background image

278410-UIM-K-1010

2

Johnson Controls Unitary Products

1.

Install this air handler only in a location and position as specified in
SECTION III of these instructions.

2.

Always install the air handler to operate within the air handler’s
intended maximum outlet air temperature. Only connect the air
handler to a duct system which has an external static pressure
within the allowable range, as specified on the air handler rating
plate.

3.

When an air handler is installed so that supply ducts carry air cir-
culated by the air handler to areas outside the space containing
the air handler, the return air shall also be handled by duct(s)
sealed to the air handler casing and terminating in the space to be
cooled/heated.

4.

The air handler is not to be used for temporary heating of buildings
or structures under construction.

5.

The size of the unit should be based on an acceptable heat loss or
gain calculation for the structure. ACCA, Manual J or other
approved methods may be used.

SAFETY REQUIREMENTS

1.

This air handler should be installed in accordance with all national
and local building/safety codes and requirements, local plumbing
or wastewater codes, and other applicable codes.

2.

Refer to the unit rating plate for the air handler model number, and
then see the dimensions page of this instruction for supply air ple-
num dimensions in Figure 3. The plenum must be installed accord-
ing to the instructions.

3.

Provide clearances from combustible materials as listed under
Clearances.

4.

Provide clearances for servicing ensuring that service access is
allowed for electric heaters and blower.

5.

Failure to carefully read and follow all instructions in this manual
can result in air handler malfunction, death, personal injury and/or
property damage.

6.

Check the rating plate and power supply to be sure that the electri-
cal characteristics match.

7.

Air handler shall be installed so the electrical components are pro-
tected from water.

8.

Installing and servicing heating/cooling equipment can be hazard-
ous due to the electrical components. Only trained and qualified
personnel should install, repair, or service heating/cooling equip-
ment. Untrained service personnel can perform basic maintenance
functions such as cleaning and replacing the air filters. When
working on heating/cooling equipment, observe precautions in the
manuals and on the labels attached to the unit and other safety
precautions that may apply.

9.

These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances,
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These
instructions are required as a minimum for a safe installation.

INSPECTION

As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s freight bill. A separate request for
inspection by the carrier’s agent should be made in writing. Also, before
installation the unit should be checked for screws or bolts, which may
have loosened in transit. There are no shipping or spacer brackets
which need to be removed.

Also check to be sure all accessories such as heater kits, suspension
kits, and coils are available. Installation of these accessories or field
conversion of the unit should be accomplished before setting the unit in
place or connecting any wiring, electric heat, ducts or piping.

LIMITATIONS

These units must be wired and installed in accordance with all national
and local safety codes. Voltage limits are as follows:

Airflow must be within the minimum and maximum limits approved for electric 
heat, evaporator coils and outdoor units.

SECTION III: UNIT INSTALLATION

CLEARANCES

Clearances must be taken into consideration, and provided for as fol-
lows:

1.

Refrigerant piping and connections - minimum 12” recommended.

2.

Maintenance and servicing access - minimum 36” from front of unit
recommended for blower motor / coil replacement.

3.

Condensate drain lines routed to clear filter and panel access.

4.

Filter removal - minimum 36” recommended.

5.

The ductwork and plenum connected to this unit are designed for
zero clearance to combustible materials.

6.

A combustible floor base accessory is available for downflow
applications of this unit, if required by local code.

LOCATION

Location is usually predetermined. Check with owner’s or dealer’s
installation plans. If location has not been decided, consider the follow-
ing in choosing a suitable location:

1.

Select a location with adequate structural support, space for ser-
vice access, clearance for air return and supply duct connections.

2.

Use hanging brackets to wall mount this single piece air handler
unit, is not recommended.

3.

Normal operating sound levels may be objectionable if the air han-
dler is placed directly over some rooms such as bedrooms, study,
etc.

4.

Select a location that will permit installation of condensate line to
an open drain or outdoors allowing condensate to drain away from
structure.

The coil is provided with a secondary drain. It should be piped to a loca-
tion that will give the occupant a visual warning that the primary drain is
clogged. If the secondary drain is not used it must be capped.

5.

When an evaporator coil is installed in an attic or above a finished
ceiling, an auxiliary drain pan should be provided under the air
handler as is specified by most local building codes.

6.

Proper electrical supply must be available.

FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. A fire or electrical hazard may
result causing property damage, personal injury or loss of life.

Air Handler Voltage

Voltage code

Normal Operating 

1

Voltage Range

1. Rated in accordance with ARI Standard 110, utilization range “A”.

208/230-1-60

06

187-253

220/240-1-50

93

198-264

Entering Air Temperature Limits

Wet Bulb Temp. °F

Dry Bulb Temp. °F

Min.

Max.

Min.

Max.

57

72

65

95

The primary and secondary drain line must be trapped to allow
proper drainage of condensate water. If the secondary drain line is
not used, it must be capped.

NOTICE

Summary of Contents for 18B

Page 1: ...ion in any upflow downflow or horizontal application These versatile models may be used for cooling or heat pump operation with or without electric heat A BRAND LABEL available from Distribution may be applied to the center of the blower access panel The unit can be positioned for bottom return air in the upflow position top return air in the downflow position and right or left return in the hor i...

Page 2: ...uest for inspection by the carrier s agent should be made in writing Also before installation the unit should be checked for screws or bolts which may have loosened in transit There are no shipping or spacer brackets which need to be removed Also check to be sure all accessories such as heater kits suspension kits and coils are available Installation of these accessories or field conversion of the...

Page 3: ...ssary based on air handler orienta tion 11 Re position and replace access panels In severe high humidity high temperature indoor unit environments an accessory insulation blanket is available to supplement the stan dard cabinet insulation Insulate with UPG Kit 1VJ0117 for B cabi nets 1VJ0121 for C cabinets or 1VJ0124 on 57 height or 1VJ0224 on 52 height D cabinets or seal completely with adequate ...

Page 4: ...erant Connections Drain Connections for Upflow and Downflow Applications 7 11 32 B A K C 1 1 2 Top Outlet Dimensions Filter Access 18 9 32 TABLE 1 Dimensions Models Dimensions Wiring Knockouts1 Refrigerant Connections Line Size A B C D E F J K Height Width Depth Power Control Liquid Vapor 18B 46 14 1 2 21 1 2 12 3 8 13 29 32 14 19 32 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 3 8 3 4 24B 46 17 1 2 12 3...

Page 5: ...nce inside the plenum box This turbulence can change the air flow patterns across the heat kit limit switch If the factory sug gested transition can not be fabricated it is recommended a block off plate approximately 8 in height and running the full width of the ple num be attached to the supply opening Please refer to Figure 7 as a visual aid The use of this block off plate will keep better air c...

Page 6: ...R HORIZONTAL APPLICATIONS 2 1 1 2 MIN 1 1 2 x 1 1 2 Angle Recommended length 26 minimum with 2 clearance on both sides of Air Handler MIN 3 8 THREADED ROD VAPOR LINE THERMAL EXPANSION VALVE BULB Required insulation not shown for clarity THERMAL EXPANSION VALVE DISTRIBUTOR BODY LIQUID LINE TXV EQUALIZER LINE NOTICE FIGURE 10 Proper Bulb Location COIL UNDER PRESSURE Relieve pressure by depressing sc...

Page 7: ...e the drains are not subject to any pressure it is not necessary to use Schedule 40 pipe for drain lines DO NOT use teflon tape pipe dope or other sealants The use of a sealant may cause damage and premature failure of the drain pan SECTION IV ELECTRIC HEATER INSTALLATION If the air handler requires electric heat install the electric heat kit according to the installation instructions included wit...

Page 8: ... will not energize the heat relay outputs or sense the limit switch input If the jumper is not present the control will operate as if the jumper is in the HEAT position If the jumper is not present and a heat kit is not pres ent the control will sense an open limit condition and the blower will run continuously Hum Stat Jumper The HUM STAT jumper configures the control to monitor the humidity swit...

Page 9: ...at signal a call for first stage heat will energize two heating elements HT1 and HT2 With either configuration the control will energize three heating ele ments HT1 HT2 and HT3 when it receives a first and second stage heat input from the thermostat Limit Switch and Lockout Operation Limit Switch Operation If the HEAT ENABLE jumper is in the HEAT position and the limit switch opens fault code 1 th...

Page 10: ...ction to the air handler If wire other than uncoated non plated 75 C ambient copper wire is used consult applicable tables of the National Electric Code ANSI NFPA 70 The chosen conductor and connections all must meet or exceed the amperage rating of the overcurrent protector circuit breaker or fuse in the circuit Additionally existing aluminum wire within the structure must be sized correctly for ...

Page 11: ... x 20 x 1 Permanent Type Kit 1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK Shipping Operating Weight lbs H Models 131 125 135 129 142 136 165 159 Models 42C 48D 60D Blower Diameter x Width 10 x 10 10 x 10 11 x 10 Motor HP 3 4 HP 3 4 HP 1 HP Nominal RPM 1075 1075 1050 Voltage 230 Amps Full Load 230 3 8 3 8 7 6 Filter1 Type DISPOSABLE OR PERMANENT Size 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 Permanent Type Ki...

Page 12: ...4 4HK16501806 0 5 Hi 13 2 17 6 45 1 60 1 3 3 4 4 6 6 8 8 13 2 17 6 42C 4HK 6500506 0 5 Lo 3 6 4 8 12 3 16 4 3 6 4 8 3 6 4 8 3 6 4 8 4HK 6500806 0 5 Med 5 6 7 5 19 2 25 6 2 8 3 75 2 8 7 5 5 6 7 5 4HK 6501006 0 5 Med 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501306 0 5 Med 9 8 13 33 3 44 4 3 3 4 3 6 5 8 7 9 8 13 0 4HK16501506 0 5 Med 10 8 14 4 36 9 49 1 3 6 4 8 7 2 9 6 10 8 14 4 4HK16501806 0 5...

Page 13: ...45 8 8 4HK 6501006 40 0 47 5 54 5 50 60 8 6 4HK16501306 54 2 63 1 72 2 70 80 4 2 4HK16501506 60 0 69 1 79 5 70 90 4 3 4HK16501806 73 3 83 6 96 1 90 100 3 3 42C 4HK 6500506 20 0 25 9 29 8 30 30 8 8 4HK 6500806 31 3 38 1 43 9 40 45 8 8 4HK 6501006 40 0 47 6 54 8 50 60 6 6 4HK16501306 54 2 63 3 72 5 70 80 4 2 4HK16501506 60 0 69 3 79 8 70 90 4 3 4HK16501806 73 3 83 7 96 4 90 100 3 3 4HK16502006 80 0 ...

Page 14: ...13 Electrical Data 208 230 3 60 Models Heat Kit Three Phase Max Static Min Speed Tap Total Heat1 KW Staging KW MBH W1 Only W2 Only W1 W2 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 24B 4HK06501025 0 5 Hi 7 2 9 6 24 6 32 8 7 2 9 6 7 2 9 6 7 2 9 6 30B 4HK06501025 0 5 Hi 7 2 9 6 24 6 32 8 7 2 9 6 7 2 9 6 7 2 9 6 4HK065N1525 0 5 Hi 10 8 14 4 36 9 49 1 10 8 14 4 10 8 14 4 10 8 14 4 36C 4HK0650102...

Page 15: ... 485 387 323 221 23 8 22 9 21 7 19 6 17 3 15 6 13 7 11 0 9 1 6 3 Low 654 614 548 483 420 349 302 218 179 130 18 5 17 4 15 5 13 7 11 9 9 9 8 6 6 2 5 1 3 7 30B High 1244 1184 1138 1079 1004 903 841 674 580 457 35 2 33 5 32 2 30 6 28 4 25 6 23 8 19 1 16 4 12 9 Med 956 913 868 815 748 663 574 487 384 N A 27 1 25 9 24 6 23 1 21 2 18 8 16 3 13 8 10 9 N A Low 941 904 862 806 731 643 566 480 361 226 26 6 ...

Page 16: ... 1681 1607 1538 1456 1360 1322 1260 966 770 49 8 47 6 45 5 43 6 41 2 38 5 37 4 35 7 27 4 21 8 Med 1320 1284 1255 1207 1146 1075 988 846 729 572 37 4 36 4 35 5 34 2 32 5 30 4 28 0 24 0 20 6 16 2 Low 1146 1119 1090 1038 992 972 841 725 617 496 32 5 31 7 30 9 29 4 28 1 27 5 23 8 20 5 17 5 14 0 42C High 1883 1764 1657 1543 1435 1327 1210 912 714 527 53 3 50 0 46 9 43 7 40 6 37 6 34 3 25 5 20 2 14 9 Me...

Page 17: ... CLEANING If the coil needs to be cleaned or replaced it should be washed with Calgon CalClean mix one part CalClean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur faces LUBRICATION The bearings of the blower motor are permanently lubricated CONDENSATE DRAINS During the coolin...

Page 18: ...278410 UIM K 1010 18 Johnson Controls Unitary Products SECTION XI WIRING DIAGRAM FIGURE 16 Wiring Diagram AHP18 48 ...

Page 19: ...278410 UIM K 1010 Johnson Controls Unitary Products 19 FIGURE 17 Wiring Diagram AHP60 ...

Page 20: ... change without notice Published in U S A 278410 UIM K 1010 Copyright 2010 by Johnson Controls Inc All rights reserved Supersedes 278410 UIM J 0810 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...

Reviews: