not include communication wiring as required between the MAP,
touchscreen display, and the controller.
Note:
For detailed parts list, review Table 17
and Table 18 and wiring drawing Figure 37.
Specifications
Table 15: Display specifications and technical data
Specification
Technical data
Supply voltage
24 VDC (10–32 VDC)
Power consumption
1.0 A at 24 VDC (maximum)
Ambient operating conditions
-4.0 to 140.0°F (-20.0 to 60.0°C). Plug-in modules and USB devices may limit maximum temperature to
122.0°F (50.0°C)
Ambient storage Conditions
-4.0 to 158.0°F (-20.0 to 70.0°C), 5–85% non-condensing relative humidity
Processor
ARM Cortex-A9 Dual core 800 MHz
Memory
4 GB flash memory
Terminations
3 conductors, 1.5 mm wire size minimum
Minimum temperature conductor rating is 221.0°F (105.0°C) Universal jack connection for DC power
supply.
Standard RS-485 port for serial connection to the controller
(See
Internal wiring for adapters in the display
Ethernet port
3 ports (RJ-45)
ETH0 – 10/100/1000 Mb
ETH1 – 10/100 Mb
ETH2 – 10/100 Mb
USB port
2 ports, host V2.0, max. 500 mA
SERIAL port
1 port (RS-485 connector - DFMC 0.5/4-ST-2.54; Manufacturer: Phoenix Contacts)
SD card
Yes – slot available
Display
LED – 16 m display with 1280 x 800 pixels, WXGA resolution screen size: 10.1 in. true glass projected
capacitive multitouch 16:9
Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units
46
Johnson Controls