Figure 14

Floor Protector Requirements

Height of top of floor 
protector above the 
exposed floor (mm)

Projection (mm)
 From glass

Remember the glass extends 
80mm from the face of the 9mm 
Promina board

Projection (mm)
From 9mm Promina board 

0

525

605

20

480

560

40

427

507

60

380

460

Summary of Contents for IS550

Page 1: ...JAYLINE IS550 ZERO CLEARANCE CABINET INSTALLATION INSTRUCTIONS August 2014...

Page 2: ...qualified installation technician Your dealer or heating specialist will be able to help with recommendations as well as advice on permits consents required for the installation in your area Please e...

Page 3: ...imber and lining products Floor Protector Hearth materials Vent Vents Other items as required Various fasteners products dependant on build type Step 2 Venting An air vent or vents are required on the...

Page 4: ...cladding should only be fitted once the ZC Cabinet firebox and flue system has been fitted and checked The remaining enclosure cladding can be standard cladding materials Please be aware the wall surf...

Page 5: ...th the front framing timber and are central within the cavity Drill screw the ZC Cabinet to the floor within 50mm of each corner Remove the door and air control knob from the firebox Fit the firebox i...

Page 6: ...ne the type of cowl and casing cover being used This will also dictate the type of venting to use refer to fig 3 4 Once the flue system has been fitted and checked a 25 x 25 x 5mm angle iron support o...

Page 7: ...s Height of top of floor protector above the exposed floor mm Projection mm From glass Remember the glass extends 80mm from the face of the 9mm Promina board Projection mm From 9mm Promina board 0 525...

Page 8: ...OSURE AND MUST BE VENTED TO OUTSIDE AIR THE BOTTOM EDGE OF THE LOWER VENT OR VENTS MUST BE NO MORE THAN 100mm ABOVE THE FLOOR AND HAVE A MINIMUM SURFACE AREA OF 10 000 SQ mm E G 200 X 100mm THE MESHED...

Page 9: ...Outer Liner 200mm Inner Liner Metal Flashing Non Combustible Top Plate e g 9mm Promina Board or thermal equivalent Height to suit Cowl Minimum FALSE CHIMNEY VENTED THROUGH 150 350 CASING COVER NOTE IT...

Page 10: ...q mm minimum e g 100mm x 200mm 25mm gap to combustible material minimum Non Combustible Top Plate e g 9mm Promina Board or thermal equivalent 200mm Inner Liner Minimum FALSE CHIMNEY VENTED THROUGH SID...

Page 11: ...850mm Minimum FRAMING REQUIREMENTS AS PER NZS 3604 SHOWING MINIMUM REQUIREMENTS FIGURE 7 645mm Minimum C L 545mm Minimum FIGURE 5 FIGURE 6...

Page 12: ...THER CLADDING ABOVE OR BESIDE THE PROMINA BOARD CAN BE STANDARD MATERIALS Figure 9 80mm C L 365mm MINIMUM CLEARANCE 25mm TO COMBUSTIBLES MINIMUM CLEARANCE 25mm TO COMBUSTIBLES MEASURED FROM THE GLASS...

Page 13: ...750mm 850mm MINIMUM 1160mm ABOVE FLOOR PROTECTOR Figure 11 DETAIL A SCALE 1 6 DETAIL B SCALE 1 6 2 X THERMAL INSULATION STRIPS MINIMUM ABOVE THE FLOOR PROTECTOR Figure 10...

Page 14: ...20mm 9mm Promina Board or thermal equivalent To be fitted to timber framing directly behind the fascia 9mm Promina Board or thermal equivalent 2 layers required Fitted directly below the ZC Cabinet on...

Page 15: ...m or heat shielding will be required IF HEAT SHIELDING IS REQUIRED PLEASE REFER TO AS NZS 2918 2001 150mm Maximum or heat shielding will be required 100mm Maximum or heat shielding will be required Fi...