Digit 12 — Efficiency/Capacity
1 = Standard Efficiency –
Standard sized evaporator.
2 = High-Capacity Evaporator
– High-capacity evaporator for glycol applications or for 40F
leaving water applications.
Digit 13 — Design Sequence
0 = Factory Assigned
Digit 14 — Array System
0 = Non-Array System –
FWCD chillers can be applied in standalone applications needing
between 20 to 75 tons of cooling. In standalone applications, chiller headers are not required and the
“no header” option can be selected in Digit 36.
1 = Array System -
More than one FWCD modular chiller may be piped together (to form an array
of chillers) for higher capacity and/or redundant chiller applications, an array controller package
must be provided from the factory. The number of modular chillers that can be physically piped
together to form an array and share a common header is limited to approximately 300 total tons or
900 gpm.
Digit 15 — Evaporator Heat Exchanger Type
0 = Brazed Plate
- Brazed plate heat exchangers are one of the most efficient ways to transfer heat.
They are designed to provide unparalleled performance with the lowest life-cycle cost.
Digit 16 — Evaporator Fluid Type
0 = Water
2 = Ethylene Glycol
3 = Propylene Glycol
Digit 17 — Evaporator Flow
0 = Constant Flow Primary -
Constant flow pumping systems utilize a staged cooling system and
a constant flow water pumping system. No modules are isolated at part load. Flow from “off”
chillers mixes with the flow from active chillers in creating the leaving array temperature. The load
may not be less than 25% of the full load in constant flow applications.
1 = Variable Flow Primary -
Variable flow systems utilize compressor staging and motorized
isolation valves with a variable flow water pumping system to modulate cooling and water flow to
meet chilled water needs and save operating energy costs. Cooling capacity is modulated by staging
Summary of Contents for FWCD Series
Page 1: ...FWCD Series Chillers Installation Operation Maintenance...
Page 2: ...Jetson www JetsonHVAC com 2...
Page 30: ...Jetson www JetsonHVAC com 30 Figure 4 FWCD array dimensions brazed plate condenser...
Page 31: ...Jetson www JetsonHVAC com 31 Figure 5 FWCD dimensions shell and tube condenser...
Page 32: ...Jetson www JetsonHVAC com 32 Figure 6 FWCD array dimensions shell and tube condenser...
Page 33: ...Jetson www JetsonHVAC com 33 Figure 7 FWCD dimensions remote condenser...
Page 34: ...Jetson www JetsonHVAC com 34 Figure 8 FWCD array dimensions remote condenser...
Page 82: ...Jetson www JetsonHVAC com 82 Wiring Figure 26 FWCD wiring schematic...
Page 83: ...Jetson www JetsonHVAC com 83 Figure 27 FWCD wiring schematic continued...
Page 84: ...Jetson www JetsonHVAC com 84 Figure 28 FWCD dual circuit secondary wiring schematic...
Page 85: ...Jetson www JetsonHVAC com 85 Figure 29 FWCD dual circuit secondary wiring schematic continued...
Page 86: ...Jetson www JetsonHVAC com 86 Figure 30 Field wiring FWCD single unit single circuit...
Page 87: ...Jetson www JetsonHVAC com 87 Figure 31 Field wiring FWCD single unit dual circuit...