FBM-Serie
11
Bus address (DIP switches 1 to 6)
Each I/O module must be assigned a bus address. The I/O modules are all addressed as slaves.
There are a total of 64 bus addresses available (slave ID „1“ to slave ID „63“).
W
1
2
4
8
16
32
DIP
1
2
3
4
5
6
Address
ON
OFF
OFF
OFF
OFF
OFF
1
OFF
ON
OFF
OFF
OFF
OFF
2
ON
OFF
OFF
ON
OFF
ON
41
OFF
ON
OFF
ON
OFF
ON
42
ON
ON
ON
ON
ON
ON
63
Setting occurs as with a
binary number.
Parity
The parity must be established with serial communica-
tion. The following assignments are possible with the
fieldbus device:
DIP
7
8
Parity
OFF
OFF
NONE
ON
OFF
ODD
ON
ON
EVEN
Baud rate (DIP switches 9 and 10)
The speed for the data transmission (baud rate) must
also be established. There are four different settings
available for the baud rate:
DIP
9
10
SPEED
OFF
OFF
4800
ON
OFF
9600
OFF
ON
19200
ON
ON
38400