30
Password
In order to make it difficult to accidentally
change the programmed data using the key-
board or the WEB interface, a password and a
password mode can be programmed. It is only
possible to switch to the pramming menus
and to change the programmed data after the
password has been correctly entered.
In the factory, no password (0000) and no
password mode (0000) are preset. In this
case the password query is skipped.
If a
password has been changed and
is no longer known, the device must
be sent to the manufacturer.
Setting range:
Password
= 0 .. 9999
Password mode = 0, 1, 2, 128, 129, 130
Factory setting:
Password
= 0
Password mode = 0
Password = 0000 => no password
= 1-9999 => with password
Configuration
Password mode
The password mode controls access to the
UMG507 over the ethernet. The UMG507 has
six password modes:
0 - Anybody can access the UMG507 over
the ethernet.
1 - Only the host names stored in the
UMG507 can access the UMG507 over the
ethernet.
2 - The UMG507 can only be accessed over
the ethernet with a password.
0/1/2 + 128 =>
128, 129, 130
If 128 is added to the password mode 0, 1 or
2 the password is queried for each change to
a configuation side.
Password mode
CONF
1
Press 2 times.
The
Select text
flashes.
The current
transfomer set-
ting is displayed.
1
Press once.
The first digit
flashes.
Program password
SELECT
CT
CONF
A
A
2
Press once.
The
Select text disappears.
The device is in
programming mode.
3
Press 5 times.
Switch to the password menu
PASS.
Change password and password mode.
Change digit.
3
Select digit.
1
CONF
Password