279815-PTG-D-0408
Johnson Controls Unitary Products
21
060
(5.0)
208/230-1-60
25.0
150
39
2.3
7.6
None
-
-
-
41.2
50
2NH04501006
7.5 / 10
2
36.1 / 41.7
54.6 / 61.6
60 / 70
2NH04501506
11.3 / 15
2
54.2 / 62.5
77.2 / 87.6
80 / 90
2NH04502006
15 / 20
2
72.2 / 83.3
99.8 / 113.7
100 / 125
2NH04502506
18.8 / 25
2
90.3 / 104.2 122.3 / 139.7
125 / 150
208/230-3-60
17.3
123
27
2.3
7.6
None
-
-
-
31.5
40
2NH04501025
7.5 / 10
1
20.8 / 24.1
35.6 / 39.6
45 / 45
2NH04501525
11.3 / 15
1
31.3 / 36.1
48.6 / 54.6
50 / 60
2NH04502025
15 / 20
2
41.7 / 48.1
61.6 / 69.6
70 / 70
2NH04502525
18.8 / 25
2
52.1 / 60.1
74.7 / 84.7
80 / 90
460-3-60
8.4
70
13
1.3
3.8
None
-
-
-
15.6
20
2NH04501046
10
1
12
19.8
20
2NH04501546
15
1
18
27.3
30
2NH04502046
20
2
24.1
34.8
35
2NH04502546
25
2
30.1
42.3
45
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
TABLE 11: ACP024-060 ELECTRICAL DATA / ELECTRIC HEAT (CONTINUED)
Size
(Tons)
Volt
Compressors
(each)
OD
Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
Model
kW
Stages
Amps