A25 Series Warm Air Control with Manual Reset Product/Technical Bulletin     

7

 

R

epairs and Replacement 

Do not make field repairs.  For a replacement control, 

contact your nearest Johnson Controls representative. 

 

 

 

 

Table 1:  Ordering Information 

Item Product 

Code 

Number 

Product 

Description 

A25 Series Warm Air Control 
with Manual Reset 

 

A25AN-1 

A25AP-1 

 

A25CN-1 

A25CP-1 

SPST, opens on temperature rise, setpoint knob adjustment. 

SPST, opens on temperature rise, concealed screwdriver adjustment,  

Factory Mutual approved. 

SPDT, setpoint knob adjustment. 

SPDT, concealed screwdriver adjustment, Factory Mutual approved. 

 

T

roubleshooting 

Table 2:  Troubleshooting Chart 

Symptom Problem  Solution 

The A25 is not sensing properly. 

The sensing element may not be 

extended into the airstream or the sensing 

element is contacting an object inside of 

the duct (or plenum). 

Insert the sensing element as far as 

possible into the airstream without 

allowing it to contact any object inside the 

duct (or plenum). 

The system does not operate. 

Incorrect switch connections or improper 

wiring. 

 

Damaged sensor. 

The A25 is tripped. 

Ensure that the wiring connections follow 

the wiring diagrams in the 

Wiring

 section. 

Check connections. 

Replace the A25. 

Reset the A25. 

A25 does not lockout upon a 
temperature rise beyond the setpoint. 

The A25 is defective. 

Replace the A25. 

The A25 does not sense the correct air 
temperature. 

The A25 is defective. 

Replace the A25. 

A25 will not reset. 

The temperature in the duct (or plenum) is 

not 20F° (11C°) below the setpoint. 

Check system for overheating or fire. 

Summary of Contents for A25 Series

Page 1: ...ntrol in the supply air duct or plenum where a lockout type control is desired or required by local code Figure 1 The A25 Series Warm Air Control with Manual Reset Features and Benefits Trip free Rese...

Page 2: ...ng location refer to Figure 2 3 Using the flange as a template on the duct mark the location for two 1 2 in 13 mm No 10 sheet metal screws 4 Punch or drill both sheet metal screw holes in the duct at...

Page 3: ...ncrease The red to blue circuit opens on temperature increase Refer to Figures 3 and 4 for terminal identification and typical wiring connections When the reset lever is pressed during normal operatio...

Page 4: ...nd the alarm or signal if applicable should activate Note The setpoint at shutdown should equal the approximate duct air temperature 3 Turn the setpoint knob clockwise to the desired setpoint Nothing...

Page 5: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Page 6: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Page 7: ...n The A25 is not sensing properly The sensing element may not be extended into the airstream or the sensing element is contacting an object inside of the duct or plenum Insert the sensing element as f...

Page 8: ...8 A25 Series Warm Air Control with Manual Reset Product Technical Bulletin Notes...

Page 9: ...e reset when the temperature drops 20F 11C below the dial setting Sensing Element Bi metal rod and tube construction Shipping Weight Individual pack 1 8 lb 0 8 kg Overpack of 12 units 23 lb 10 4 kg Wi...

Reviews: