background image

page 4

www.jayline.co.nz

NOVEMBER 2016

Installation requirements for Jayline IS550 fi replace insert and fl ue system, where timber framing 
is less than 50mm from the chimney structure.

The installation should be carried out by a suitably qualifi ed installation technician who will ensure the 
following:
*   The minimum clearances determined by tests in accordance with AS/NZS 2918:2001 are complied 
 

with to prevent overheating of nearby combustibles.

*   The minimum opening size of 590mm wide x 570mm high x 481mm deep is available when the 
 

fi rebricks are removed.  These measurements exclude the 30mm insulating blanket fi tted to the 

 

sides, back & top of the outer casing.  Please make an allowance for the blanket, as it must be used 

 

to ensure maximum effi  ciency.

*   If the fi replace opening is in a heat sensitive wall, a non-metallic heat resistant material shall 
 

extend not less than 50mm beyond each side of the appliance and 150mm beyond the top of 

 

the appliance.

*   A clearance of at least 1 metre between the front of the appliance and building structure, or any 
 

other substantial immovable object.

*   The ash fl oor protector of non-combustible material is provided, extending not less than the 
 

dimensions shown in the specifi cation sheets for this appliance.

*   A fi replace shall not be connected to a fl ue common with an open fi replace.
*   The fl ue pipe must be fi tted up to, and above the chimney top.  The space between the fl ue pipe 
 

and the chimney must be vented at the top.  The area of this vent must not be less than 10,000mm².  

 

The vent must be fi tted with means to prevent signifi cant water and debris from entering the cavity, 

 

or vent area.  The fl ue must be free to move up & down 25mm or more due to the expansion and 

 

contraction of the fl ue under normal use.

*   Seismic restraints consisting of two M6 x 50mm dynabolts (or equivalent) are fi tted through 
 

the front edge of the outer cabinet base brackets, and into the masonry base below, before the 

 

fascia is fi tted.

INSTALLATION 

Establish the masonry cavity is suitable as above.
*   Unpack the fi re box / outer casing and fascia and check there is no damage. 
*   Read the specifi cation sheets and installation instructions.
*   With the top front outer case panel removed, and the door removed, slide the fi re box / outer case
 

into the prepared cavity and centralise (including the outer case insulating blanket).

*   Ensure the folded edges of the outer case are fl ush with the front of the cavity, allowing for any 
 

fi breglass seal that may be required as an air seal between the fascia and masonry.

*   The S/S fl ue pipes must be sealed & fastened with at least 3 x S/S rivets each (follow the fl ue 
 

manufacturer’s instructions) .

*   Lower the fl ue system down the cavity and into the fl ue spigot using a hi-temp sealant (an off set 
 

may be required in some cases).

*   Drill and secure the fl ue pipe into the fl ue spigot using a S/S self-tapping screw.
*   Re-check the outer case is still fl ush with the front of the cavity, then drill & secure the seismic 
 

restraints as above.

Summary of Contents for IS550

Page 1: ...JAYLINE IS550 INSERT WOOD FIRE INSTALLATION OPERATION INSTRUCTIONS Please leave this information with the appliance NOVEMBER 2016...

Page 2: ...___________ ______________________________________________________________________________ EMAIL ________________________________________ PHONE ________________________ MODEL _________________________...

Page 3: ...nd standard AS NZS 2918 2001 As safety and emissions performance can be affected by altering the appliance no modifications are allowed without the written permission from the manufacturer PRE INSTALL...

Page 4: ...top The space between the flue pipe and the chimney must be vented at the top The area of this vent must not be less than 10 000mm The vent must be fitted with means to prevent significant water and d...

Page 5: ...ontinue to the minimum length of 4 6m from the top of the floor protector to the cowl Flue exiting more than 3 metres from the ridgeline must terminate no less than 1 metre above the roof penetration...

Page 6: ...O BE IN BREACH OF THE APPROVAL GRANTED FOR COMPLIANCE WITH AN NZS 4013 1999 3 PLEASE ENSURE THAT ONLY COMPONENTS APPROVED BY JAYLINE ARE USED FOR THE INSTALLATION as substitutes may adversely affect p...

Page 7: ...quantity of finely split dry soft wood kindling in a variety of sizes and 4 Seasoned firewood split into a range of piece sizes The first step is to crumple half a dozen sheets of newspaper and put t...

Page 8: ...than five pieces of small firewood on the embers Open the air inlets fully and close the door If everything is just right fast ignition of the new load should be expected Allow the fire to burn with...

Page 9: ...spring and autumn To build a small hot fire rake the embers evenly in the firebox and place several small pieces of firewood on it The bottom layer should be placed to ensure that combustion air can f...

Page 10: ...oon after refuelling or not raking the charcoal to the combustion air inlet or turning the combustion air down too low to support efficient combustion or all of the above REMEMBER THE HOTTER THE FIRE...

Page 11: ...e negative pressure in the house when they are operating Because new houses are tightly sealed there are few holes to allow replacement air to enter and the house pressure becomes negative This negati...

Page 12: ...he stacks of firewood should be in an open area so that air can circulate through them During the summer as warm breezes flow through the stacks carrying away the evaporating water the moisture conten...

Page 13: ...s will eventually need replacing DOORS Check all gaskets used for wear and replace if necessary Adjust door fitting if required LUBRICATION All moving parts should be lubricated with graphite grease e...

Page 14: ...nt cleaning advice should be sought to investigate the installation and the operation of the fire Flue pipes can deteriorate very quickly with incorrect firing CONSUMABLES Some parts of your Jayline f...

Page 15: ...IQUIDS OR AEROSOLS IN THE VICINITY OF THIS APPLIANCE WHEN IT IS OPERATING WARNING DO NOT STORE FUEL WITHIN APPLIANCE INSTALLATION CLEARANCES WARNING OPEN AIR CONTROL BEFORE OPENING FIRE DOOR CAUTION T...

Page 16: ...essary At the same time any other minor potential problems can be detected and corrected before they turn into major ones We think this is a small price to pay to ensure your heater is kept in peak co...

Page 17: ...irst instance should be directed to the store of purchase Any repairs undertaken without the manufacturer s authority will render the guarantee void Water boosters must be a Jayline model specified wi...

Reviews: