Jetson
www.JetsonHVAC.com
18
Digit 30 — Local Unit Controller Interface
0 = Keypad with Dot Pixel Display -
keypad, 128 x 64 dot pixel STN monochrome graphics LCD
with 2.8" diagonal viewing area
B = 15.4-in. Color Touchscreen -
Information and graphics are shown on high resolution
(1280x800) LCD display with LED back lighting. The high-resolution screen makes it easy for the
user to manage complex installations without losing the overall view or requiring a separate laptop.
Pages can be navigated in a fast and straightforward manner.
Digit 31 — Remote BMS Interface (Digital Comm)
0 = None
2 = Lon Talk®
4 = BACnet® MS/TP
5 = BACnet® IP
6 = MODBUS®
8 = Johnson N2
Digit 32 — Blank
0 = Blank
Digit 33 — Blank
0 = Blank
Digit 34 — Refrigeration Options
1 = Active Freeze Protection (All Circuits) –
Active freeze protection is a suction pressure-based
freeze protection. Active Freeze Protection is standard on all FWCD Series chillers. The chiller’s
unit controller continually monitors the saturated suction pressure and will open (energize) the
Active Freeze Protection solenoid if the suction pressure falls to approximately 101 psig (32°F).
The solenoid closes (de-energizes) when the pressure climbs to approximately 105 psig (34°F) and
the freezing potential no longer exists.
2 = Hot Gas Bypass (All Circuits) -
Hot gas bypass can stabilize the system balance point by
diverting hot, high- pressure refrigerant vapor from the discharge line directly to the low-pressure
side of the system. This tactic keeps the compressor more fully loaded while the evaporator satisfies
the part-load condition. The Jetson Active Freeze Protection can be configured to function as Hot
Gas Bypass by configuring the controller to monitor both the leaving water temperature and the
suction temperature. In Hot Gas Bypass operating mode, the Active Freeze Protection provides an
additional step of capacity.
Summary of Contents for FWCD Series
Page 1: ...FWCD Series Chillers Installation Operation Maintenance...
Page 2: ...Jetson www JetsonHVAC com 2...
Page 30: ...Jetson www JetsonHVAC com 30 Figure 4 FWCD array dimensions brazed plate condenser...
Page 31: ...Jetson www JetsonHVAC com 31 Figure 5 FWCD dimensions shell and tube condenser...
Page 32: ...Jetson www JetsonHVAC com 32 Figure 6 FWCD array dimensions shell and tube condenser...
Page 33: ...Jetson www JetsonHVAC com 33 Figure 7 FWCD dimensions remote condenser...
Page 34: ...Jetson www JetsonHVAC com 34 Figure 8 FWCD array dimensions remote condenser...
Page 82: ...Jetson www JetsonHVAC com 82 Wiring Figure 26 FWCD wiring schematic...
Page 83: ...Jetson www JetsonHVAC com 83 Figure 27 FWCD wiring schematic continued...
Page 84: ...Jetson www JetsonHVAC com 84 Figure 28 FWCD dual circuit secondary wiring schematic...
Page 85: ...Jetson www JetsonHVAC com 85 Figure 29 FWCD dual circuit secondary wiring schematic continued...
Page 86: ...Jetson www JetsonHVAC com 86 Figure 30 Field wiring FWCD single unit single circuit...
Page 87: ...Jetson www JetsonHVAC com 87 Figure 31 Field wiring FWCD single unit dual circuit...