Johnson Controls Unitary Products YCCS TEC2603-4 BACnet Installation Instructions Manual Download Page 3

YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions 

3

676292-YIM-A-0111

Wiring

When an existing thermostat controller is replaced, 
remove and label the wires to identify the terminal 
functions. When a TEC2603-4 Thermostat Controller is 
replaced, simply remove the old screw terminal blocks 
and reinsert them onto the PCB of the replacement 
thermostat controller.           

To wire the thermostat controller:

1.

Strip the ends of each wire 1/4 in. (6 mm) and 
connect them to the appropriate screw terminals as 
indicated in Figure 5.

Note:

If multiple wires are inserted into the 

terminals, be sure to properly twist the wires 
together prior to inserting them into the terminal 
connectors.

2.

Carefully push any excess wire back into the wall. 

Note:

Seal the hole in the wall with fireproof 

material to prevent drafts from affecting the 
ambient temperature readings.

3.

Reinsert the screw terminal blocks onto the PCB.

4.

Reattach the thermostat controller cover to the 
mounting base (top side first).

5.

Use a Phillips-head screwdriver to reinstall the 
security screw on the bottom of the thermostat 
controller cover. 

Connecting the YCCS System Bus

To connect the YCCS System Bus:

1.

Set the YCCS System Bus address of the 
thermostat controller per the engineering drawings 
and test for bus voltage and polarity prior to wiring 
the YCCS System Bus. Use the 

Com addr

 

parameter to set the system bus address for the 
thermostat controller.

2.

Observe the polarity when connecting the bus 
wires to the thermostat controller.

3.

After the bus wires are connected to the first 
thermostat controller, continue in a daisy-chained 
fashion to the next YCCS System Bus device.

Note:

The bus wiring must be twisted-pair lines. 

Do not run the bus wiring in the same conduit as 
line voltage wiring (30 VAC or above) or other 
wiring that switches power to highly inductive loads 
(such as contactors, coils, motors, or generators).

System Communication RS-485 serial protocol Bus 
segments requires proper End-of-Line (EOL) 
termination to reduce interference from signal bounce 
back on the Bus segment. The system requires at least 
one termination at either end of the Bus segment. The 
System Manager ships with the EOL switch in the 
factory default, ON (up) position. Ensure that this 
device is EOL on one end of the System Bus segment. 
See the 

End-of-Line (EOL) Terminations

 section for 

more information. 

The thermostat controller has automatic baud rate 
detection. Do not exceed the maximum number of 
devices allowed on a YCCS System bus (38 devices 
total, including up to 24 TEC Series thermostat 
controllers).

Be sure that the wiring terminations are set correctly 
and that all communication wiring is daisy-chained with 
no taps. See the 

Troubleshooting

 section for 

information on correcting physical bus problems.

Figure 5 shows TEC2603-4 Thermostat Controller 
wiring; see Figure 6 for a YCCS communication riser. 

   

!

CAUTION: Risk of Electric Shock.

Disconnect the power supply before 
making electrical connections to avoid 
electric shock. 

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment. 

IMPORTANT:

Make all wiring connections in 

accordance with local, national, and regional 
regulations. Do not exceed the electrical ratings of 
the TEC2603-4 Thermostat Controller.

Summary of Contents for YCCS TEC2603-4 BACnet

Page 1: ...ler Skip this step if the screw is not installed on the bottom of the cover 2 Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1 IMPO...

Page 2: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Page 3: ...tat controller continue in a daisy chained fashion to the next YCCS System Bus device Note The bus wiring must be twisted pair lines Do not run the bus wiring in the same conduit as line voltage wirin...

Page 4: ...ipment Transformer 24 VAC for Heating Stages Energizes on a Call for First Stage Heating Energizes on a Call for Second Stage Heating Auxiliary Output Digital Input 1 Filter Only Digital Input 2 Disab...

Page 5: ...128 O N 24V COM 24V CO M COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 1 6 8 4 2 128 O N 24V COM 24V CO M Drain Wire Drain Wire Tape back Drain Wire Drain Wire Address 4 Address 6 Address 7 VAV Rooftop Unit...

Page 6: ...AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Sch...

Page 7: ...NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu see the Main User Menu section access the Installer Configu...

Page 8: ...he configured password is required to proceed Use the UP DOWN arrow keys to enter the configured password then press the MENU key to proceed through the Installer Configuration Menu parameters 2 Once...

Page 9: ...eadband between the heating and cooling setpoints Default 2 0 Deg F 1 0 Deg C Options 2 0 Deg F 3 0 Deg F 4 0 Deg F 1 0 Deg C 1 5 Deg C 2 0 Deg C Cooling Unocc Setpoint Sets the unoccupied cooling set...

Page 10: ...removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Fro...

Page 11: ...ables the thermostat controller to activate the fan in response to a call for heating Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off Note The fan delay...

Page 12: ...the fan output is also disabled Requires that an outside air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Disabl...

Page 13: ...ne where communication is unreliable partition disconnect and isolate a portion of the system Bus for testing purposes and test the Bus portion connected to the System Manager Correcting Physical Comm...

Page 14: ...om Probable Causes Multiple Symptoms The baud rate may have been changed on some devices on the network but not all devices A download may be in progress There may be a fault at a device A repeater ma...

Page 15: ...on Repair Information If the TEC2603 4 Thermostat Controller fails to operate within its specifications replace the unit For a replacement thermostat controller contact the nearest Johnson Controls re...

Page 16: ...F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...

Reviews: