Johnson Controls Unitary Products YCCS TEC2603-4 BACnet Installation Instructions Manual Download Page 6

676292-YIM-A-0111

YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions

6

End-of-Line (EOL) Terminations

Daisy-chained RS485 protocol networks require 
End-of-Line (EOL) termination to reduce interference. 
Interference is caused by signal reflection that occurs 
when data transmissions reach the end of a bus 
segment and bounce back (Figure 7). The high baud 
rates on Master-Slave/Token-Passing (MS/TP) bus 
applications require robust EOL termination and strict 
adherence to the EOL termination rules.

On a YCCS System bus or Zone bus, only one EOL 
termination is required due to the fewer number of 
devices on one bus and the shorter wiring length. 
Specifically, the System bus must always have a 
System Manager as the EOL device, and the Zone bus 
must always have a Zone Coordinator as the EOL 
device. Figure 8 shows a YCCS EOL wiring example.  

No EOL = No Signal Cushioning 

(Bounce Back and Noise)

 

No

EOL

EOL

EOL Provides Signal 

Cushioning (No Bounce Back)

FI

G

:in

tr

fr

n

c

Figure 7: Interference

Figure 8: End-of-Line Wiring

Input

Output

Module

24V

COM

CO

M

-

+

BI-1

COM

BI-2

COM

AI-3

COM

AI-4

Monitored Contact

To Temperature, 

RH%,  CO

2

 Sensor, 

Building Pressure, 

Light Sensor, 

Refrigerant Sensor

To 24VAC

BO-3

BO-2

BO-1

BO-4

COM

Monitored Contact

To Scheduled Item 1

To Scheduled Item 2

To Scheduled Item 3

To Scheduled Item 4

Non-

CCS

HVAC

System

Universal

CV Unit

Controller

24V

COM

Zone Sensor

CO

M

-

+

AI-1

COM

AI-2

1

2

3

4

BO-1

BO-2

BO-3

BO-4

BO-5

C

R

G

Y1

Y2

W1

W2

COM

AI-6

COM

AI-7

COM

AI-8

COM

AI-4

COM

AI-5

COM

BI-2

SAT Sensor

RAT Sensor

OAT Sensor

To Zone RH% Sensor

To Zone CO

2

 Sensor

APS

Zone Sensor

COBP Zone Coordinator

System 

Bus

COM

SB-

SB+

EOL

O
N

?

Zone

Bus

COM

ZB

-

ZB

+

EOL

O
N

?

COM

24V

LAN

To 24VAC

System Manager

System 

Bus

COM

SB-

SB+

EOL

O
N

Zone

Bus

COM

ZB-

ZB+

EOL

O
N

COM

24V

Modem

LAN

To 24VAC

To Phone Line

To Ethernet Hub

VAV Zone Coordinator

System 

Bus

COM

SB-

SB+

EOL

O
N

Zone

Bus

COM

ZB-

ZB+

EOL

O
N

COM

24V

LAN

To 24VAC

tape

off

CV Unit Controller

COM

-

+

Simplicity Board

Binary

&

ModBus

This end of the Drain Wire 
connected to cabinet ground

Other System Bus Devices

AI-1

COM

AI-2

1

2

3

4

Other System Bus Devices

Other System Bus Devices

To COBP Zone 
Bus Devices

To VAV Zone 
Bus Devices

Zone Coordinator must be end of line for zone bus

System Manager must be end of line for system bus

TEC2601-4
TEC2602-4
TEC2603-4

Y2
Y1

G

RC

C

RH
W1
W2

Aux

DI1
DI2

RS

Scom

OS
MS

+
_

Ref

CO

M

-

+

FIG

:T

E

C

_

E

O

L

Summary of Contents for YCCS TEC2603-4 BACnet

Page 1: ...ler Skip this step if the screw is not installed on the bottom of the cover 2 Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1 IMPO...

Page 2: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Page 3: ...tat controller continue in a daisy chained fashion to the next YCCS System Bus device Note The bus wiring must be twisted pair lines Do not run the bus wiring in the same conduit as line voltage wirin...

Page 4: ...ipment Transformer 24 VAC for Heating Stages Energizes on a Call for First Stage Heating Energizes on a Call for Second Stage Heating Auxiliary Output Digital Input 1 Filter Only Digital Input 2 Disab...

Page 5: ...128 O N 24V COM 24V CO M COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 1 6 8 4 2 128 O N 24V COM 24V CO M Drain Wire Drain Wire Tape back Drain Wire Drain Wire Address 4 Address 6 Address 7 VAV Rooftop Unit...

Page 6: ...AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Sch...

Page 7: ...NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu see the Main User Menu section access the Installer Configu...

Page 8: ...he configured password is required to proceed Use the UP DOWN arrow keys to enter the configured password then press the MENU key to proceed through the Installer Configuration Menu parameters 2 Once...

Page 9: ...eadband between the heating and cooling setpoints Default 2 0 Deg F 1 0 Deg C Options 2 0 Deg F 3 0 Deg F 4 0 Deg F 1 0 Deg C 1 5 Deg C 2 0 Deg C Cooling Unocc Setpoint Sets the unoccupied cooling set...

Page 10: ...removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Fro...

Page 11: ...ables the thermostat controller to activate the fan in response to a call for heating Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off Note The fan delay...

Page 12: ...the fan output is also disabled Requires that an outside air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Disabl...

Page 13: ...ne where communication is unreliable partition disconnect and isolate a portion of the system Bus for testing purposes and test the Bus portion connected to the System Manager Correcting Physical Comm...

Page 14: ...om Probable Causes Multiple Symptoms The baud rate may have been changed on some devices on the network but not all devices A download may be in progress There may be a fault at a device A repeater ma...

Page 15: ...on Repair Information If the TEC2603 4 Thermostat Controller fails to operate within its specifications replace the unit For a replacement thermostat controller contact the nearest Johnson Controls re...

Page 16: ...F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...

Reviews: