© JBG-HT (v.2.0)
21
SERVICE MANUAL
– HEAT PUMP
5.4. Heater
Enabled
: enales the heater to operate in CH mode.
Alarm Input EN
: enables the display of information
about thermal protection.
Hours
: heater run time
Next thr
: Time after which the component should be
replaced/maintained
Reset h.
: switch to reset the counter
Status
: current status of the heater
Manual
: option to turn the heater on/off manually, or
set automatic mode
Heater modes
:
Integration
: continuous support of the compressor
in CH mode.
Substitution
: replacement of the compressor in CH
mode.
Integration by alarm
: integration during alarm in CH
mode.
Boost
: intelligent support of the compressor in CH
mode.
Thresh
: the ambient temperature threshold, below
which the heater in CH mode can start in compressor
support mode
Diff
: after returning to the higher Diff tem-
perature, the heater cannot start up
Delay
: delay for the heater to start
Act. Level
: the ambient temperature threshold, below
which the heater in CH mode can start in intelligent
compressor support mode.
Check Time
: the period of time when the tempera-
ture increment is tested
Delta Value
: the temperature increment during
Check Time below which the heater will start for
Timeout
Timeout
: the time to start the heater if requested
Act
: current return temperature value
Last
: last measured value of return temperature at
the end of Check Time
Status
: the status of the heater activation