A25 Series Warm Air Control with Manual Reset Product/Technical Bulletin 

A

pplication Overview 

A typical application for the A25 Series Warm Air 

Control with Manual Reset is to stop the operation of 

air conditioning or ventilating fans upon a temperature 

rise. Models A25AP and A25CP are Factory Mutual 

approved for use as fire protection devices. 

I

nstallation 

1. 

Select a mounting location for the A25 in the duct 

(or plenum).  The location must allow the sensing 

element to sense the average temperature in the 

duct. 

2. 

Drill (or cut) a 1-3/8 in. hole in the duct at the 

selected mounting location (refer to Figure 2).

 

3. 

Using the flange as a template on the duct, mark 

the location for two 1/2 in. (13 mm) No. 10 sheet 

metal screws. 

4. 

Punch (or drill) both sheet metal screw holes in 

the duct at the marked locations. 

5. 

Secure the flange to the duct with two 1/2 in.  

(13 mm) No. 10 sheet metal screws provided. 

6. 

Insert the sensing element and sleeve through the 

flange installed in Step 5 (and into the duct). 

7. 

Secure the A25 to the flange by screwing the set 

screw firmly against the sleeve.  Do not  

overtorque the set screw. 

Note: 

Insert the sensing element as far as possible 

into the air stream without allowing it to 

contact any object inside the duct.  Provide at 

least  

5-3/4 in. (14 cm) clearance between the 

sensor and any other objects inside the duct. 

 

 

Figure 2:  Installing the A25  

Summary of Contents for A25 Series

Page 1: ...ntrol in the supply air duct or plenum where a lockout type control is desired or required by local code Figure 1 The A25 Series Warm Air Control with Manual Reset Features and Benefits Trip free Rese...

Page 2: ...ng location refer to Figure 2 3 Using the flange as a template on the duct mark the location for two 1 2 in 13 mm No 10 sheet metal screws 4 Punch or drill both sheet metal screw holes in the duct at...

Page 3: ...ncrease The red to blue circuit opens on temperature increase Refer to Figures 3 and 4 for terminal identification and typical wiring connections When the reset lever is pressed during normal operatio...

Page 4: ...nd the alarm or signal if applicable should activate Note The setpoint at shutdown should equal the approximate duct air temperature 3 Turn the setpoint knob clockwise to the desired setpoint Nothing...

Page 5: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Page 6: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Page 7: ...n The A25 is not sensing properly The sensing element may not be extended into the airstream or the sensing element is contacting an object inside of the duct or plenum Insert the sensing element as f...

Page 8: ...8 A25 Series Warm Air Control with Manual Reset Product Technical Bulletin Notes...

Page 9: ...e reset when the temperature drops 20F 11C below the dial setting Sensing Element Bi metal rod and tube construction Shipping Weight Individual pack 1 8 lb 0 8 kg Overpack of 12 units 23 lb 10 4 kg Wi...