Jetter AG
Programming | 7
JXM-IO-E32 User Manual
34 / 38
Code
Description
0x3100
Voltage exceeds the permitted limits
0x4200
Device temperature is too high
0x8110
CAN data overrun (lost objects)
0x8130
Life guard error or heartbeat error
0x8140
Recovered from bus-off
0x8210
Processing errors due to incorrect length of PDOs
0x8220
PDO length exceeded
0xff00
Configuration error on the device
0xff01
IO port OVERVOLTAGE
0xff02
IO port OVERCURRENT
0xff03
IO port SUPPLYFAULT
0xff06
IO port TIMEOUT
0xff08
IO port OVERTEMPERATURE signaled by PT1000 sensor
Tab. 39:
Emergency Error Codes
7.8.1 Heartbeat
The device sends a heartbeat message cyclically as soon as it is in the
Pre-Operational
state.
Index
Subindex
Description
Type
Type of
access
Default value
0x1017
0
Producer heartbeat time in ms
U16
R/W
1000
Tab. 40:
Index of the heartbeat message