Janfire NH Burner Service Installation Manual 4.16.09 - Technical specifications are subject to change without prior
notice.
25(38
)
User Menu
Press “menu” button briefly to scroll through user menu.
Changes are made with “+” and “-“ buttons.
Save changes by pressing and holding “menu” for 3 seconds.
User menu
Status
Min value
Max value
This shows the present status information, it can show
errors or running status.
Target temp. °F
131/136/149
179/185/197
Is only shown when modulating output regulation is
activated. If outdoor temp sensor is active, no adjustment is
possible. Brackets are then shown around numbers.
<Start temp
→ Target temp ← Stop temp>
Pellets used
( x lb) y lb
Shows calculated pellet consumption. The control has two
counters, one resettable and a total consumption counter.
Use “menu” to reset reset counter to zero.
Select power level
xx MBTU
10
78
Select power level. Service menu #60 and #61 specifies
maximum power level and lower limit of selected power
level.
Selection of NH Burner Output Value when running
without modulating functions.
Ashscrape each
39 lb (0.000lb)
3
144
Every xx lbs (40 lbs (=18 kg) default value). The second
value shows actual consumption.
Volumeweight:
42.1 lb/ft3
31.2
49.9
Correct level (lbs/ft3) is supplied by pellet supplier or by
weighing.
Energyvalue:
7.42 MBTU/lb
(ENHV)
6.49
7.89
Your pellet supplier must supply the correct value
(MBTU/lbs) based on European Net Heat Value.
Shut down?
“Menu”@3sec=
Yes
Mode is used to remove ashes from the boiler. Running
down function runs in three sequences: begin cooling,
burning cup scraping and then combustion stop. Press and
hold “menu” button for more than 3 seconds activates this
mode. This function is shown only when the burner is in
operation.
Manual feeding*
(dosage auger)
This text is shown only when the burner has stopped
operation. Feature is used to manually fill the dosage auger
for the initial start-up.
Press and hold down the “+” button and the dosage auger
will run until the button is released.
Manual feeding*
(external auger)
This text is shown only when the burner has stopped
operation. Feature allows you to manually fill the feeder
auger and burner hopper at initial system operation or after
running out of pellets.
Press and hold down the “+” button and the external feed
auger will run until the button is released or when the level
meter in the burner filling tube is affected.
*These two parameters should only be used by the installing contractor at the initial start-up of the system.