A25 Series Warm Air Control with Manual Reset Product/Technical Bulletin     

3

 

W

iring 

 WARNING: 

Shock hazard. 

 To avoid 

electrical shock or damage to 

equipment, disconnect all power 

before making wiring 

connections. 

If available, follow the instructions for the unit onto 

which the A25 will be installed.  Make all wiring 

connections only with copper conductors and in 

accordance with the National Electrical Code and local 

regulations.  Refer to the label inside the A25’s cover 

for the maximum electrical rating. 

Models A25CN and A25CP  
SPDT (Single Pole Double Throw) Units 

The wiring terminals on the SPDT (Single Pole  

Double Throw) models are color coded: 

 

Red is common. 

 

The red to yellow circuit closes on 

temperature increase. 

 

The red to blue circuit opens on temperature  

increase. 

Refer to Figures 3 and 4 for terminal identification and 

typical wiring connections. 

When the reset lever is pressed during normal 

operation, the trip free contacts are activated, the red 

to blue contact opens and the auxiliary red to yellow 

contact closes.  At this point, the auxiliary system  

will activate. 

Models A25AN and A25AP  
SPST (Single Pole Single Throw) Units 

When the temperature increases to above the 

setpoint, the circuit opens. When the reset lever is 

pressed after the sensed temperature decreases to 

approximately  

20F° (11C°) below the setpoint, the circuit closes. 

Refer to Figures 5 and 6 for terminal identification and 

typical wiring connections. 

 

 

 

IMPORTANT: 

Only use the terminal screws 

furnished with the A25 (8-32 x  

1/4 in. binder head).  Use of 

other screws will void warranty, 

may damage switch terminals, 

and result in improper 

connections. 

Summary of Contents for A25 Series

Page 1: ...ntrol in the supply air duct or plenum where a lockout type control is desired or required by local code Figure 1 The A25 Series Warm Air Control with Manual Reset Features and Benefits Trip free Rese...

Page 2: ...ng location refer to Figure 2 3 Using the flange as a template on the duct mark the location for two 1 2 in 13 mm No 10 sheet metal screws 4 Punch or drill both sheet metal screw holes in the duct at...

Page 3: ...ncrease The red to blue circuit opens on temperature increase Refer to Figures 3 and 4 for terminal identification and typical wiring connections When the reset lever is pressed during normal operatio...

Page 4: ...nd the alarm or signal if applicable should activate Note The setpoint at shutdown should equal the approximate duct air temperature 3 Turn the setpoint knob clockwise to the desired setpoint Nothing...

Page 5: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Page 6: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Page 7: ...n The A25 is not sensing properly The sensing element may not be extended into the airstream or the sensing element is contacting an object inside of the duct or plenum Insert the sensing element as f...

Page 8: ...8 A25 Series Warm Air Control with Manual Reset Product Technical Bulletin Notes...

Page 9: ...e reset when the temperature drops 20F 11C below the dial setting Sensing Element Bi metal rod and tube construction Shipping Weight Individual pack 1 8 lb 0 8 kg Overpack of 12 units 23 lb 10 4 kg Wi...