background image

Grey Water Interface Unit 12L

Tel. +47 70 03 91 00

www.jetsgroup.com

Product No. GWT800PL

Doc. Rev.: 2 (2019-06-17)

7

9

Remove the Tank/Pipe Seals 

from 

the tank 

.

Service and Maintenance - Assembly Instructions

Assembly is to be performed in the reverse order of the disassembly procedure.

Scheduled Maintenance

Interval

Action

Note

As required.

Check for damage to equipment. 
Replace or repair damaged equipment 
and take measures to prevent future 
damage to the system.

See maintenance routines as described in the technical 
information for products where it is applicable, i.e. the 
discharge valve.

Troubleshooting

Jets Vacuum AS provides the following troubleshooting information to assist in resolving issues that may arise with your installation. For more 
detailed information or assistance, please contact Jets Vacuum AS.

Problem

Cause

Action

Tank content is not discharged.

No vacuum.

Check sufficient vacuum is being generated.

Discharge time is too short.

Increase the discharge time, up to a Maximum of 2 
seconds, after the tank is empty.

Valve is blocked due to debris.

Remove the debris.

Defective non-return valve.

Clean or replace the non-return valve.

Leaks in the vacuum hose(s) on the 
valve.

Replace the hose(s) or check that hose(s) are fitted 
correctly.

The vacuum hose/s on the valve are 
disconnected.

Reconnect the hose(s).

Reduced vacuum due to backflow in 
the piping.

Check the pipe installation.

Malfunction of the level sensor.

Replace the level sensor if necessary. 

Malfunction of the valve.

Refer to technical information for the valve. Replace the 
valve if necessary.

Continuous discharge.

Valve is blocked due to debris.

Clean the valve and remove debris. Replace the valve, if 
needed.

Malfunction of the level sensor.

Replace the level sensor if necessary. 

Malfunction of the valve.

Refer to technical information for the valve. Replace the 
valve if necessary.

Summary of Contents for GWT800PL

Page 1: ...d upon request Information provided herein is solely for information purposes does not constitute any warranty or representation of any kind and is subject to change without notice We strive to reproduce product colors reasonably accurate Without prior written approval this document or any part of may not be reproduced in any form Jets Vacuumarator Helivac VC VOD CVS and Softsound are trademarks a...

Page 2: ...G 100mm H 200mm I 45mm J 45mm K Ø50 L 15mm M 170mm N 9mm O 20mm A 470mm Note Installation is to occur within the water barrier in line with local industry requirements and in compliance with all local state and federal wet room requirements Note the Air Overflow Valve shown in the dimension drawing may not be included in the tank delivery but may be purchased as an accessory ...

Page 3: ...sing Sequence 1 Level Sensor ℱ DEACTIVATES 2 Controller ℰ DEACTIVATES 3 Valve ℯ CLOSES 4 Suction Pipe EMPTIES 5 Outlet C FLOW STOPS Result Grey water enters the tank until the determined level is reached Grey water is sucked from the tank to the outlet Chemicals and Detergents The following information is for Grey Water Interface Units which have washing machines kitchen sinks showers etc connecte...

Page 4: ...anding by that can render aid if needed If extended periods of time are required for tank inspections repairs appropriate respiratory equipment PPE should be utilized 9 2 Danger Disease Hazards Effluent is a common mode of transmission for parasitic organisms Some of these may be pathogenic meaning that they may have the capability of causing serious communicable disease Good personal hygiene use ...

Page 5: ... A Interchangable connection for the Inlet gravity inlet from the source Air Overflow Note that an air overflow valve is required A suitable valve is available in Jets product range Alternatively the tank may be vented for example above roof height B Outlet Optional C For installations with LAH Level Alarm High D For installations with a VTS VIP Controller Refer to the tanks technical information ...

Page 6: ...t routine inspection and cleaning inside and outside of the tank be carried out a minimum of one time each third year depending on frequency of use Service and Maintenance Technical Assistance Jets Vacuum AS provides all customers with 24 hour worldwide technical assistance For urgent matters please contact Jets Vacuum AS service department directly at 47 70039100 For other matters please contact ...

Page 7: ...Cause Action Tank content is not discharged No vacuum Check sufficient vacuum is being generated Discharge time is too short Increase the discharge time up to a Maximum of 2 seconds after the tank is empty Valve is blocked due to debris Remove the debris Defective non return valve Clean or replace the non return valve Leaks in the vacuum hose s on the valve Replace the hose s or check that hose s ...

Reviews: