MECHANICAL SPECIFICATIONS

GENERAL DESCRIPTION

Units shall be factory-assembled, single packaged, Electric 
Cooling units, designed for outdoor mounted installation. ACP 
units shall have minimum SEER ratings of 13. They shall have 
built in, equal size, field convertible duct connections for down 
discharge supply/return or horizontal discharge supply/return.

The units shall be factory wired, piped, charged with R-22 
refrigerant and factory tested prior to shipment. All unit wiring 
shall be both numbered and color coded.

All units shall be manufactured in a facility certified to ISO 9001 
standards, and the cooling performance shall be rated in 
accordance with DOE and ARI test procedures. Units shall be 
certified to UL 1995/CAN/CSA C22.2 No. 236 standard.

UNIT CABINET

1.

Unit cabinet shall be constructed of galvanized steel, with 
exterior surfaces coated with a non-chalking, powered 
paint finish, certified at 1000 hours salt spray test per 
ASTM-B117 standards.

2.

The unit top shall be a single piece “Water Shed” design, 
with drip edges and no-seam corners to provide optimum 
water integrity.

3.

Unit shall have a rigidly mounted condenser coil guard to 
provide protection from objects and personnel after 
installation.

4.

Indoor blower section shall be insulated with up to 3/4” 
thick, aluminum, foil faced insulation, fastened to prevent 
insulation from entering the air stream.

5.

Cabinet panels shall be “large” size, easily removable for 
servicing and maintenance, with built-in lift handles.

6.

Unit shall be built on a formed, “Super-Structure” design 
base pan, with embossments at critical points to add 
strength, rigidity and aid in minimizing sound.

7.

Full perimeter base rails shall be provided to assure 
reliable transit of equipment, overhead rigging, fork truck 
access and proper sealing on roof curb applications. Base 
rails shall be removable, when required, to lower unit 
height.

8.

Filters shall be furnished and be accessible through a 
removable access door, sealed air tight. (Single phase 
models - accessory kit available. Three phase models - 
standard from factory.)

9.

Units vertical discharge and return duct configuration shall 
be designed to fit between standard 24” O.C. beams 
without modification to building structure, duct work and 
base unit.

10. Condensate pan shall be internally sloped and conform to 

ASHARE 62-89 self-draining standards, with ¾” NPTI 
copper, ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

1.

The ACP fan motor shall be direct drive, 5 speed design.

2.

Fan wheel shall be double-inlet type with forward-curved 
blades, dynamically balanced to operate smoothly 
throughout the entire range of operation. Airflow design 
shall be constant air volume.

3.

Bearings shall be sealed and permanently lubricated for 
longer life and no maintenance.

4.

Fan assembly shall be “Slip Track” (slide-out) design for 
easy removal and cleaning.

OUTDOOR (CONDENSER) FAN ASSEMBLY

1.

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to 
corrosion resistant steel spider bracket and shall be 
statically balanced for smooth operation.

2.

The outdoor fan motor shall be totally enclosed with 
permanently lubricated bearings and internally protected 
against overload conditions.

REFRIGERANT COMPONENTS

1.

Compressors:

a. Shall be fully hermetic reciprocating type, direct drive,

internally protected with internal high-pressure relief and
over temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or -
10% of the unit nameplate voltage.

b Shall have internal isolation and sound muffling to

minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.

2.

Coils:

a. Evaporator and condenser coils shall have aluminum

plate fins mechanically bonded to seamless internally-
enhanced copper tubes with all joints brazed.

b Evaporator and Condenser coils shall be of the direct

expansion, draw-thru design.

3.

Refrigerant Circuit and Refrigerant Safety Components 
shall include:

a. Independent fixed-orifice or balanced port bi-flow TXV

expansion devices.

b. Filter/strainer to eliminate any foreign matter.

c. Accessible service gage connections on both suction

and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge and without
disrupting condenser or evaporator air flow.

d The refrigeration system shall provide at least 10° F of

liquid sub-cooling at design conditions.

4.

Unit Controls:

Summary of Contents for ACP024

Page 1: ...r flexibility and needs to carry less inventory LOWER INSTALLATION COST Installation time and costs are reduced by easy power and control wiring connections The small base dimension means less space is required on the ground or roof plus the installer can fit this unit between the wheel wells of a full size pick up truck All models are well under 500 pounds All units are completely wired charged w...

Page 2: ...WIRING DIAGRAM 460 3 60 POWER SUPPLY ACP MODELS 28 LIST OF TABLES Tbl Pg 1 PHYSICAL DATA 5 2 RATINGS ARI 5 3 COOLING CAPACITIES 2 TON ACP024 6 4 COOLING CAPACITIES 2 1 2 TON ACP030 8 5 COOLING CAPACITIES 3 TON ACP036 10 6 COOLING CAPACITIES 3 1 2 TON ACP042 12 7 COOLING CAPACITIES 4 TON ACP048 14 8 COOLING CAPACITIES 5 TON ACP060 16 9 SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE 17 10 ADDITIONAL ...

Page 3: ...n does not disrupt neighboring areas and does not dry out vegetation surrounding the unit The warm air from the top mounted fan is blown up away from the structure and any landscaping This allows compact location on multi unit applications CONDENSER COIL GRILLE A multi piece totally enclosed rigidly mounted condenser coil grille provides protection from objects and personal after installation and ...

Page 4: ...r duct mounted side supply return and unit mounted down supply return applications Damper capable of providing 0 thru 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly RECTANGLE TO ROUND ADAPTERS Kit includes one supply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over current duct openings on the base unit Tran...

Page 5: ... FINS PER INCH 20 20 20 20 20 20 FACE AREA Sq Ft 12 9 12 9 12 9 12 9 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 4 10 5 9 5 0 4 12 6 0 10 8 FILTER FACE AREA Sq Ft Qty Size 2 14 1 14 x 22 COMPRESSOR HERMETIC QTY 1 Type Recip Rotary Scroll Scroll Scroll Scroll 3 4 3 4 TABLE 2 RATINGS ARI Model ACP Cooling1 Capacity 80 67 95 F Sound Rating2 decibels Electric Heat Nom Capacity KW single phase Electric Heat...

Page 6: ...2 1 8 19 6 17 0 14 4 11 7 26 6 2 0 20 7 17 5 14 4 11 2 67 26 9 1 8 25 0 23 8 19 7 17 1 14 4 25 7 2 0 23 4 22 8 19 7 16 5 13 3 62 25 9 1 8 25 0 25 0 24 6 22 0 19 4 16 7 24 5 1 9 23 4 23 4 23 2 20 1 16 9 13 8 57 25 0 1 8 25 0 25 0 25 0 22 3 19 7 17 1 23 4 1 9 23 4 23 4 23 4 20 3 17 1 14 0 95 F 105 F 600 77 26 3 2 1 12 2 9 7 7 1 24 6 2 3 11 8 9 2 6 5 72 24 9 2 1 16 3 13 8 11 2 8 7 22 6 2 3 15 7 13 0 ...

Page 7: ...16 7 13 2 9 6 6 1 15 9 2 5 15 8 15 8 15 1 11 6 7 7 3 9 57 17 7 2 3 17 7 17 7 17 7 14 2 10 6 7 1 15 9 2 5 15 9 15 9 15 9 12 3 8 4 4 6 900 72 21 7 2 5 18 1 16 1 12 2 8 2 19 8 2 7 16 3 15 7 11 5 7 3 67 19 0 2 4 18 1 18 1 16 8 12 8 8 9 16 5 2 5 16 3 16 3 15 9 11 7 7 5 62 18 6 2 4 18 1 18 1 17 6 13 6 9 7 5 8 16 4 2 5 16 3 16 3 16 0 11 8 7 6 3 4 57 18 1 2 4 18 1 18 1 18 1 14 1 10 2 6 3 16 3 2 5 16 3 16 ...

Page 8: ...4 0 20 6 17 2 13 8 32 3 2 3 24 8 20 9 17 0 13 1 67 32 8 2 2 31 8 26 5 23 1 19 7 16 3 31 2 2 4 29 9 26 9 23 0 19 1 15 2 62 32 0 2 1 31 8 31 8 31 6 28 2 24 7 21 3 29 9 2 3 29 9 29 9 29 7 25 8 21 9 18 0 57 31 8 2 0 31 8 31 8 31 8 28 4 25 0 21 6 30 0 2 2 30 0 30 0 30 0 26 1 22 2 18 3 95 F 105 F 750 77 31 8 2 5 14 8 11 8 8 8 30 8 2 7 14 3 11 2 8 1 72 30 3 2 5 19 8 16 8 13 7 10 7 28 8 2 6 19 1 15 9 12 8...

Page 9: ...8 22 6 18 5 14 4 10 2 20 4 3 0 20 4 20 4 20 4 16 7 12 1 7 8 57 23 1 2 8 23 1 23 1 22 4 18 3 14 1 10 0 20 8 3 0 20 8 20 8 20 8 16 2 11 6 7 3 1125 72 25 8 3 0 22 3 19 9 14 5 9 9 23 2 3 2 19 6 19 6 13 8 8 9 67 23 5 2 9 22 3 22 3 20 0 15 5 10 9 20 5 3 1 19 6 19 6 19 1 14 3 9 5 62 22 3 2 8 22 3 22 3 22 3 17 7 13 1 8 6 19 7 3 0 19 7 19 7 19 7 15 1 10 2 5 4 57 22 7 2 8 22 7 22 7 22 7 17 7 13 2 8 6 20 0 3...

Page 10: ... 31 2 24 9 18 6 43 5 3 1 36 4 30 1 23 8 17 6 67 43 3 2 8 43 3 38 6 32 4 26 1 19 8 40 5 3 1 40 5 37 4 31 1 24 8 18 5 62 39 7 2 7 39 7 39 7 39 7 33 4 27 2 20 9 36 9 2 9 36 9 36 9 36 9 30 6 24 4 18 1 57 37 2 2 9 37 2 37 2 37 2 30 9 24 6 18 3 35 3 3 0 35 3 35 3 35 3 29 0 22 7 16 4 95 F 105 F 1000 77 42 6 3 1 20 5 16 7 12 8 39 3 3 4 19 2 15 5 11 9 72 38 9 3 1 26 3 22 4 18 6 14 8 35 7 3 3 24 7 21 1 17 4...

Page 11: ...27 8 27 8 27 8 22 3 16 8 11 3 24 9 3 8 24 9 24 9 24 9 19 4 13 5 7 8 57 27 6 3 5 27 6 27 6 27 6 22 1 16 6 11 1 25 1 3 8 25 1 25 1 25 1 19 6 13 7 8 0 1375 72 34 3 3 8 31 1 25 3 19 4 13 6 30 8 4 0 30 1 24 2 18 3 12 3 67 30 8 3 7 30 8 30 8 25 8 20 0 14 1 27 6 3 9 27 6 27 6 24 5 18 5 12 6 62 28 0 3 6 28 0 28 0 28 0 22 2 16 3 10 5 25 2 3 8 25 2 25 2 25 2 19 3 13 3 7 3 57 27 9 3 6 27 9 27 9 27 9 22 0 16 ...

Page 12: ... 5 30 3 25 1 20 0 47 3 3 5 35 1 29 8 24 4 19 1 67 46 2 3 1 42 5 37 8 32 7 27 5 22 4 43 9 3 5 40 3 37 3 32 0 26 6 21 3 62 43 3 3 1 42 5 42 5 42 0 36 9 31 7 26 6 40 5 3 4 40 3 40 3 39 8 34 5 29 1 23 8 57 42 5 3 0 42 5 42 5 42 5 37 3 32 1 27 0 40 3 3 3 40 3 40 3 40 3 35 0 29 6 24 3 95 F 105 F 1050 77 47 9 3 8 22 6 18 4 14 3 45 4 4 2 21 5 17 3 13 1 72 44 2 3 7 29 1 25 0 20 9 16 8 41 7 4 1 28 3 24 1 19...

Page 13: ...2 2 32 2 27 0 21 8 16 6 29 8 4 8 29 8 29 8 29 8 25 4 19 9 14 5 57 33 0 4 4 33 0 33 0 33 0 27 8 22 6 17 4 30 7 4 8 30 7 30 7 30 7 26 2 20 6 15 2 1400 72 39 5 4 7 31 2 25 8 20 3 14 9 36 7 5 1 29 9 24 7 19 1 13 5 67 35 6 4 6 32 4 32 4 27 8 22 3 16 9 32 8 5 0 29 9 29 9 26 7 21 1 15 6 62 32 4 4 5 32 4 32 4 32 4 26 9 21 4 15 9 29 9 4 9 29 9 29 9 29 9 24 8 19 0 13 5 57 33 1 4 5 33 1 33 1 33 1 27 7 22 2 1...

Page 14: ... 39 4 31 0 22 7 55 5 3 9 47 1 38 7 30 3 21 9 67 53 6 3 4 53 6 48 5 40 1 31 8 23 4 50 5 3 8 50 5 47 3 38 9 30 6 22 2 62 49 2 3 4 49 2 49 2 49 2 40 8 32 5 24 1 45 8 3 8 45 8 45 8 45 8 37 5 29 1 20 7 57 47 8 3 9 47 8 47 8 47 8 39 5 31 1 22 7 44 1 3 7 44 1 44 1 44 1 35 8 27 4 19 0 95 F 105 F 1200 77 53 8 4 0 26 4 21 9 17 3 50 5 4 5 24 9 20 5 16 1 72 48 9 4 0 33 1 28 5 23 9 19 3 45 6 4 5 31 3 26 9 22 5...

Page 15: ...4 7 34 7 34 7 27 7 20 7 13 6 31 4 5 5 31 4 31 4 31 4 24 3 16 8 9 5 57 34 7 4 9 34 7 34 7 34 7 27 7 20 6 13 6 32 3 5 6 32 3 32 3 32 3 25 3 17 7 10 4 1800 72 44 8 5 2 41 0 33 3 25 6 18 0 41 2 5 7 39 7 32 0 24 2 16 4 67 39 5 5 2 39 5 39 5 33 2 25 5 17 9 35 9 5 7 35 9 35 9 31 5 23 7 16 0 62 35 1 5 1 35 1 35 1 35 1 27 5 19 8 12 2 31 7 5 6 31 7 31 7 31 7 24 1 16 2 8 4 57 35 1 5 0 35 1 35 1 35 1 27 4 19 ...

Page 16: ... 39 5 33 2 26 8 66 0 4 8 45 5 38 9 32 3 25 7 67 64 6 4 3 56 9 50 5 44 2 37 8 31 5 61 4 4 8 56 5 49 9 43 3 36 7 30 1 62 60 4 4 3 60 4 60 4 54 7 48 3 42 0 35 7 57 0 4 7 57 0 57 0 53 3 46 7 40 1 33 5 57 58 0 4 3 58 0 58 0 58 0 51 6 45 3 38 9 54 9 4 7 54 9 54 9 54 9 48 3 41 7 35 1 95 F 105 F 1500 77 65 5 5 0 29 0 23 4 17 8 62 8 5 6 28 3 22 7 17 1 72 60 5 5 0 38 7 33 1 27 5 21 9 57 4 5 6 37 6 32 0 26 4...

Page 17: ...Bh Total Capacity1 MBh Total Input kW 2 Sensible Capacity MBh CFM WB F Return Dry Bulb F Return Dry Bulb F 90 85 80 75 70 65 90 85 80 75 70 65 TABLE 9 SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE Model No ACP Blower Speed Setting External Static Pressure Inches Water Gauge 0 2 0 4 0 6 0 8 1 0 CFM W RPM CFM W RPM CFM W RPM CFM W RPM CFM W RPM 024 2 0 Low 1 726 87 632 629 99 739 Low Medium 2 768 97...

Page 18: ... 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08 1500 0 04 0 05 0 04 0 09 1600 0 04 0 06 0 05 0 10 1700 0 05 0 07 0 05 0 11 1800 0 05 0 07 0 06 0 11 1900 0 06 0 08 0 06 0 11 2000 0 07 0 08 0 07 0 12 048 4 0 1100 0 03 0 01 0 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08 1500 0 04 0 05 0 04 0 09 1600 0 04 0 06 0 05 0 10 1700 0 0...

Page 19: ... POWER WIRING 24 VOLT TRANSFORMER UNIT TERMINAL STRIP THERMOSTAT NOTE HEAT ANTICIPATOR SHOULD BE SET AT 0 25 AMPS FOR ALL MODELS CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing PROGRAMMABLE THERMOSTAT ONLY Minimum wire size of 18 AWG wire should be used for all field installed 24...

Page 20: ...25 11 3 15 1 31 4 36 1 44 3 50 2 45 60 460 3 60 5 8 45 9 0 8 2 1 None 10 1 15 2NH04501046 10 1 12 17 6 20 2NH04501546 15 1 18 25 1 30 042 3 5 208 230 1 60 21 1 115 33 1 2 6 0 None 33 6 45 2NH04500506 3 8 5 1 18 3 20 8 33 6 33 6 45 45 2NH04500706 5 6 7 5 2 26 9 31 3 41 2 46 6 50 50 2NH04501006 7 5 10 2 36 1 41 7 52 6 59 6 60 60 2NH04501506 11 3 15 2 54 3 62 5 75 4 85 6 80 90 208 230 3 60 13 4 89 21...

Page 21: ...0 60 2NH04502025 15 20 2 41 7 48 1 61 6 69 6 70 70 2NH04502525 18 8 25 2 52 1 60 1 74 7 84 7 80 90 460 3 60 8 4 70 13 1 3 3 8 None 15 6 20 2NH04501046 10 1 12 19 8 20 2NH04501546 15 1 18 27 3 30 2NH04502046 20 2 24 1 34 8 35 2NH04502546 25 2 30 1 42 3 45 1 Minimum Circuit Ampacity 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit breaker size installed at factory or fie...

Page 22: ...ERALL 4 1 2 UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN DIA KNOCKOUT HIGH VOLTAGE CONN DIA KNOCKOUT REFRIGERANT CONNECTIONS A UNIT SIZE DIMENSION A 024 042 33 048 060 41 CLEARANCES Minimum Front 12 Back 0 Left Side Filter Access 24 Right Side 24 Below Unit 1 0 Above Unit 2 36 For...

Page 23: ...1 048 384 379 103 90 87 99 060 500 495 135 117 113 130 26 FRONT OF UNIT A B C D CENTER OF GRAVITY TABLE 13 CLEARANCES Unit Clearances Minimum Front 12 Back 0 Left Side Filter Access 24 Right Side 24 Below Unit1 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 0 Above Unit2 2 Units must be installed outdoors Overhanging structures or shrubs shou...

Page 24: ...POWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT SUPPLY AIR DUCT RETURN AIR DUCT CONTROL WIRING TO INDOOR THERMOSTAT TO POWER SUPPLY FIELD SUPPLIED DISCONNECT SWITCH MOUNTED ON UNIT ROOF CURB INSTALLATION REAR DUCT ...

Page 25: ...TED PANELS 22 14 OPENING FOR RETURN AIR DUCT OPENING FOR SUPPLY AIR DUCT RECOMMENDED DUCT SIZE SUPPLY AIR DUCT x RETURN AIR DUCT x UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FRAME COUNTERFLASHING INSULATION CANT STRIP ROOF DECK AND ROOFING MATERIAL INSULATION AND ROOFING MATERIAL x 1 WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES 14 1 ...

Page 26: ...279815 PTG D 0408 26 Johnson Controls Unitary Products FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY ACP MODELS ...

Page 27: ...279815 PTG D 0408 Johnson Controls Unitary Products 27 FIGURE 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY ACP MODELS ...

Page 28: ...279815 PTG D 0408 28 Johnson Controls Unitary Products FIGURE 11 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY ACP MODELS ...

Page 29: ...on shall be designed to fit between standard 24 O C beams without modification to building structure duct work and base unit 10 Condensate pan shall be internally sloped and conform to ASHARE 62 89 self draining standards with NPTI copper ridged mount connection INDOOR EVAPORATOR FAN ASSEMBLY 1 The ACP fan motor shall be direct drive 5 speed design 2 Fan wheel shall be double inlet type with forwa...

Page 30: ... shall have a primary limit control s and automatic reset to prevent the heating element system from operating at an excessive temperature 3 The heating section assembly shall slide out of the unit for easy maintenance and service 4 Units with electric heating sections shall be wired for a single point power supply with branch circuit fusing where required UNIT OPERATING CHARACTERISTICS 1 Unit sha...

Page 31: ...279815 PTG D 0408 Johnson Controls Unitary Products 31 ...

Page 32: ... change without notice Printed in U S A 279815 PTG D 0408 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 279815 PTG C 1007 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...

Reviews: