background image

676292-YIM-A-0111

YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions

10

Table 2:  Installer Configuration Menu  (Part 1 of 3)

Parameter 
Appearing 

on Display

1

Description and Default

Selection Options

Com addr

YCCS System Bus address of the 
controller.
Default: 

254

Range: 

42

 to 

65

Pswrd

Set at System Manager.

DI1

Set to 

Filter 

by System Manager. 

(Value cannot be changed)

(Filter):

 A Filter alarm is displayed. This alarm can be connected to 

a differential pressure switch that monitors a filter.

DI2

Disabled by System Manager.

MenuScro

Gives the option of having the 
display continuously scroll the 
parameters.
Default: 

on

(off):

 The scroll is inactive.

(on):

 The scroll is active.

Lockout

Disables access at TEC to scheduling, setpoints, and mode settings. Set by System Manager to 

No 

Access

 (2). Value cannot be changed.

Pwr del

2

Sets the delay time period at 
thermostat controller powerup, or 
each time power is removed and 
reapplied, before any operation 
(fan, heating, or cooling) is 
authorized. Also can be used to 
sequence the startup of multiple 
units in one location.
Default: 

10.0 sec

Range: 

10.0

 to 

120.0 sec

Frost pr

Provides a minimum heating 
setpoint of 42.0°F/5.5°C to prevent 
freezing in the zone controlled by 
the thermostat controller. 
Default: 

off

(on):

 Enabled

(off):

 Disabled

Heat max

Set at System Manager (Heating Occ Setpoint, Heating Unocc Setpoint).

Cool min

Set at System Manager (Cooling Occ Setpoint, Cooling Unocc Setpoint).

Pband

Proportional Band used by the PI 
temperature control loop of the 
thermostat controller.
Pband is not converted with C or F 
scale and is always shown with a 
range of 2 to 8.
Default: 

2

 (

2.0F°/1.1C°

)

Value

F Scale Pband/C Scale Pband

2

2.0F°/1.1C°

3

3.0F°/1.7C°

4

4.0F°/2.2C°

5

5.0F°/2.8C°

6

6.0F°/3.3C°

7

7.0F°/3.9C°

8

8.0F°/4.4C°

Note:

The use of a larger proportional band is not to use the 

thermostat controller as a discharge air controller device. The use of 
a larger proportional band can be used to solve issues for flawed 
HVAC design with basic sizing and thermostat controller location 
errors that cannot be worked around.

Summary of Contents for YCCS TEC2603-4 BACnet

Page 1: ...ler Skip this step if the screw is not installed on the bottom of the cover 2 Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1 IMPO...

Page 2: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Page 3: ...tat controller continue in a daisy chained fashion to the next YCCS System Bus device Note The bus wiring must be twisted pair lines Do not run the bus wiring in the same conduit as line voltage wirin...

Page 4: ...ipment Transformer 24 VAC for Heating Stages Energizes on a Call for First Stage Heating Energizes on a Call for Second Stage Heating Auxiliary Output Digital Input 1 Filter Only Digital Input 2 Disab...

Page 5: ...128 O N 24V COM 24V CO M COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 1 6 8 4 2 128 O N 24V COM 24V CO M Drain Wire Drain Wire Tape back Drain Wire Drain Wire Address 4 Address 6 Address 7 VAV Rooftop Unit...

Page 6: ...AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Sch...

Page 7: ...NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu see the Main User Menu section access the Installer Configu...

Page 8: ...he configured password is required to proceed Use the UP DOWN arrow keys to enter the configured password then press the MENU key to proceed through the Installer Configuration Menu parameters 2 Once...

Page 9: ...eadband between the heating and cooling setpoints Default 2 0 Deg F 1 0 Deg C Options 2 0 Deg F 3 0 Deg F 4 0 Deg F 1 0 Deg C 1 5 Deg C 2 0 Deg C Cooling Unocc Setpoint Sets the unoccupied cooling set...

Page 10: ...removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Fro...

Page 11: ...ables the thermostat controller to activate the fan in response to a call for heating Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off Note The fan delay...

Page 12: ...the fan output is also disabled Requires that an outside air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Disabl...

Page 13: ...ne where communication is unreliable partition disconnect and isolate a portion of the system Bus for testing purposes and test the Bus portion connected to the System Manager Correcting Physical Comm...

Page 14: ...om Probable Causes Multiple Symptoms The baud rate may have been changed on some devices on the network but not all devices A download may be in progress There may be a fault at a device A repeater ma...

Page 15: ...on Repair Information If the TEC2603 4 Thermostat Controller fails to operate within its specifications replace the unit For a replacement thermostat controller contact the nearest Johnson Controls re...

Page 16: ...F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...

Reviews: