A419ABG-3 Electronic Temperature Control Installation Instructions    

5

Temperature Offset

 (

OFS

)

 

establishes a set

secondary 

Setpoint

 and 

Differential

 values that may

be invoked to control an application when a circuit is
closed between the binary input (

BIN

) and common

(

COM

) terminals (and 

BIN

 appears on the display).

See Figure 6. Offset range is 0 to 50F° or C° (in
1-degree increments). A typical application might use
a switching time clock to invoke night-setback
temperature settings.

IMPORTANT:

Make sure the Touchpad Lock

jumper is installed (unlocked) before attempting to
adjust the A419 control functions. See 

Figure 5

.

Changing the A419 Control Temperature Units

The A419 control is factory set to display Fahrenheit
temperature. To change to Celsius, press 

Up

 and

Down

 (arrows) simultaneously. Press them again to

display Fahrenheit units. Verify that the control is
displaying the desired temperature units before setting
the Setpoint.

Setting the A419 Control Setpoint Value

To view and adjust Setpoint, follow these steps:

1.  Press and hold MENU (about 2 seconds) until the

display flashes SP.

2.  Press MENU again to display the existing setpoint

value.

3.  Press Up or Down (arrows) to change the setpoint

value.

4.  Press MENU again to save the new value. The

display returns to the sensed temperature.

If no setup entry is made for 30 seconds, the control
reverts to the (normal) temperature display.

IMPORTANT: 

If MENU is not pressed after

changing the setpoint value, the control reverts to
the previously programmed setpoint value.

MENU

F

BIN

MENU

Button

DOWN

 Arrow

Button

UP

 Arrow

Button

Output Relay 

Status Indicator

LED

Operating Mode

Indicator

Temperature

Units Indicator

Temperature

Offset Indicator

Liquid Crystal

Display

Figure 6: Liquid Crystal Display, Touchpad, and

LED Indicator

Table 3: Display Symbols, Control Function, Ranges, Units, Values, and Factory Settings

Display
Symbol

Control Function

Range – Units/Value

Factory Set
Value

SP

Setpoint*

-30 to 212 – 

°

F (-34 to 100 – 

°

C)

30

dIF

Differential*

1 to 30 – (F

°

 or C

°

 in 1-degree increments)

5

ASd

Anti-short Cycle Delay

0 to 12 – (in 1-minute increments)

1

OFS

Temperature Offset

0 to 50 (F

°

 or C

°

 in 1-degree increments)

0

SF

Sensor Failure Operation

(No range) – 

0 = output relay  de-energized
1 = output relay energized

1

F or C

Temperature Units

(No range) – F

°

 or C

°

BIN

Temperature Offset Indicator

(No range) – BIN is displayed and the A419 control
operates on the secondary setpoints when the circuit
between the BIN and COM terminals is closed.

N/A

 or 

Cooling or Heating Mode of
Operation

(No range) – 

 (Cooling Mode) is displayed when the

Jump1 jumper is removed.   (Heating Mode) is displayed
when the Jump1 jumper is installed.

Cooling Mode

*

The sum of the Setpoint and Differential values must be within the Setpoint range, or the control may not function
properly.

Summary of Contents for A419ABG-3C

Page 1: ...lity and electronic accuracy in a Type NEMA 1 high impact plastic enclosure suitable for surface or DIN rail mounting The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls PENN A99 temperature sensors FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules Thes...

Page 2: ...the sensor to the A419 control Wire insulation rating must be 90 C minimum Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15 2 m use a twisted pair shielded cable to reduce electrical interference A99 temperature sensors are not polarity sensitive Wire the leads to SEN and COM on the sensor terminal block TB3 See Figure 2 Keep the lea...

Page 3: ...h IMPORTANT To ensure that the output relay operates as intended verify that all three of the jumpers are positioned properly for the application before powering the A419 control IMPORTANT The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins Do not discard jumpers in case they are required in the future See Figure 4 and Figure 5 Positioning the Jumpers The P5 jumper...

Page 4: ...blishes the minimum time that the output relay remains de energized before the next on cycle The ASd does not allow the output relay to re energize until the programmed time delay has elapsed The delay is activated when the control is first turned on and every time an on cycle ends When the delay is activated the LCD alternately flashes the sensor temperature and ASd The Anti short Cycle Delay ran...

Page 5: ...ure If no setup entry is made for 30 seconds the control reverts to the normal temperature display IMPORTANT If MENU is not pressed after changing the setpoint value the control reverts to the previously programmed setpoint value MENU F BIN MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Operating Mode Indicator Temperature Units Indicator Temperature Offset Indicat...

Page 6: ... Electrical Shock Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter Failure to use properly insulated tools and probes may result in severe personal injuries or death If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following pro...

Page 7: ...dicated in Figure 7 replace the A419 control i If proper operation of the A419 control is verified reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment Fault Codes If the LCD displays an alarm or fault code SF or EE consult Table 5 for explanation Table 4 A419 Output Relay Operation in Different Operating Modes Setpoint Mode Operatin...

Page 8: ...set WEL11A 601C Immersion Well for Mounting Sensor in Liquid Applications Technical Specifications Product A419ABG 3C Electronic Temperature Control Setpoint Range 30 to 212 F 34 to 100 C Differential Range 1 to 30F 1 to 30C Supply Voltage 120 VAC 60 Hz Power Consumption 1 8 VA Maximum SPST Output Relay Contacts Electrical Ratings Full Load Amperes N O 12 A Locked Rotor Amperes N O 72 A Non induct...

Reviews: