15
S0 Pulse input
Each input can also be used as an S0 pulse
input to DIN EN62053-31. An external auxil-
iary voltage of 20..28V DC and an external
1.5kOhm resistor each is required for this.
Fig.: Example for connection of an S0 pulse
generator at the digital input 6
.
3,9V
4k
4
Digital
Input 1
UMG507
Digital inputs 1-6
3,9V
3,9V
4k
5
Digital
Input 2
3,9V
4k
6
Digital
Input 3
4k
7
Digital
Input 4
4k
8
Digital
Input 5
3,9V
3,9V
4k
9
10
Digital
Input 6
S0 Pulse
generator
1,5k
+
-
24V
DC
Installation
Digital inputs
The UMG507 has a total of 6 digital inputs
which can be connected to transducers. An
input signal is detected at a digital input if a
voltage of at least 10V and maximum 28V is
applied. A current of at least 1mA and maxi-
mum 6mA then flows.
Fig.: Example for connection of the external
main switching contacts S1 and S2 to the
digital inputs 5 and 6
.
3,9V
4k
4
Digital
Input 1
UMG507
Digital inputs 1-6
3,9V
24V
DC
+
-
S2
3,9V
4k
5
Digital
Input 2
3,9V
4k
6
Digital
Input 3
4k
7
Digital
Input 4
4k
8
Digital
Input 5
3,9V
3,9V
4k
9
10
Digital
Input 6
S1