Sales/Spares 01604 707012   Replacement Help Line 01604 707011

FAN NOT OPERATING WHEN PIPE IS ABOVE 60°C

NO

YES

YES

YES

NO

YES

NO

NO

YES

NO

NO

Is there and external clock fitted or external mains room stat 

fitted?

Is there and external clock fitted or external mains room stat 

fitted?

Check for mains going into fan plug

There must be a link between high voltage terminals 1 & 6 and 

high voltage terminals 3 & 6. Make sure both links are present

There must be a link between 

High Voltage

 terminals 1 & 6 and 

high voltage terminals 3 & 6. Make sure both links are present

Measure DC voltage (0 to 10V) within Low Voltage fan connector 

(blue & yellow)

Make sure mains is present across high voltage terminals   1 & 

2 and 3 & 4

Make sure mains is present across High Voltage terminals   1 & 

2 and 2 & 3

Is measured voltage greater than 2V?

Check pipe and connections. 

If sound, isolate from mains 

& measure resistance across 

plug J2 pins 5 & 6

Does the actual pipe temp. 

match the approx. pipe temp. 

for the measured voltage in 

Table A?

Is measured resistance greater 

than 11K?

Faulty fan

Faulty 

PCB

Check sensor is fitted correctly. 

If it is then replace sensor.

Faulty PCB

PCB is not seeing sensor. 

Confirm by measuring 

sensor resistance. Replace 

sensor if resistance is 

greater then 28K.

YES

YES

NO

In there 230 ~ 250 VAC across high voltage terminals 1 & 2?

If there 230 ~ 250 VAC across High Voltage terminals 1 & 2?

Make sure mains is present across High Voltage terminals 2 & 3

Is the MAF stat connected?

Is fan now running?

Link out low voltage terminals 3 & 4.

Measure voltage across Low Voltage terminals 5 & 6

Is measured voltage greater than 4.7V DC?

Make sure clock or room stat supplies mains voltage to high voltage 

terminals 1 & 2. No mains - no fan operation (except for summer vent)

DC VOLTAGE 

ACROSS PIPE 

SENSOR

APPROX. PIPE 

TEMP. 

°

C

DC VOLTAGE 

ACROSS PIPE 

SENSOR

APPROX. PIPE 

TEMP. 

°

C

DC VOLTAGE 

ACROSS PIPE 

SENSOR

APPROX. PIPE 

TEMP. 

°

C

DC VOLTAGE 

ACROSS PIPE 

SENSOR

APPROX. PIPE 

TEMP. 

°

C

3.24

10

2.13

33

1.26

56

0.73

79

3.19

11

2.08

34

1.23

57

0.71

80

3.14

12

2.04

35

1.20

58

0.70

81

3.09

13

1.99

36

1.17

59

0.68

82

3.04

14

1.95

37

1.15

60

0.66

83

2.99

15

1.91

38

1.12

61

0.65

84

2.94

16

1.87

39

1.09

62

0.63

85

2.89

17

1.83

40

1.07

63

0.63

86

2.84

18

1.79

41

1.04

64

0.60

87

2.79

19

1.75

42

1.02

65

0.59

88

2.75

20

1.71

43

0.99

66

0.58

89

2.70

21

1.67

44

0.97

67

0.56

90

2.65

22

1.63

45

0.95

68

0.55

91

2.60

23

1.59

46

0.92

69

0.54

92

2.55

24

1.56

47

0.90

70

0.53

93

2.50

25

1.52

48

0.88

71

0.51

94

2.45

26

1.49

49

0.86

72

0.50

95

2.40

27

1.45

50

0.84

73

0.49

96

2.36

28

1.42

51

0.82

74

0.48

97

2.31

29

1.39

52

0.80

75

0.47

98

2.26

30

1.35

53

0.78

76

0.46

99

2.22

31

1.32

54

0.76

77

0.45

100

2.17

32

1.29

55

0.75

78

TABLE A

Summary of Contents for Aquair S-10

Page 1: ...ON COMMISSIONING SERVICING INSTRUCTIONS AQUAIR S SERIES of Water to Air Space Heaters These instructions are to be left with the User Publication No ZZ 1416 4 October 2014 COMMISSIONING S sustainable...

Page 2: ...turn Air System 5 9 Electrical 6 10 Fan Performance Graph 6 11 Operating Mode 6 12 Commissioning 7 13 Servicing Maintenance 7 14 Circuit Diagram 11 15 Notes 9 16 Dimensions 10 17 Spares List 11 18 Exp...

Page 3: ...ature of 60 C Water connections are left or right handed through knockouts in the sides of the cabinet 2 2 The air is drawn in through the air filter or air cleaner if fitted and the heat exchanger by...

Page 4: ...t 5 1 2 All wiring must be in accordance with the appropriate standards 5 1 3 Ensure safety regulations and practices are adhered to when installing and using this equipment 5 2 DUCTING INFORMATION 5...

Page 5: ...o 1000 0302300 MUST be fitted to the top of the unit Call Johnson Starley Ltd for details Tel 01604 762881 7 7 4 Swivel the disc cap by breaking the paint seal tap the disc and swivel Remove the cap i...

Page 6: ...thermista stat demand 11 1 3 With no thermista stat connected the fan will run when a water temperature of 44 C is reached the fan speed is controlled by the water temperature The maximum fan speed re...

Page 7: ...ter and unscrew the two retaining screws holding the front cover on the unit gently pull it forward Maintenance should be carried out at least once per year 13 1 1 Check that the heat exchanger airway...

Page 8: ...voltage terminal 4 Ensure all connections are sound Check clock is on measure output Check for live supply into clock Repace clock if live is present Is 230 250VAC present Check harness connections to...

Page 9: ...ter then 28K YES YES NO In there 230 250 VAC across high voltage terminals 1 2 If there 230 250 VAC across High Voltage terminals 1 2 Make sure mains is present across High Voltage terminals 2 3 Is th...

Page 10: ...02 631 402 42 22 53 97 463 44 331 169 365 61 445 787 22 53 97 517 48 296 336 60 325 52 341 350 44 42 362 300 768 48 362 402 53 97 22 384 217 44 42 550 205 365 55 48 FIGURE 7 AQUAIR S 20 DIMENSIONS FIG...

Page 11: ...FROM HEAT SOURCE FIGURE 8 AQUAIR S EXPLODED DIAGRAM ITEM DESCRIPTION QTY 10S 16S 20S 1 Air filter 1 AQ10 0182005 AQ16 0182005 AQ20 0182005 2 Air circulation fan with EC technology 1 AQ10 0126005 AQ16...

Page 12: ...ndstarley co uk Reception 01604 762881 Fax 01604 767408 Johnson Starley Dravo Division Industrial H V Sales 01604 707022 sales johnsonandstarley co uk www dravo co uk Anniversary 1922 2012 In the inte...