There must be a link 

between High Voltage 

terminals 1 & 6 and high 

voltage termnials 3 & 6. 

Make sure both links are 

present

MAF STAT CONNECTED NOT CALLING FOR HEAT (BOILER NOT FIRING) WHEN MAF STAT ON MAXIMUM

NO

YES

YES

NO

NO

YES

YES

YES

NO

YES

NO

NO

NO

NO

YES

YES

NO

Is there 230 ~ 250VAC across High Voltage terminals 2 & 4?

Is there 230 ~ 250VAC across High Voltage terminals 1 & 2?

Measure DC voltage (5.1V DC Max.) across 

Low Voltage

 terminals 3 & 4

Is measured voltage greater 

than 4.7V

Is measured resistance 

greater than 11K?

Is measured voltage greater 

than 4.7V

Check pipe sensor and 

connections. If sound, isolate 

from mains & measure 

resistance across plug J2 pins 

5 & 6

Is measured voltage greater than 4.19V?

Is there an external clock fitted?

Measure DC voltage (5.1V DC 

Max.) across 

Low Voltage

 

terminals 5 & 6

Check black wire of MAF stat 

goes to 

Low Voltage

 terminal 3 

and red wire of MAF stat goes 

to low voltage terminal 4. Ensure 

all connections are sound

Check clock is on & measure 

output

Check for live supply into clock. 

Repace clock if live is present

Is 230 ~ 250VAC present?

Check harness connections 

to PCB. If all OK Replace 

PCB

Remove MAF stat connections 

and link 

Low Voltage

 terminals 

TPV & 3. Is there 230 ~ 250VAC 

across High Voltage terminals 

2 & 4?

Open circuit between clock 
out & High Voltage terminal 

block 1

Unit mains 

supply is 

missing. 

Check spur 

e.g. fuse is 

intact

Check 

connections 

to high 

voltage 

terminals 

2 & 3

Problem with switched live output going from High Voltage terminal 3 

to switch live of boiler

Is there 230 ~ 250VAC across High Voltage terminals 2 & 3?

14. CIRCUIT 

DIAGRAM

14. FAULT 

FINDING

FIGURE 4.  AQUAIR S CIRCUIT DIAGRAM

LINK TO SET

FAN SPEED MIN.

LINK FOR SUMMER 

VENT OR TO SET

FAN SPEED MAX.

VOLT FREE

DIGITAL STAT

MAF STAT

PIPE SENSOR TEST

OPTIONAL JUMPER

(SEE INSTRUCTIONS)

REMOVE LINK IF 

CLOCK OR

SWITCHED LIVE

IS CONNECTED

MAINS

EARTH

LINK TO TEST

DEMAND

HIGH VOLTAGE

TERMINAL

LOW VOLTAGE

TERMINAL

PIPE SENSOR

FAN

PCB

COLOUR CODE

bn

BROWN

bl

BLUE

bk

BLACK

g/y

GREEN/YELLOW

r

RED

w

WHITE

or

ORANGE

y

YELLOW

Summary of Contents for Aquair S-10

Page 1: ...ON COMMISSIONING SERVICING INSTRUCTIONS AQUAIR S SERIES of Water to Air Space Heaters These instructions are to be left with the User Publication No ZZ 1416 4 October 2014 COMMISSIONING S sustainable...

Page 2: ...turn Air System 5 9 Electrical 6 10 Fan Performance Graph 6 11 Operating Mode 6 12 Commissioning 7 13 Servicing Maintenance 7 14 Circuit Diagram 11 15 Notes 9 16 Dimensions 10 17 Spares List 11 18 Exp...

Page 3: ...ature of 60 C Water connections are left or right handed through knockouts in the sides of the cabinet 2 2 The air is drawn in through the air filter or air cleaner if fitted and the heat exchanger by...

Page 4: ...t 5 1 2 All wiring must be in accordance with the appropriate standards 5 1 3 Ensure safety regulations and practices are adhered to when installing and using this equipment 5 2 DUCTING INFORMATION 5...

Page 5: ...o 1000 0302300 MUST be fitted to the top of the unit Call Johnson Starley Ltd for details Tel 01604 762881 7 7 4 Swivel the disc cap by breaking the paint seal tap the disc and swivel Remove the cap i...

Page 6: ...thermista stat demand 11 1 3 With no thermista stat connected the fan will run when a water temperature of 44 C is reached the fan speed is controlled by the water temperature The maximum fan speed re...

Page 7: ...ter and unscrew the two retaining screws holding the front cover on the unit gently pull it forward Maintenance should be carried out at least once per year 13 1 1 Check that the heat exchanger airway...

Page 8: ...voltage terminal 4 Ensure all connections are sound Check clock is on measure output Check for live supply into clock Repace clock if live is present Is 230 250VAC present Check harness connections to...

Page 9: ...ter then 28K YES YES NO In there 230 250 VAC across high voltage terminals 1 2 If there 230 250 VAC across High Voltage terminals 1 2 Make sure mains is present across High Voltage terminals 2 3 Is th...

Page 10: ...02 631 402 42 22 53 97 463 44 331 169 365 61 445 787 22 53 97 517 48 296 336 60 325 52 341 350 44 42 362 300 768 48 362 402 53 97 22 384 217 44 42 550 205 365 55 48 FIGURE 7 AQUAIR S 20 DIMENSIONS FIG...

Page 11: ...FROM HEAT SOURCE FIGURE 8 AQUAIR S EXPLODED DIAGRAM ITEM DESCRIPTION QTY 10S 16S 20S 1 Air filter 1 AQ10 0182005 AQ16 0182005 AQ20 0182005 2 Air circulation fan with EC technology 1 AQ10 0126005 AQ16...

Page 12: ...ndstarley co uk Reception 01604 762881 Fax 01604 767408 Johnson Starley Dravo Division Industrial H V Sales 01604 707022 sales johnsonandstarley co uk www dravo co uk Anniversary 1922 2012 In the inte...

Reviews: