676292-YIM-A-0111
YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions
10
Table 2: Installer Configuration Menu (Part 1 of 3)
Parameter
Appearing
on Display
1
Description and Default
Selection Options
Com addr
YCCS System Bus address of the
controller.
Default:
254
Range:
42
to
65
Pswrd
Set at System Manager.
DI1
Set to
Filter
by System Manager.
(Value cannot be changed)
(Filter):
A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
DI2
Disabled by System Manager.
MenuScro
Gives the option of having the
display continuously scroll the
parameters.
Default:
on
(off):
The scroll is inactive.
(on):
The scroll is active.
Lockout
Disables access at TEC to scheduling, setpoints, and mode settings. Set by System Manager to
No
Access
(2). Value cannot be changed.
Pwr del
2
Sets the delay time period at
thermostat controller powerup, or
each time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default:
10.0 sec
Range:
10.0
to
120.0 sec
Frost pr
Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat controller.
Default:
off
(on):
Enabled
(off):
Disabled
Heat max
Set at System Manager (Heating Occ Setpoint, Heating Unocc Setpoint).
Cool min
Set at System Manager (Cooling Occ Setpoint, Cooling Unocc Setpoint).
Pband
Proportional Band used by the PI
temperature control loop of the
thermostat controller.
Pband is not converted with C or F
scale and is always shown with a
range of 2 to 8.
Default:
2
(
2.0F°/1.1C°
)
Value
F Scale Pband/C Scale Pband
2
2.0F°/1.1C°
3
3.0F°/1.7C°
4
4.0F°/2.2C°
5
5.0F°/2.8C°
6
6.0F°/3.3C°
7
7.0F°/3.9C°
8
8.0F°/4.4C°
Note:
The use of a larger proportional band is not to use the
thermostat controller as a discharge air controller device. The use of
a larger proportional band can be used to solve issues for flawed
HVAC design with basic sizing and thermostat controller location
errors that cannot be worked around.