278410-UIM-K-1010
14
Johnson Controls Unitary Products
TABLE 12:
Electrical Data - (For
Multi-Source
Power Supply) - Copper Wire - 208/230-1-60
Models
Heater
Models
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
75
°
C Wire Size - AWG
Circuit
Circuit
Circuit
1st
2nd
3rd
1st
2nd
3rd
1st
2nd
3rd
208/230
208/230
208/230
208/230 208/230 208/230 208/230 208/230 208/230
24B
4HK16501306
40.9/47.0
19.5/22.5
–
45/50
20/25
–
8/8
10/10
–
30B
4HK16501306
41.6/47.9
19.5/22.5
–
45/50
20/25
–
8/8
10/10
–
4HK165N1506
45.8/52.8
21.7/25.0
–
50/60
25/25
–
8/6
10/10
–
36C
4HK16501306
41.2/47.6
22.0/24.6
–
50/50
30/30
–
6/6
12/10
–
4HK16501506
47.5/54.5
21.7/25.0
–
50/60
25/25
–
8/6
10/10
–
4HK16501806
43.9/50.3
39.8/45.8
–
45/60
40/50
–
8/6
8/8
–
42C
4HK16501306
41.3/47.7
22.0/24.8
–
50/50
30/30
–
6/6
12/10
–
4HK16501506
47.6/54.8
21.7/25.0
–
50/60
25/25
–
8/6
10/10
–
4HK16501806
44.0/50.6
39.8/45.8
–
45/60
40/50
–
8/6
8/8
–
4HK16502006
47.6/54.8
43.4/50.0
–
50/60
40/50
–
8/6
8/8
–
48D
4HK16501306
41.3/47.7
22.0/24.8
–
50/50
30/30
–
6/6
12/10
–
4HK16501506
47.6/54.8
21.7/25.0
–
50/60
25/25
–
8/6
10/10
–
4HK16501806
44.0/50.6
39.8/45.8
–
45/60
40/50
–
8/6
8/8
–
4HK16502006
47.6/54.8
43.4/50.0
–
50/60
40/50
–
8/6
8/8
–
60D
4HK16501306
43.8/50.1
24.6/27.1
–
50/60
30/30
–
6/6
10/10
–
4HK16501506
52.9/59.5
21.7/25.0
–
60/60
25/25
–
6/6
10/10
–
4HK16501806
49.3/55.3
39.8/45.8
–
50/60
45/60
–
6/6
8/6
–
4HK16502006
52.9/59.5
43.4/50.0
–
60/60
45/50
–
6/6
8/8
–
4HK16502506
52.9/59.5
43.4/50.0
21.68/25.00
60/60
45/50
25/25
6/6
8/8
10/10
TABLE 13:
Electrical Data - 208/230-3-60
Models
Heat Kit -
Three Phase
Max.
Static
Min.
Speed
Tap
Total Heat
1
KW Staging
KW
MBH
W1 Only
W2 Only
W1 + W2
208V
230V
208V
230V
208V
230V
208V
230V
208V
230V
24B
4HK06501025
0.5
Hi
7.2
9.6
24.6
32.8
7.2
9.6
7.2
9.6
7.2
9.6
30B
4HK06501025
0.5
Hi
7.2
9.6
24.6
32.8
7.2
9.6
7.2
9.6
7.2
9.6
4HK065N1525
0.5
Hi
10.8
14.4
36.9
49.1
10.8
14.4
10.8
14.4
10.8
14.4
36C
4HK06501025
0.5
Med
7.2
9.6
24.6
32.8
7.2
9.6
7.2
9.6
7.2
9.6
4HK06501525
0.5
Med
10.8
14.4
36.9
49.1
10.8
14.4
10.8
14.4
10.8
14.4
42C
4HK06501025
0.5
Med
7.2
9.6
24.6
32.8
7.2
9.6
7.2
9.6
7.2
9.6
4HK06501525
0.5
Med
10.8
14.4
36.9
49.1
10.8
14.4
10.8
14.4
10.8
14.4
4HK06501825
0.5
Hi
12.9
17.2
44.7
58.7
12.9
17.2
12.9
17.2
12.9
17.2
48D
4HK06501025
0.5
Med
7.2
9.6
24.6
32.8
7.2
9.6
7.2
9.6
7.2
9.6
4HK06501525
0.5
Med
10.8
14.4
36.9
49.1
10.8
14.4
10.8
14.4
10.8
14.4
4HK06501825
0.5
Hi
12.9
17.2
44.7
58.7
12.9
17.2
12.9
17.2
12.9
17.2
60D
4HK06501025
0.5
#3
7.2
9.6
24.6
32.8
7.2
9.6
7.2
9.6
7.2
9.6
4HK06501525
0.5
#2
10.8
14.4
36.9
49.1
10.8
14.4
10.8
14.4
10.8
14.4
4HK16501825
0.5
#2
12.9
17.2
44.7
58.7
12.9
17.2
12.9
17.2
12.9
17.2
4HK16502525
0.5
#2
18.0
24.0
61.4
81.4
9.0
12.0
18.0
24.0
18.0
24.0
1. See conversion Table 8.
TABLE 14:
Electrical Data - (For
Multi-Source
Power Supply) - Copper Wire - 208/230-3-60
Models
Heater
Model
Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
Circuit
1st
2nd
3rd
1st
2nd
3rd
1st
2nd
3rd
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
60D
4HK16501825
31.9/35.4
22.4/25.9
–
35/40
25/30
–
8/8
10/10
–
4HK16502525
40.8/45.6
31.3/36.1
–
45/50
35/40
–
8/8
8/8
–
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.