DESCRIPTION

These packaged cooling air conditioners are designed for 
outdoor installation. Only utility and duct connections are 
required at the point of installation.

Field-installed electric heater accessories are available to 
provide electric heat combined with electric cooling.

STANDARD FEATURES / BENEFITS

OPERATING EFFICIENCY -

 All ACP units provide high 

operating efficiencies and have a SEER up to 13.

ON SITE FLEXIBILITY -

 All model sizes share a common, 

compact design cabinet with a single footprint. The installer has 
the flexibility of setting one curb and placing the proper tonnage 
unit on that curb after the internal load has been determined. 
Field convertible duct connections from side shot to down shot 
allows the installer to have greater flexibility and needs to carry 
less inventory.

LOWER INSTALLATION COST -

 Installation time and costs 

are reduced by easy power and control wiring connections. The 
small base dimension means less space is required on the 
ground or roof, plus, the installer can fit this unit between the 
wheel wells of a full size pick-up truck. All models are well under 
500 pounds.

All units are completely wired, charged with R-22 and tested 
prior to shipment. Unique test stations using a new state of the 
art computerized process system are used to insure product 
quality. Refrigerant charge, and component part numbers are 
verified via computers at installation. Vital run test statistics 
such as system pressure, motor currents, air velocity and 
temperature and unit vibration are monitored and recorded by 
the system to insure unit performance.

Equal size, side supply and return duct connections allows easy 
hook-up of ducts to match low crawl spaces without transition 
pieces.

SINGLE PACKAGE
COOLING UNITS

ACP024 THRU 060
2 THRU 5 TON (13 SEER)

          

          

          

ISO 9001

Certified Quality

Management System

Summary of Contents for ACP024

Page 1: ...r flexibility and needs to carry less inventory LOWER INSTALLATION COST Installation time and costs are reduced by easy power and control wiring connections The small base dimension means less space is required on the ground or roof plus the installer can fit this unit between the wheel wells of a full size pick up truck All models are well under 500 pounds All units are completely wired charged w...

Page 2: ...WIRING DIAGRAM 460 3 60 POWER SUPPLY ACP MODELS 28 LIST OF TABLES Tbl Pg 1 PHYSICAL DATA 5 2 RATINGS ARI 5 3 COOLING CAPACITIES 2 TON ACP024 6 4 COOLING CAPACITIES 2 1 2 TON ACP030 8 5 COOLING CAPACITIES 3 TON ACP036 10 6 COOLING CAPACITIES 3 1 2 TON ACP042 12 7 COOLING CAPACITIES 4 TON ACP048 14 8 COOLING CAPACITIES 5 TON ACP060 16 9 SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE 17 10 ADDITIONAL ...

Page 3: ...n does not disrupt neighboring areas and does not dry out vegetation surrounding the unit The warm air from the top mounted fan is blown up away from the structure and any landscaping This allows compact location on multi unit applications CONDENSER COIL GRILLE A multi piece totally enclosed rigidly mounted condenser coil grille provides protection from objects and personal after installation and ...

Page 4: ...r duct mounted side supply return and unit mounted down supply return applications Damper capable of providing 0 thru 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly RECTANGLE TO ROUND ADAPTERS Kit includes one supply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over current duct openings on the base unit Tran...

Page 5: ... FINS PER INCH 20 20 20 20 20 20 FACE AREA Sq Ft 12 9 12 9 12 9 12 9 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 4 10 5 9 5 0 4 12 6 0 10 8 FILTER FACE AREA Sq Ft Qty Size 2 14 1 14 x 22 COMPRESSOR HERMETIC QTY 1 Type Recip Rotary Scroll Scroll Scroll Scroll 3 4 3 4 TABLE 2 RATINGS ARI Model ACP Cooling1 Capacity 80 67 95 F Sound Rating2 decibels Electric Heat Nom Capacity KW single phase Electric Heat...

Page 6: ...2 1 8 19 6 17 0 14 4 11 7 26 6 2 0 20 7 17 5 14 4 11 2 67 26 9 1 8 25 0 23 8 19 7 17 1 14 4 25 7 2 0 23 4 22 8 19 7 16 5 13 3 62 25 9 1 8 25 0 25 0 24 6 22 0 19 4 16 7 24 5 1 9 23 4 23 4 23 2 20 1 16 9 13 8 57 25 0 1 8 25 0 25 0 25 0 22 3 19 7 17 1 23 4 1 9 23 4 23 4 23 4 20 3 17 1 14 0 95 F 105 F 600 77 26 3 2 1 12 2 9 7 7 1 24 6 2 3 11 8 9 2 6 5 72 24 9 2 1 16 3 13 8 11 2 8 7 22 6 2 3 15 7 13 0 ...

Page 7: ...16 7 13 2 9 6 6 1 15 9 2 5 15 8 15 8 15 1 11 6 7 7 3 9 57 17 7 2 3 17 7 17 7 17 7 14 2 10 6 7 1 15 9 2 5 15 9 15 9 15 9 12 3 8 4 4 6 900 72 21 7 2 5 18 1 16 1 12 2 8 2 19 8 2 7 16 3 15 7 11 5 7 3 67 19 0 2 4 18 1 18 1 16 8 12 8 8 9 16 5 2 5 16 3 16 3 15 9 11 7 7 5 62 18 6 2 4 18 1 18 1 17 6 13 6 9 7 5 8 16 4 2 5 16 3 16 3 16 0 11 8 7 6 3 4 57 18 1 2 4 18 1 18 1 18 1 14 1 10 2 6 3 16 3 2 5 16 3 16 ...

Page 8: ...4 0 20 6 17 2 13 8 32 3 2 3 24 8 20 9 17 0 13 1 67 32 8 2 2 31 8 26 5 23 1 19 7 16 3 31 2 2 4 29 9 26 9 23 0 19 1 15 2 62 32 0 2 1 31 8 31 8 31 6 28 2 24 7 21 3 29 9 2 3 29 9 29 9 29 7 25 8 21 9 18 0 57 31 8 2 0 31 8 31 8 31 8 28 4 25 0 21 6 30 0 2 2 30 0 30 0 30 0 26 1 22 2 18 3 95 F 105 F 750 77 31 8 2 5 14 8 11 8 8 8 30 8 2 7 14 3 11 2 8 1 72 30 3 2 5 19 8 16 8 13 7 10 7 28 8 2 6 19 1 15 9 12 8...

Page 9: ...8 22 6 18 5 14 4 10 2 20 4 3 0 20 4 20 4 20 4 16 7 12 1 7 8 57 23 1 2 8 23 1 23 1 22 4 18 3 14 1 10 0 20 8 3 0 20 8 20 8 20 8 16 2 11 6 7 3 1125 72 25 8 3 0 22 3 19 9 14 5 9 9 23 2 3 2 19 6 19 6 13 8 8 9 67 23 5 2 9 22 3 22 3 20 0 15 5 10 9 20 5 3 1 19 6 19 6 19 1 14 3 9 5 62 22 3 2 8 22 3 22 3 22 3 17 7 13 1 8 6 19 7 3 0 19 7 19 7 19 7 15 1 10 2 5 4 57 22 7 2 8 22 7 22 7 22 7 17 7 13 2 8 6 20 0 3...

Page 10: ... 31 2 24 9 18 6 43 5 3 1 36 4 30 1 23 8 17 6 67 43 3 2 8 43 3 38 6 32 4 26 1 19 8 40 5 3 1 40 5 37 4 31 1 24 8 18 5 62 39 7 2 7 39 7 39 7 39 7 33 4 27 2 20 9 36 9 2 9 36 9 36 9 36 9 30 6 24 4 18 1 57 37 2 2 9 37 2 37 2 37 2 30 9 24 6 18 3 35 3 3 0 35 3 35 3 35 3 29 0 22 7 16 4 95 F 105 F 1000 77 42 6 3 1 20 5 16 7 12 8 39 3 3 4 19 2 15 5 11 9 72 38 9 3 1 26 3 22 4 18 6 14 8 35 7 3 3 24 7 21 1 17 4...

Page 11: ...27 8 27 8 27 8 22 3 16 8 11 3 24 9 3 8 24 9 24 9 24 9 19 4 13 5 7 8 57 27 6 3 5 27 6 27 6 27 6 22 1 16 6 11 1 25 1 3 8 25 1 25 1 25 1 19 6 13 7 8 0 1375 72 34 3 3 8 31 1 25 3 19 4 13 6 30 8 4 0 30 1 24 2 18 3 12 3 67 30 8 3 7 30 8 30 8 25 8 20 0 14 1 27 6 3 9 27 6 27 6 24 5 18 5 12 6 62 28 0 3 6 28 0 28 0 28 0 22 2 16 3 10 5 25 2 3 8 25 2 25 2 25 2 19 3 13 3 7 3 57 27 9 3 6 27 9 27 9 27 9 22 0 16 ...

Page 12: ... 5 30 3 25 1 20 0 47 3 3 5 35 1 29 8 24 4 19 1 67 46 2 3 1 42 5 37 8 32 7 27 5 22 4 43 9 3 5 40 3 37 3 32 0 26 6 21 3 62 43 3 3 1 42 5 42 5 42 0 36 9 31 7 26 6 40 5 3 4 40 3 40 3 39 8 34 5 29 1 23 8 57 42 5 3 0 42 5 42 5 42 5 37 3 32 1 27 0 40 3 3 3 40 3 40 3 40 3 35 0 29 6 24 3 95 F 105 F 1050 77 47 9 3 8 22 6 18 4 14 3 45 4 4 2 21 5 17 3 13 1 72 44 2 3 7 29 1 25 0 20 9 16 8 41 7 4 1 28 3 24 1 19...

Page 13: ...2 2 32 2 27 0 21 8 16 6 29 8 4 8 29 8 29 8 29 8 25 4 19 9 14 5 57 33 0 4 4 33 0 33 0 33 0 27 8 22 6 17 4 30 7 4 8 30 7 30 7 30 7 26 2 20 6 15 2 1400 72 39 5 4 7 31 2 25 8 20 3 14 9 36 7 5 1 29 9 24 7 19 1 13 5 67 35 6 4 6 32 4 32 4 27 8 22 3 16 9 32 8 5 0 29 9 29 9 26 7 21 1 15 6 62 32 4 4 5 32 4 32 4 32 4 26 9 21 4 15 9 29 9 4 9 29 9 29 9 29 9 24 8 19 0 13 5 57 33 1 4 5 33 1 33 1 33 1 27 7 22 2 1...

Page 14: ... 39 4 31 0 22 7 55 5 3 9 47 1 38 7 30 3 21 9 67 53 6 3 4 53 6 48 5 40 1 31 8 23 4 50 5 3 8 50 5 47 3 38 9 30 6 22 2 62 49 2 3 4 49 2 49 2 49 2 40 8 32 5 24 1 45 8 3 8 45 8 45 8 45 8 37 5 29 1 20 7 57 47 8 3 9 47 8 47 8 47 8 39 5 31 1 22 7 44 1 3 7 44 1 44 1 44 1 35 8 27 4 19 0 95 F 105 F 1200 77 53 8 4 0 26 4 21 9 17 3 50 5 4 5 24 9 20 5 16 1 72 48 9 4 0 33 1 28 5 23 9 19 3 45 6 4 5 31 3 26 9 22 5...

Page 15: ...4 7 34 7 34 7 27 7 20 7 13 6 31 4 5 5 31 4 31 4 31 4 24 3 16 8 9 5 57 34 7 4 9 34 7 34 7 34 7 27 7 20 6 13 6 32 3 5 6 32 3 32 3 32 3 25 3 17 7 10 4 1800 72 44 8 5 2 41 0 33 3 25 6 18 0 41 2 5 7 39 7 32 0 24 2 16 4 67 39 5 5 2 39 5 39 5 33 2 25 5 17 9 35 9 5 7 35 9 35 9 31 5 23 7 16 0 62 35 1 5 1 35 1 35 1 35 1 27 5 19 8 12 2 31 7 5 6 31 7 31 7 31 7 24 1 16 2 8 4 57 35 1 5 0 35 1 35 1 35 1 27 4 19 ...

Page 16: ... 39 5 33 2 26 8 66 0 4 8 45 5 38 9 32 3 25 7 67 64 6 4 3 56 9 50 5 44 2 37 8 31 5 61 4 4 8 56 5 49 9 43 3 36 7 30 1 62 60 4 4 3 60 4 60 4 54 7 48 3 42 0 35 7 57 0 4 7 57 0 57 0 53 3 46 7 40 1 33 5 57 58 0 4 3 58 0 58 0 58 0 51 6 45 3 38 9 54 9 4 7 54 9 54 9 54 9 48 3 41 7 35 1 95 F 105 F 1500 77 65 5 5 0 29 0 23 4 17 8 62 8 5 6 28 3 22 7 17 1 72 60 5 5 0 38 7 33 1 27 5 21 9 57 4 5 6 37 6 32 0 26 4...

Page 17: ...Bh Total Capacity1 MBh Total Input kW 2 Sensible Capacity MBh CFM WB F Return Dry Bulb F Return Dry Bulb F 90 85 80 75 70 65 90 85 80 75 70 65 TABLE 9 SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE Model No ACP Blower Speed Setting External Static Pressure Inches Water Gauge 0 2 0 4 0 6 0 8 1 0 CFM W RPM CFM W RPM CFM W RPM CFM W RPM CFM W RPM 024 2 0 Low 1 726 87 632 629 99 739 Low Medium 2 768 97...

Page 18: ... 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08 1500 0 04 0 05 0 04 0 09 1600 0 04 0 06 0 05 0 10 1700 0 05 0 07 0 05 0 11 1800 0 05 0 07 0 06 0 11 1900 0 06 0 08 0 06 0 11 2000 0 07 0 08 0 07 0 12 048 4 0 1100 0 03 0 01 0 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08 1500 0 04 0 05 0 04 0 09 1600 0 04 0 06 0 05 0 10 1700 0 0...

Page 19: ... POWER WIRING 24 VOLT TRANSFORMER UNIT TERMINAL STRIP THERMOSTAT NOTE HEAT ANTICIPATOR SHOULD BE SET AT 0 25 AMPS FOR ALL MODELS CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing PROGRAMMABLE THERMOSTAT ONLY Minimum wire size of 18 AWG wire should be used for all field installed 24...

Page 20: ...25 11 3 15 1 31 4 36 1 44 3 50 2 45 60 460 3 60 5 8 45 9 0 8 2 1 None 10 1 15 2NH04501046 10 1 12 17 6 20 2NH04501546 15 1 18 25 1 30 042 3 5 208 230 1 60 21 1 115 33 1 2 6 0 None 33 6 45 2NH04500506 3 8 5 1 18 3 20 8 33 6 33 6 45 45 2NH04500706 5 6 7 5 2 26 9 31 3 41 2 46 6 50 50 2NH04501006 7 5 10 2 36 1 41 7 52 6 59 6 60 60 2NH04501506 11 3 15 2 54 3 62 5 75 4 85 6 80 90 208 230 3 60 13 4 89 21...

Page 21: ...0 60 2NH04502025 15 20 2 41 7 48 1 61 6 69 6 70 70 2NH04502525 18 8 25 2 52 1 60 1 74 7 84 7 80 90 460 3 60 8 4 70 13 1 3 3 8 None 15 6 20 2NH04501046 10 1 12 19 8 20 2NH04501546 15 1 18 27 3 30 2NH04502046 20 2 24 1 34 8 35 2NH04502546 25 2 30 1 42 3 45 1 Minimum Circuit Ampacity 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit breaker size installed at factory or fie...

Page 22: ...ERALL 4 1 2 UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN DIA KNOCKOUT HIGH VOLTAGE CONN DIA KNOCKOUT REFRIGERANT CONNECTIONS A UNIT SIZE DIMENSION A 024 042 33 048 060 41 CLEARANCES Minimum Front 12 Back 0 Left Side Filter Access 24 Right Side 24 Below Unit 1 0 Above Unit 2 36 For...

Page 23: ...1 048 384 379 103 90 87 99 060 500 495 135 117 113 130 26 FRONT OF UNIT A B C D CENTER OF GRAVITY TABLE 13 CLEARANCES Unit Clearances Minimum Front 12 Back 0 Left Side Filter Access 24 Right Side 24 Below Unit1 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 0 Above Unit2 2 Units must be installed outdoors Overhanging structures or shrubs shou...

Page 24: ...POWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT SUPPLY AIR DUCT RETURN AIR DUCT CONTROL WIRING TO INDOOR THERMOSTAT TO POWER SUPPLY FIELD SUPPLIED DISCONNECT SWITCH MOUNTED ON UNIT ROOF CURB INSTALLATION REAR DUCT ...

Page 25: ...TED PANELS 22 14 OPENING FOR RETURN AIR DUCT OPENING FOR SUPPLY AIR DUCT RECOMMENDED DUCT SIZE SUPPLY AIR DUCT x RETURN AIR DUCT x UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FRAME COUNTERFLASHING INSULATION CANT STRIP ROOF DECK AND ROOFING MATERIAL INSULATION AND ROOFING MATERIAL x 1 WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES 14 1 ...

Page 26: ...279815 PTG D 0408 26 Johnson Controls Unitary Products FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY ACP MODELS ...

Page 27: ...279815 PTG D 0408 Johnson Controls Unitary Products 27 FIGURE 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY ACP MODELS ...

Page 28: ...279815 PTG D 0408 28 Johnson Controls Unitary Products FIGURE 11 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY ACP MODELS ...

Page 29: ...on shall be designed to fit between standard 24 O C beams without modification to building structure duct work and base unit 10 Condensate pan shall be internally sloped and conform to ASHARE 62 89 self draining standards with NPTI copper ridged mount connection INDOOR EVAPORATOR FAN ASSEMBLY 1 The ACP fan motor shall be direct drive 5 speed design 2 Fan wheel shall be double inlet type with forwa...

Page 30: ... shall have a primary limit control s and automatic reset to prevent the heating element system from operating at an excessive temperature 3 The heating section assembly shall slide out of the unit for easy maintenance and service 4 Units with electric heating sections shall be wired for a single point power supply with branch circuit fusing where required UNIT OPERATING CHARACTERISTICS 1 Unit sha...

Page 31: ...279815 PTG D 0408 Johnson Controls Unitary Products 31 ...

Page 32: ... change without notice Printed in U S A 279815 PTG D 0408 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 279815 PTG C 1007 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...