Supply voltage
The device obtains the supply voltage from the measured voltage.
Supply from 1st phase
115 - 277 V (+-10%), 50/60 Hz
Supply from 3 phases
80 - 277 V (+-10%), 50/60 Hz
Power consumption
max. 1.5 VA
Voltage measurement
3-phase 4-wire systems with nominal voltages (L-N/L-L)
max. 277 V/480 V
Networks
Measurement in TT and TN networks
Rated surge voltage
4 kV
Protection of the voltage measurement
1 - 10 A tripping characteristic B, (with IEC/UL approval)
Overvoltage category
300 V CAT III
Resolution
0.01 V
Crest factor
2 (relative to 240 Vrms)
Sampling frequency
5.4 kHz
Frequency of the fundamental oscillation
- Resolution
45 Hz .. 65 Hz
0.001 Hz
Fourier analysis
1st-40th harmonic
Serial interface (RS485)
Protocol, Modbus RTU
Modbus RTU/Slave
Transmission rate
9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps,
Factory setting: automatic detection
Current measurement
Nominal current
5 A
Rated current
6 A
Crest factor
2 (relative to 6 Arms)
Resolution
0.1 mA
Measuring range
0.005 .. 6 Arms
Overvoltage category
300 V CAT II
Rated surge voltage
2 kV
Power consumption
approx. 0.2 VA (Ri = 5 mΩ)
Overload for 1 s
60 A (sinusoidal)
Sampling frequency
5.4 kHz/phase