Page 29
= Peak value
= Minimum value
= Supply
Configuration data
Description
Display
Setting range
Presettings
Current transformer, primary
CT
1A .. 10,0kA (../5A)
5A
1A .. 2,0kA (../1A)
Current transformer, secondary
CT
1A, 5A
5A
Voltage transformer, primary
Type plate, 196 .. 275V
VT
100V .. 60,0kV
400V
Typeplate, 98 .. 140V
VT
100V .. 60,0kV
200V
Type plate, 49 .. 76V
VT
100V .. 60,0kV
100V
Current transformer secondary
Type plate, 196 .. 275V
VT
400V (cannot be changed)
400V
Type plate, 98 .. 140V
VT
200V, 220V
200V
Type plate, 49 .. 76V
VT
100V, 110V
100V
Outputs (by choice)
K
x
Pulse output
K1, K2
K1, K2
Measured values
Reactive and real energy
K1=Real., K2=React.
Pulse valency
0,00(W/var)h .. 99,9k(W/var)h
K1=1,00Wh, K2=1,00varh
Switching output
K1, K2
-
Measured value
All values except energy
-
Exceeding
0,01 .. 20,0M
-
Underscoring
0,01 .. 20,0M
-
Minimum pulse width
0.05...2.00 sec.
0.05 sec.
Averaging time current
5, 10, .. 900 sec.
900 sec.
Averaging time power
5, 10, .. 900 sec.
900 sec.
Rotation time
0 .. 255
0=no rotation
Measured value rotation
see table
No measured value rotation
Measured value selection
see table
All measured value indicat.
LCD contrast
0 .. 15
7
Software Release
x.xx
x.xx
User password
000 .. 999
„000“ = no password
These specifications presuppose a yearly calibration and a warm up time of 10 minutes.
Used abbreviations:
rng = of measuring range
rdg = of measured value