background image

4

    A419ABG-3 Electronic Temperature Control Installation Instructions

To position a jumper in the 

Installed 

position, place

the jumper on both pins, which closes the circuit
between the pins. To position a jumper in the

Removed 

position, place the jumper on one pin only.

See Figure 4.

Jumper

Pins

Removed

(Jumper Positioned on One Pin)

Installed

(Jumper Positioned on Both Pins)

=

=

Figure 4: Positioning the Jumpers

P5

P4

Touchpad

Locked

Heating Mode

Cut-in at Setpoint

Heating Mode

Cut-out at Setpoint

Cooling Mode

Cut-out at Setpoint

Cooling Mode

Cut-in at Setpoint

JUMP2

Figure 5: Jumper Positions and Control Settings

The A419 Control Functions

Setpoint 

(SP

)

 establishes the temperature value at

which the equipment is switched on or off, depending
on the user selected mode of operation. Setpoint
range is -30 to 212°F or -34 to 100°C (in 1-degree
increments).
If Setpoint mode is set to cut-in, setpoint is the
temperature value at which the control closes the
Normally Open (N.O.) contacts. If Setpoint mode is set
to cutout, setpoint is the temperature at which the N.O.
contacts open.

Differential 

(

dIF

) establishes the difference in

temperature between the cut-in value and cutout
value. The differential is set relative to Setpoint and
may be set from 1 to 30 F° or C° (in 1-degree
increments).

Anti-Short Cycle Delay

 (

ASd

) establishes the

minimum time that the output relay remains
de-energized before the next on-cycle. The 

ASd

 does

not allow the output relay to re-energize until the
programmed time delay has elapsed. The delay is
activated when the control is first turned on and every
time an on-cycle ends. When the delay is activated,
the LCD alternately flashes the sensor temperature
and 

ASd

. The Anti-short Cycle Delay range is

0 to 12 minutes (in 1-minute increments).

Sensor Failure Operation 

(

SF

) establishes how the

A419 control’s output-relay operates the equipment in
the event of a sensor or sensor wiring failure. The user
may select to run the equipment continuously or to
shut it down. When the control detects a sensor circuit
failure, the LCD flashes 

SF

 alternately with 

OP

 (if the

sensor circuit is open), or 

SH

 (if the sensor circuit is

shorted). Before indicating a failure, the control
implements a 1-minute delay, which allows verification
of failure condition and avoids nuisance failure
indications.

Table 2: Jumper Designations, Jumper Positions, and Control Settings

Function

Jumper Pins Designation

on Control

Setting

Jumper

Position

Factory Default Setting

(and Jumper Position)

Cooling Mode

Removed

Cooling/Heating
Operating Mode

JUMP1

(Top Pair of Pins on Block P4)

Heating Mode

Installed

Cooling Mode
(Jumper Removed)

Setpoint
at Cut-in

Removed

Setpoint at

Cut-in or Cutout

JUMP2

(Bottom Pair of Pins on Block P4)

Setpoint
at Cutout

Installed

Cut-in
(Jumper Removed)

Touchpad Lock

P5

Locked

Removed

Unlocked
(Jumper Installed)

Summary of Contents for A419ABG-3C

Page 1: ...lity and electronic accuracy in a Type NEMA 1 high impact plastic enclosure suitable for surface or DIN rail mounting The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls PENN A99 temperature sensors FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules Thes...

Page 2: ...the sensor to the A419 control Wire insulation rating must be 90 C minimum Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15 2 m use a twisted pair shielded cable to reduce electrical interference A99 temperature sensors are not polarity sensitive Wire the leads to SEN and COM on the sensor terminal block TB3 See Figure 2 Keep the lea...

Page 3: ...h IMPORTANT To ensure that the output relay operates as intended verify that all three of the jumpers are positioned properly for the application before powering the A419 control IMPORTANT The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins Do not discard jumpers in case they are required in the future See Figure 4 and Figure 5 Positioning the Jumpers The P5 jumper...

Page 4: ...blishes the minimum time that the output relay remains de energized before the next on cycle The ASd does not allow the output relay to re energize until the programmed time delay has elapsed The delay is activated when the control is first turned on and every time an on cycle ends When the delay is activated the LCD alternately flashes the sensor temperature and ASd The Anti short Cycle Delay ran...

Page 5: ...ure If no setup entry is made for 30 seconds the control reverts to the normal temperature display IMPORTANT If MENU is not pressed after changing the setpoint value the control reverts to the previously programmed setpoint value MENU F BIN MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Operating Mode Indicator Temperature Units Indicator Temperature Offset Indicat...

Page 6: ... Electrical Shock Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter Failure to use properly insulated tools and probes may result in severe personal injuries or death If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following pro...

Page 7: ...dicated in Figure 7 replace the A419 control i If proper operation of the A419 control is verified reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment Fault Codes If the LCD displays an alarm or fault code SF or EE consult Table 5 for explanation Table 4 A419 Output Relay Operation in Different Operating Modes Setpoint Mode Operatin...

Page 8: ...set WEL11A 601C Immersion Well for Mounting Sensor in Liquid Applications Technical Specifications Product A419ABG 3C Electronic Temperature Control Setpoint Range 30 to 212 F 34 to 100 C Differential Range 1 to 30F 1 to 30C Supply Voltage 120 VAC 60 Hz Power Consumption 1 8 VA Maximum SPST Output Relay Contacts Electrical Ratings Full Load Amperes N O 12 A Locked Rotor Amperes N O 72 A Non induct...

Reviews: