HSO 2024 to HSO 2035 Installation, Operation and Maintenance Manual
Page 28 of 94
Publication 2-119
Issue 1.2 : 03/10
View With DIN Plug Removed
Specification
The power supply/amplifier must meet the following criteria:
Supply voltage = 12 to 28 V dc
Short-circuit current = 50 mA (minimum)
Transformer type = isolated
Approval = ATEX
When used in an Ex area the installation must be carried out
according to EU norm EN 60079-14 general terms and IEC 79-11
intrinsic safety ‘I’.
The equipment must be electrically connected via an approved or
certified galvanically isolated interface/zener barrier placed outside
the hazardous area. P Fuchs Ex barrier type KFD2-CR-
EX1.30.300 (illustrated) is recommended.
DIN Plug Connector
Safe Area
+ 24 V dc supply
1
Ex Area Zone 1
- 0 V dc (common)
2
or Zone 2
4 to 20 mA signal
3
No connection
Fig 6 HBLVDT External Wiring Connections for Explosion-Proof Version
Calibration Button
Red LED (Supply)
CE
0158
Ex
II 2G
DEMKO 04 ATEX 135657
EEx 1b IIC T5
Um: 28 V I
1
: 35 mA C
1
: 50
µ
F L
1
: 0.1 mH
Cable
Entry
DIN Plug
IP65
Slide valves
at maximum
load = 20 mA
Slide valves
at minimum
load = 4 mA
Discharge
End Cover
FW
154
FW
151
FW
153
FW
152
1
2
3
12
11
8
7
Supply
+ 24 V dc - 0 V dc
KFD2-CR-
EX1.30.300
Connections to J & E Hall
International Fridgewatch
2000 and 2100 Controllers
+ 24 V dc - 0 V dc
Supply
Green LED Digital Output Indication
Minimum
Maximum
Slide Valve Travel
‘Flashing’
Illuminated
Extinguished
95 %
4 to 20 mA Signal
Screw Cap Covering Calibration
Buttons and LEDs
Hex Head Socket Grubscrew
(one each side)
Electronics
Module