Congratulations on the purchase of your Jayline IS550 wood fire and ZC Cabinet.

Introduction

Please read the entire manual before commencing the installation.

The Jayline IS550 wood fire ZC Cabinet system have been tested together and complies with 
AS/NZS 2918:2001, AS/NZS 4012:1999 & AS/NZS 4013:1999 when installed in accordance with this 
manual.  Correct installation is critical to the safe operation and performance of this fire.

For your safety, the building regulatory Authorities in New Zealand require any wood fire installation 
to comply with Installation Standard AS/NZS 2918:2001.  They may also have local requirements in 
addition to those in the Standard.  Check with your local Building Authority before commencing the 
installation to find if you require a Building Consent and whether there are extra requirements.  

As the safety and emission performance can be affected by altering the appliance, no  
modifications are allowed without written permission from the manufacturer.

Jayline recommends the installation only be carried out by a suitably qualified installation technician. 
Your dealer or heating specialist will be able to help with recommendations as well as advice on 
permits / consents required for the installation in your area.  Please ensure you have all relevant 
permits prior to installation.

CAUTION!

Inspect the house construction at the proposed installation position to verify the flue / liner system will 
pass through the house without requiring the removal of essential roof or ceiling support beams.  A 
minimum overall length of 4600mm, of flue pipes and casings must be used above the floor of the 
appliance to ensure the correct performance of this fire and ZC Cabinet installation.  This comprises 
of 150mm diameter flue pipes, 200mm diameter inner liners and 250mm diameter outer liners. 
Deviation from this may alter the heaters performance and may nullify the Jayline warranty if the flue 
is excessively long or short.  If in doubt, contact your Jayline dealer.

The ZC Cabinet must be secured to the floor / floor protector prior to the firebox being fitted.

All flue and liner joints must be riveted.  The bottom of the flue must be fully sealed into the 
flue spigot and secured through the hole in the spigot.

The fire must be bolted securely to the floor to comply with the seismic restraint provisions of 
AS/NZS 2918:2001.

Summary of Contents for IS550

Page 1: ...JAYLINE IS550 ZERO CLEARANCE CABINET INSTALLATION INSTRUCTIONS August 2014...

Page 2: ...qualified installation technician Your dealer or heating specialist will be able to help with recommendations as well as advice on permits consents required for the installation in your area Please e...

Page 3: ...imber and lining products Floor Protector Hearth materials Vent Vents Other items as required Various fasteners products dependant on build type Step 2 Venting An air vent or vents are required on the...

Page 4: ...cladding should only be fitted once the ZC Cabinet firebox and flue system has been fitted and checked The remaining enclosure cladding can be standard cladding materials Please be aware the wall surf...

Page 5: ...th the front framing timber and are central within the cavity Drill screw the ZC Cabinet to the floor within 50mm of each corner Remove the door and air control knob from the firebox Fit the firebox i...

Page 6: ...ne the type of cowl and casing cover being used This will also dictate the type of venting to use refer to fig 3 4 Once the flue system has been fitted and checked a 25 x 25 x 5mm angle iron support o...

Page 7: ...s Height of top of floor protector above the exposed floor mm Projection mm From glass Remember the glass extends 80mm from the face of the 9mm Promina board Projection mm From 9mm Promina board 0 525...

Page 8: ...OSURE AND MUST BE VENTED TO OUTSIDE AIR THE BOTTOM EDGE OF THE LOWER VENT OR VENTS MUST BE NO MORE THAN 100mm ABOVE THE FLOOR AND HAVE A MINIMUM SURFACE AREA OF 10 000 SQ mm E G 200 X 100mm THE MESHED...

Page 9: ...Outer Liner 200mm Inner Liner Metal Flashing Non Combustible Top Plate e g 9mm Promina Board or thermal equivalent Height to suit Cowl Minimum FALSE CHIMNEY VENTED THROUGH 150 350 CASING COVER NOTE IT...

Page 10: ...q mm minimum e g 100mm x 200mm 25mm gap to combustible material minimum Non Combustible Top Plate e g 9mm Promina Board or thermal equivalent 200mm Inner Liner Minimum FALSE CHIMNEY VENTED THROUGH SID...

Page 11: ...850mm Minimum FRAMING REQUIREMENTS AS PER NZS 3604 SHOWING MINIMUM REQUIREMENTS FIGURE 7 645mm Minimum C L 545mm Minimum FIGURE 5 FIGURE 6...

Page 12: ...THER CLADDING ABOVE OR BESIDE THE PROMINA BOARD CAN BE STANDARD MATERIALS Figure 9 80mm C L 365mm MINIMUM CLEARANCE 25mm TO COMBUSTIBLES MINIMUM CLEARANCE 25mm TO COMBUSTIBLES MEASURED FROM THE GLASS...

Page 13: ...750mm 850mm MINIMUM 1160mm ABOVE FLOOR PROTECTOR Figure 11 DETAIL A SCALE 1 6 DETAIL B SCALE 1 6 2 X THERMAL INSULATION STRIPS MINIMUM ABOVE THE FLOOR PROTECTOR Figure 10...

Page 14: ...20mm 9mm Promina Board or thermal equivalent To be fitted to timber framing directly behind the fascia 9mm Promina Board or thermal equivalent 2 layers required Fitted directly below the ZC Cabinet on...

Page 15: ...m or heat shielding will be required IF HEAT SHIELDING IS REQUIRED PLEASE REFER TO AS NZS 2918 2001 150mm Maximum or heat shielding will be required 100mm Maximum or heat shielding will be required Fi...