type anchor bolt will make removal of a unit easier
if required.
If the floor is warped, uneven or in poor condition,
make necessary repairs before positioning the unit.
Once the unit is in place, it should be level within
1/8 inch side-to-side (width) and 1/8-inch front-to-
back (depth).
Clearances
Provide adequate space around each unit for
unrestricted
Spreader Bar
access for installation
and maintenance. Unit dimensions
are given in the Dimensions and Weights chapter.
It is critical that adequate space is provided for
service and maintenance of evaporator, condenser
and compressor. A minimum of 36 inches above
the unit is recommended for effective compressor
service. A minimum clearance of 3 ft.-6 inches is
required to open the control panel door.
Important: In all cases, local codes will take
precedence over these recommendations.
Ventilation
Provisions must be made to remove heat generated
by unit operation from the equipment room.
Ventilation must be adequate to maintain an
ambient temperature lower than 125°F.
Drainage
Front View
Locate the unit near a large capacity drain for
drain-down
Spreader
during shutdown or repair.
Handling
FWCD units are shipped stretch-wrapped and
bolted to a shipping skid unless special packaging
is arranged.
The skidded unit can be moved by using a fork
truck of suitable capacity. See Dimensions and
Weights chapter for unit weights.
When moving the unit, the lifting forks must be
positioned under the shipping skid as wide as
possible. Lift the unit and move it to the desired
location.
Once the unit is at the installation location,
remove the stretch wrap. Inspect the unit for
damage and report if damage is found.
Optional “ship loose” items may be inside the
control box, attached to the skid or shipped
separately depending on options selected.
Summary of Contents for FWCD Series
Page 1: ...FWCD Series Chillers Installation Operation Maintenance...
Page 2: ...Jetson www JetsonHVAC com 2...
Page 30: ...Jetson www JetsonHVAC com 30 Figure 4 FWCD array dimensions brazed plate condenser...
Page 31: ...Jetson www JetsonHVAC com 31 Figure 5 FWCD dimensions shell and tube condenser...
Page 32: ...Jetson www JetsonHVAC com 32 Figure 6 FWCD array dimensions shell and tube condenser...
Page 33: ...Jetson www JetsonHVAC com 33 Figure 7 FWCD dimensions remote condenser...
Page 34: ...Jetson www JetsonHVAC com 34 Figure 8 FWCD array dimensions remote condenser...
Page 82: ...Jetson www JetsonHVAC com 82 Wiring Figure 26 FWCD wiring schematic...
Page 83: ...Jetson www JetsonHVAC com 83 Figure 27 FWCD wiring schematic continued...
Page 84: ...Jetson www JetsonHVAC com 84 Figure 28 FWCD dual circuit secondary wiring schematic...
Page 85: ...Jetson www JetsonHVAC com 85 Figure 29 FWCD dual circuit secondary wiring schematic continued...
Page 86: ...Jetson www JetsonHVAC com 86 Figure 30 Field wiring FWCD single unit single circuit...
Page 87: ...Jetson www JetsonHVAC com 87 Figure 31 Field wiring FWCD single unit dual circuit...