Electrical Requirements

Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in 

conformance with National Electrical Code, ANSI/NFPA 70 (latest 

edition) or CSA Standards C22.1-94, Canadian Electrical Code, 

Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes 

and ordinances.
If codes permit and a separate ground wire is used, it is 

recommended that a qualified electrician determine that  

the ground path is adequate.
A copy of the above code standards can be obtained from:

National Fire Protection Association 

1 Batterymarch Park 

Quincy, MA 02169-7471

CSA International 

8501 East Pleasant Valley Road 

Cleveland, OH 44131-5575

 

A 120-volt, 60 Hz., AC-only, 15-amp, fused electrical  

circuit is required.

 

If the house has aluminum wiring, follow the procedure 

below:

1. 

Connect a section of solid copper wire to the pigtail leads.

2. 

Connect the aluminum wiring to the added section 

of copper wire using special connectors and/or tools 

designed and UL listed for joining copper to aluminum.

Follow the electrical connector manufacturer's recommended 

procedure. Aluminum/copper connection must conform with 

local codes and industry accepted wiring practices.

 

Wire sizes and connections must conform with the rating of 

the appliance as specified on the model/serial/rating plate. 

The model/serial/rating plate is located on the front of the 

downdraft vent above the wiring box cover.

 

Wire sizes must conform to the requirements of the National 

Electrical Code, ANSI/NFPA 70 (latest edition) or CSA 

Standards C22. 1-94, Canadian Electrical Code, Part 1 and 

C22.2 No. 0-M91 (latest edition) and all local codes and 

ordinances.

Venting Requirements

IMPORTANT:

 Make sure there is proper clearance within the wall 

or floor before making exhaust vent cutouts.

 

Use heavy (rigid) metal vent.

 

Venting system must terminate to the outside.

 

Do not terminate the vent system in an attic or other 

enclosed area.

 

Do not use 4" (10.2 cm) laundry-type wall caps.

 

Do not install 2 elbows together.

 

Do not use plastic or metal foil vent.

 

The length of vent system and number of elbows should  

be kept to a minimum to provide efficient performance.

 

Use no more than three 90° elbows.

 

Make sure there is a minimum of 24" (61 cm) of straight vent 

between the elbows if more than one elbow is used.

 

Use clamps or duct tape to seal all joints in the vent system.

 

Use caulking tape to seal the exterior wall or floor opening 

around cap.

 

Do not cut joist or stud. If vent cutout falls over a joist  

or stud, a supporting frame must be constructed.

Flexible metal vent is not recommended. If it is used, calculate 

each foot of flexible vent as 2 ft (0.6 m) of rigid metal vent.
Flexible elbows count twice as much as standard elbows.

Recommended vent system length:

For either interior-mounted or exterior-mounted blower 

installations, the vent system length should not exceed the 

maximum lengths listed in the “Maximum Length of Vent 

System” chart. See “Calculating Vent System Length” in the 

“Venting Methods” section in the Installation Instructions.

Cold Weather Installations

An additional backdraft damper should be installed to minimize 

backward cold airflow and a thermal break should be installed 

to minimize conduction of outside temperatures as part of the 

vent system. The damper should be on the cold air side of the 

thermal break.
The break should be as close as possible to where the vent 

system enters the heated portion of the house.

Makeup Air

Local building codes may require the use of makeup air systems 

when using ventilation systems greater than specified CFM of 

air movement. The specified CFM varies from locale to locale. 

Consult your HVAC professional for specific requirements in  

your area.

Summary of Contents for JXD7036Y Series

Page 1: ...In Canada call 1 800 JENNAIR 1 800 536 6247 or visit our website at www jennair ca Instructions d installation et Guide d utilisation et d entretien Pour des questions propos des caract ristiques du f...

Page 2: ...U S A 20 In Canada 20 Accessories 20 WARRANTY 21 S CURIT DU SYST ME DE VENTILATION 22 EXIGENCES D INSTALLATION 24 Outils et pi ces 24 Exigences d emplacement 24 Sp cifications lectriques 27 Exigences...

Page 3: ...his manual and on your appliance Always read and obey all safety messages This is the safety alert symbol This symbol alerts you to potential hazards that can kill or hurt you and others All safety me...

Page 4: ...4 IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS...

Page 5: ...as windows doors and strong heating vents or fans Cabinet opening dimensions that are shown must be used Given dimensions provide minimum clearance Consult the cooktop manufacturer installation instru...

Page 6: ...Range Hood Front of Range Hood Top trim widths 30 76 2 cm 36 91 4 cm 13 34 3 cm retractable vent height 27 68 6 cm for 30 76 2 cm vent 33 83 8 cm for 36 91 4 cm vent 16 42 0 cm 10 25 4 cm 2 5 4 cm 28...

Page 7: ...the countertop before making any cutouts See the Installation Instructions that came with your cooktop for complete cutout dimensions location dimensions and installation details A B C E H D I G F A...

Page 8: ...or before making exhaust vent cutouts Use heavy rigid metal vent Venting system must terminate to the outside Do not terminate the vent system in an attic or other enclosed area Do not use 4 10 2 cm l...

Page 9: ...VC Sewer Pipe Front Mounted Blower Motor Standard Rear Mounted Blower Motor Calculating Vent System Length 3 x 10 8 3 cm x 25 4 cm rectangular vent is required from the blower motor box It can be tran...

Page 10: ...n the maximum vent length of 35 ft 8 9 m 2 90 elbow 10 0 ft 3 m 1 wall cap 0 0 ft 0 0 m 8 ft 2 4 m straight 8 0 ft 2 4 m Transition 4 5 ft 1 4 m Length of 6 15 2 cm or 31 4 x 10 8 3 cm x 25 4 cm syste...

Page 11: ...om the cover plate mounted to the face of the motor box and set them aside 3 Slide the cover plate up and slip it over the keyhole slot shoulder screws Set the cover aside 4 Remove 4 screws from the b...

Page 12: ...slots Disconnect wire connection from blower motor and set blower motor box aside 3 Remove 6 screws from the mounting flange of the 6 4 mm deep cover B A C A A A Screws 7 B Keyhole slot shoulder scre...

Page 13: ...ar of the vent box and reconnect the wire connection to the blower motor 12 Mount the blower motor box to the vent box and secure using the 6 screws previously removed 13 Mount the 43 4 12 0 cm cover...

Page 14: ...mm screws A A B A 3 5 x 9 5 mm screws B 3 x 10 8 3 cm x 25 4 cm backdraft damper A B A 3 5 x 9 5 mm screws B 6 15 2 cm round vent transition with damper 2 Remove 4 screws attaching the terminal box co...

Page 15: ...ntertop when tightened D A B C A Vent box B Undercounter mounting bracket C Keyhole slots D Guide tabs A B C A Screws B Backsplash C Countertop 7 Check that the downdraft vent is level as shown below...

Page 16: ...he button on the top of the downdraft vent for a few seconds The retractable section of the downdraft vent will rise and the blower will be able to start using the control slider Remove any protective...

Page 17: ...rating 2 Immediately turn off the downdraft vent at the speed control located on the right hand side of the downdraft vent 3 Turn off the power supply to the downdraft vent at the circuit breaker box...

Page 18: ...t will go to activate the microswitch behind the filter Has the Start button been pressed for at least 3 seconds Push and hold the button on the top of the downdraft vent for at least 3 seconds to com...

Page 19: ...C 1 8 5 4 3 6 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 Motor Specifications Power supply 120 VAC Frequency 60 Hz Wattage rating 420 W Amperage 3 7 A Motor Resistance BU WH 21 6 Ohms BU RD 18 Ohms BU GY...

Page 20: ...ssistance If you need further assistance you can write to Jenn Air Appliances with any questions or concerns at Jenn Air Brand Home Appliances Customer eXperience Center 553 Benson Road Benton Harbor...

Page 21: ...tc 5 Defects or damage caused by the use of non genuine Jenn Air parts or accessories 6 Conversion of products from natural gas or L P gas 7 Damage from accident misuse abuse fire floods acts of God o...

Page 22: ...re appareil m nager Assurez vous de toujours lire tous les messages de s curit et de vous y conformer AVERTISSEMENT DANGER Voici le symbole d alerte de s curit Ce symbole d alerte de s curit vous sign...

Page 23: ...ue d incendie et vacuer ad quatement les gaz veiller acheminer l air aspir par un conduit jusqu l ext rieur ne pas d charger l air aspir dans un espace vide du b timent comme une cavit murale un plafo...

Page 24: ...ecter les dimensions indiqu es pour les ouvertures d couper dans les placards Ces dimensions tiennent compte des valeurs minimales des d gagements de s paration Avant d effectuer des d coupes consulte...

Page 25: ...uisini re Largeurs de la garniture sup rieure 30 76 2 cm 36 91 4 cm 13 34 3 cm hauteur de l vacuation r tractable 27 68 6 cm pour une vacuation de 30 76 2 cm 33 83 8 cm pour une vacuation de 36 91 4 c...

Page 26: ...voir les illustrations suivantes Pour viter une erreur avant de d couper une ouverture il est recommand de tracer le p rim tre de la table de cuisson et des ouvertures d couper sur le plan de travail...

Page 27: ...rger l air l ext rieur Ne pas terminer le syst me d extraction dans un grenier ou dans un autre espace ferm Ne pas utiliser une bouche de d charge murale de 4 10 2 cm normalement utilis e pour un quip...

Page 28: ...rs le bas B C A A vacuation vers le bas B vacuation gauche C vacuation droite Configuration en lot Circuit d vacuation install sous une dalle de b ton utilisation de conduit de PVC pour gout Ventilate...

Page 29: ...d 90 de 6 15 2 cm vers 31 4 x 10 8 3 cm x 25 4 cm 5 0 pi 1 5 m Exemple de circuit d vacuation Dans l exemple suivant la longueur effective du circuit est inf rieure au maximum de 35 pi 8 9 m 2 coudes...

Page 30: ...droit 1 deux personnes ou plus poser l arri re du syst me d extraction par le bas face au sol 2 Retirer les 4 vis du couvercle mont l avant de la caisse du moteur et les mettre de c t 3 Faire glisser...

Page 31: ...blage du ventilateur et mettre de c t la caisse du ventilateur 3 ter les 6 vis du rebord de montage du couvercle d paisseur 1 4 6 4 mm B A C A A A Vis 7 B Vis paulement pour encoches en trou de serrur...

Page 32: ...her le c blage au ventilateur Monter la caisse du ventilateur sur la caisse du syst me d extraction et la fixer l aide des 6 vis pr c demment retir es A B A Platine de montage du c ble B OEillet 12 Mo...

Page 33: ...mm A A B A Vis de 3 5 x 9 5 mm B Clapet anti retour de 3 x 10 8 3 cm x 25 4 cm A B A Vis de 3 5 x 9 5 mm B Raccord de transition rond de 6 15 2 cm avec clapet 2 ter les 4 vis du couvercle du bo tier d...

Page 34: ...plan de travail C Orifices en trou de serrure D Guides A B C A Vis B Panneau anti claboussure C Plan de travail 7 V rifier que le syst me d extraction par le bas est d aplomb vertical comme illustr De...

Page 35: ...e bas La section r tractable du syst me d extraction par le bas se d ploie et le ventilateur peut tre mis en marche l aide du curseur de commande Retirer le film de protection et utiliser un nettoyant...

Page 36: ...menter le r glage de la flamme de la table de cuisson pour ce br leur Utilisation du syst me d extraction par le bas Utilisation 1 Appuyer pendant quelques secondes sur le bouton au sommet de l appare...

Page 37: ...e vers le bas 2 Laver le s filtre s m tallique s selon le besoin au lave vaisselle ou avec une solution de d tergent chaude 3 R installer le filtre en s assurant que les poign es ressort sont orient e...

Page 38: ...ifier que le syst me d extraction est enti rement d ploy Les filtres sont ils bien install s Pousser le plus possible le filtre vers l int rieur pour activer le contact situ derri re le filtre Le curs...

Page 39: ...du moteur Alimentation 120 VCA Fr quence 60 Hz Puissance nominale 420 W Intensit 3 7 A R sistance du moteur BU BL 21 6 ohms BU R 18 ohms BU GRIS 14 3 ohms BU N 9 8 ohms Fonctionnement du commutateur d...

Page 40: ...assistance vous pouvez crire Jenn Air en soumettant toute question ou tout probl me Jenn Air Brand Home Appliances Customer eXperience Center 553 Benson Road Benton Harbor MI 49022 2692 N oubliez pas...

Page 41: ...ant de l utilisation de pi ces ou accessoires Jenn Air non authentiques 6 Conversion de votre produit du gaz naturel ou du gaz de p trole liqu fi 7 Dommages caus s par accident m susage abus incendie...

Page 42: ...42 Notes...

Page 43: ...43 Notes...

Page 44: ...W10342490F 2016 Jenn Air Used under license in Canada All rights reserved Utilis sous licence au Canada Tous droits r serv s 4 16...

Reviews: