Module 96-PA-RCM / 96-PA-RCM-EL
ATTENTION
A disconnected or defective module disrupts
the communication with the basic device and
leads to a device fault.
If communication between the basic device to
the module is lacking or faulty during operation,
a warning signal will appear on the display of the
basic device.
·
Disconnect your system (the basic device)
from the power supply prior to mounting the
module.
·
Check the positioning of the RCM module. If
necessary, apply slight pressure to press the
module onto the basic device until it audibly
snaps in.
·
Check the display of your basic device (if the
menu item
Residual current
is present, the
basic device has recognized the module).
·
If necessary, restart the basic device before
reinstallation (cf. section „8.3 Restarting the
·
If the measures indicated here are unsuc-
cessful, please contact our support team
(www.janitza.de).
·
If there is discernible damage, send the
device, component or module back to the
manufacturer in compliance with proper
transport conditions.
Fig. Example “Basic device warning alert when
communication to module is faulty”.
8.4 Module-relevant alarms
When there is an alarm, the following warning alert
appears:
When there is an alarm, the title bar of your device
display is shown in
red
with the time indicated. It
is also possible to activate blinking of the display
when there is an alarm using the Modbus editor or
the GridVis
®
software (see table below).
Pressing function button 5 displays a list of all
alarms that have occurred, regardless of from
which menu window it is pressed. In the alarm list,
alarms can be selected and deleted.
Once all alarms have been deleted, the device
closes the alarm list and goes to the last menu
window.
Alarm description
Display property
Warning limit value for RCM channel 1 exceeded
Alarm limit value for RCM channel 1 exceeded
Display blinks
Warning limit value for RCM channel 2 exceeded
Alarm limit value for RCM channel 2 exceeded
Display blinks
Overcurrent L4
Cable break on RCM channel 1
Cable break on RCM channel 2
No module communication for the last 10 seconds
Display blinks
Tab. Alarm list with module-relevant alarms
Module-relevant alarm list:
INFORMATION
·
Detailed information on alarms and warning
alerts can be found in the user manual of your
basic device.
·
A Modbus address list can be found in the
download area at www.janitza.de.