"Periodic commands"
If the device receives periodic Modbus com-
mands for synchronization, there are different
scenarios.
Scenario "Command outside the capture
time"
:
·Summed intermediate values are set to 0
·The time is set to 0 (new relative zero point)
·There is no value calculation
Pulse
Time base
end
Capture time
Scenario "Command according to time base,
but within the capture time"
·Summed intermediate values are set to 0
·The time is set to 0 (new relative zero point)
·There is no value calculation
Pulse
Time base
end
Scenario "Command before time base within
the capture time"
·Perform value calculation now
·The time is set to 0 (new relative zero point)
·Delete summed intermediate values
Pulse
Time base
end
INFORMATION
With periodic synchronization, the time is synchro-
nized with each command!
INFORMATION
The GridVis
®
software enables user-friendly config-
uration of the drag indicator functionality.
Modbus
address
Function
Setting range
820
Set trigger flag for
drag indicator syn-
chronization
0 ...1
821
Time base in seconds
60 .. 65535
822
Enable flag of the
Modbus trigger
0 .. 1
823
Capture time in sec-
onds
0 .. 254
Fig.: Principle of synchronization with "Periodic
commands"
Capture time
Capture time
Capture time
Capture time
Time base
Time base
Time base
Command history
Synchronization principle
Resynchronization
Relative
zero point
2 minutes